From:

Peter Tam To:

internet:donna.j.mitchell@ccnppi.com; INTERNet:getachew.tesfaye@ccnppi.com; internet:patricia.s.furio@ccnppi.com Date:

2/25/03 3:22PM

Subject:

Draft RAI FOR Calvert Cliffs, TAC MB7752 and MB7753 Pat:

Our reviewer, Allen Hiser, is reviewing your submittal dated February 18, 2003, and he has identified the following questions. Please call me to set up a phone call for the near future (later this afternoon, or tomorrow morning) to discuss these with with Hiser.

1. What is the justification that coverage up to 0.75 inches above the weld will provide an adequate level of quality and safety? In other words, provide justification that increasing the scope of inspection to 2 inches above the J-groove will not provide an increase in quality and safety. Are there residual stress data that indicates that 0.75 inches is a sufficient level above the weld, or is there any other basis that demonstrates an acceptable level of quality and safety for the restricted inspections?
2. With the proposed limits to the examination above the J-groove weld, how will the licensee provide "an assessment to determine if leakage has occurred in to the interference fit zone" of each nozzle?
3. Experience at St. Lucie identified inspection limitations that resulted in the loss of data for some axial locations on some nozzles. Does the licensee anticipate similar issues at Calvert, and if so, what are their plans to demonstrate that the inspection coverage was adequate?

This email does not formally convey an NRC staff position, nor does it formally request for additional information. We will discuss disposition of these questions in the upcoming conference call.

Peter S. Tam, Senior Project Manager Project Directorate I-1 Division of Licensing Project Management Office of Nuclear Reactor Regulation e-mail: pst@nrc.gov Tel.: 301-415-1451 CC:

Allen Hiser Mail Envelope Properties (3E5BD06A.569 : 10 : 20510)

Subject:

Draft RAI FOR Calvert Cliffs, TAC MB7752 and MB7753 Creation Date:

2/25/03 3:22PM From:

Peter Tam

Created By:

PST@nrc.gov Recipients Action Date & Time donna.j Transferred 02/25/03 03:22PM mitchell (internet:donna.j.mitchell@ccnpp getachew Transferred 02/25/03 03:22PM tesfaye (INTERNet:getachew.tesfaye@ccnppi patricia.s Transferred 02/25/03 03:22PM furio (internet:patricia.s.furio@ccnppi.c owf2_po.OWFN_DO Delivered 02/25/03 03:22PM ALH1 CC (Allen Hiser)

Opened 02/25/03 03:28PM Post Office Delivered Route donna.j internet:ccnppi.com getachew INTERNet:ccnppi.co m

patricia.s internet:ccnppi.com owf2_po.OWFN_DO 02/25/03 03:22PM Files Size Date & Time MESSAGE 2841 02/25/03 03:22PM Options Auto Delete:

No Expiration Date:

None Notify Recipients:

Yes Priority:

Standard Reply Requested:

No Return Notification:

None Concealed

Subject:

No Security:

Standard To Be Delivered:

Immediate Status Tracking:

Delivered & Opened