April 1, 2003 Mr. Harold W. Keiser Chief Nuclear Officer & President PSEG Nuclear LLC - X04 Post Office Box 236 Hancocks Bridge, NJ 08038
SUBJECT:
HOPE CREEK GENERATING STATION - REQUEST FOR ADDITIONAL INFORMATION REGARDING USE OF CODE CASE N-566-2 (TAC NO. MB7836)
Dear Mr. Keiser:
By letter dated February 14, 2003, PSEG Nuclear, LLC requested relief from the requirements of sub-paragraph IWA-5250(a)(2) of Section XI of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code (ASME Code), 1989 Edition, in order to implement the alternative requirements of ASME Code Case N-566-2 at the Hope Creek Generating Station when leakage is detected at bolted connections. The U.S. Nuclear Regulatory Commission staff has begun its review of the proposed relief and requests that you answer the enclosed questions regarding your submittal. These questions were discussed with Mr. Howard Berrick of your staff in a telephone call on March 26, 2003.
In order that we may complete our review in a timely manner, we understand that you intend to submit your response to the enclosed request for additional information within 15 days of the date of this letter. If this is incorrect or if you have any questions, please do not hesitate to call.
I can be reached at (301) 415-1494.
Sincerely,
/RA/
George F. Wunder, Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-354
Enclosure:
As stated cc w/encl: See next page
ML030850359 OFFICE PDI-2/PM PDI-2/LA DE/EMCB PDI-2/SC NAME GWunder CRaynor SCoflin JClifford DATE 03/27/03 03-27-03 3/31/03 3/31/03
Hope Creek Generating Station cc:
Jeffrie J. Keenan, Esquire PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Hope Creek Resident Inspector U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038 Mr. David F. Garchow Vice President - Operations PSEG Nuclear - X10 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Gabor Salamon Manager - Nuclear Safety and Licensing PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Richard Hartung Electric Service Evaluation Board of Regulatory Commissioners 2 Gateway Center, Tenth Floor Newark, NJ 07102 Lower Alloways Creek Township c/o Mary O. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038
REQUEST FOR ADDITIONAL INFORMATION REGARDING USE OF CODE CASE N-566-2 HOPE CREEK GENERATING STATION, UNIT NO. 1 DOCKET NO. 50-354 Question 1: The request does not address what actions would be taken in the event that the evaluation of Code Case N-566-2, paragraphs (a) or (b) determines that the relevant condition cannot be accepted for continuing operation. Please specify what actions would be taken in this event and the requirements directing those actions, e.g., code, procedures.
Question 2: The relief request does not address what subsequent inspections would be performed in the event that the evaluation of Code Case N-566-2, paragraphs (a) or (b) determines that the relevant condition can be accepted for continuing service. This is of particular interest for Code Class 2 and 3 components. Please specify what actions would be taken in this event and the requirements directing those actions, e.g., code, procedures.