POINT BEACH NUCLEAR PLANT AOP-10A ABNORMAL OPERATING PROCEDURE SAFETY RELATED Revision 33 5/16/2002 SAFE SHUTDOWN - LOCAL CONTROL Page 12 of 7?

L~i S

I ACTION/EXPECTED RESPONSE I

RESPONSE NOT OBTAINED 39 Perform Local Actions Per Attachments For Selected Power Source

a.

DOS

  • Attachment A. DOS LOCAL ACTIONS
b. Third Reactor Operator
  • Attachment B, THIRD REACTOR OPERATOR LOCAL ACTIONS
c. Unit 1 Control Operator
  • Attachment C. UNIT 1 CONTROL OPERATOR LOCAL ACTIONS
d. Unit 2 Control Operator
  • Attachment D, UNIT 2 CONTROL OPERATOR LOCAL ACTIONS
  • 40 Maintain B S/G Level -

BETWEEN 300 AND 330 INCHES

a. Throttle auxiliary feed pump discharge

)

a 1AF-4000 (1LI-470A-1)

CAUTIONS

"* To prevent AFW pump damage. monitor and maintain minimum AFW discharge flow greater than 75 gpm or stop the affected AFW Pump as necessary to control SIG levels.

"* Changes in auxiliary feedwater flow must be carefully coordinated to prevent excessive changes in RCS temperature and pressure.

I' NOTE Unit 1 Control Operator should remain in the AFW pump room to control auxiliary feedwater flow to the steam generators as directed.

I I

I