Issuance of License Amendments Administrative Controls for High Radiation Areas
ML030150528
Person / Time
Site: Brunswick  
(DPR-062, DPR-071, NPF-037, NPF-066)
Issue date: 01/13/2003
From: Mozafari B
NRC/NRR/DLPM/LPD2
To: Keenan J
Carolina Power & Light Co
Olshan L N, NRR/DLPM, 415-1419
References
TAC MB5581, TAC MB5582
Download: ML030150528 (15)


Text

January 13, 2003 Mr. J. S. Keenan Vice President Brunswick Steam Electric Plant Carolina Power & Light Company Post Office Box 10429 Southport, North Carolina 28461

SUBJECT:

BRUNSWICK STEAM ELECTRIC PLANT, UNITS 1 AND 2 - ISSUANCE OF AMENDMENT RE: ADMINISTRATIVE CONTROLS FOR HIGH RADIATION AREAS (TAC NOS. MB5581 AND MB5582)

Dear Mr. Keenan:

The Nuclear Regulatory Commission has issued the enclosed Amendment No. 225 to Facility Operating License No. DPR-71 and Amendment No. 252 to Facility Operating License No.

DPR-62 for Brunswick Steam Electric Plant, Units 1 and 2. The amendments are in response to your application dated July 2, 2002.

The amendments change the administrative controls in Technical Specification 5.7, High Radiation Area.

A copy of the related Safety Evaluation is also enclosed. A Notice of Issuance will be included in the Commission's bi-weekly Federal Register Notice.

Sincerely,

/RA by L.Olshan Acting for/

Brenda L. Mozafari, Senior Project Manager, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-325 and 50-324

Enclosures:

1. Amendment No. 225 to License No. DPR-71
2. Amendment No. 252 to License No. DPR-62
3. Safety Evaluation cc w/enclosures:

See next page

Mr. J. S. Keenan January 13, 2003 Vice President Brunswick Steam Electric Plant Carolina Power & Light Company Post Office Box 10429 Southport, North Carolina 28461

SUBJECT:

BRUNSWICK STEAM ELECTRIC PLANT, UNITS 1 AND 2 - ISSUANCE OF AMENDMENT RE: ADMINISTRATIVE CONTROLS FOR HIGH RADIATION AREAS (TAC NOS. MB5581 AND MB5582)

Dear Mr. Keenan:

The Nuclear Regulatory Commission has issued the enclosed Amendment No. 225 to Facility Operating License No. DPR-71 and Amendment No. 252 to Facility Operating License No.

DPR-62 for Brunswick Steam Electric Plant, Units 1 and 2. The amendments are in response to your application dated July 2, 2002.

The amendments change the administrative controls in Technical Specification 5.7, High Radiation Area.

A copy of the related Safety Evaluation is also enclosed. A Notice of Issuance will be included in the Commission's bi-weekly Federal Register Notice.

Sincerely,

/RA by L.Olshan Acting for/

Brenda L. Mozafari, Senior Project Manager, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-325 and 50-324

Enclosures:

1. Amendment No. 225 to License No. DPR-71
2. Amendment No. 252 to License No. DPR-62
3. Safety Evaluation cc w/enclosures:

See next page DISTRIBUTION: See next page Adams Accession No.ML030150528(Letter)

  • No major changes to SE.

OFFICE PM:PDII/S2 LA:PDII/S2 SC:PDII/S2 IEHB*

OGC NAME LOlshan for BMozafari EDunnington AHowe KGibson DATE 12/19/02 12/19/02 1/10/03 11/26/02 1/6/03 COPY Yes/No Yes/No Yes/No Yes/No Yes/No OFFICIAL RECORD COPY

AMENDMENT NO. 225 TO FACILITY OPERATING LICENSE NO. DPR BRUNSWICK, UNIT 1 AMENDMENT NO. 252 TO FACILITY OPERATING LICENSE NO. DPR BRUNSWICK, UNIT 2 DISTRIBUTION:

PUBLIC PD II-2 Rdg.

OGC G. Hill (4)

R. Dennig R. Pedersen ACRS P. Fredrickson, RII cc: Brunswick Service List

CAROLINA POWER & LIGHT COMPANY DOCKET NO. 50-325 BRUNSWICK STEAM ELECTRIC PLANT, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 225 License No. DPR-71 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment filed by Carolina Power & Light Company (the licensee), dated July 2, 2002, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications, as indicated in the attachment to this license amendment; and paragraph 2.C.(2) of Facility Operating License No. DPR-71 is hereby amended to read as follows:

(2)

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 225, are hereby incorporated in the license. Carolina Power & Light Company shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and shall be implemented within 60 days of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

/RA/

Allen G. Howe, Chief, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: January 13, 2003

ATTACHMENT TO LICENSE AMENDMENT NO. 225 FACILITY OPERATING LICENSE NO. DPR-71 DOCKET NO. 50-325 Replace the following pages of the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.

Remove Pages Insert Pages 5.0-22 5.0-22 5.0-23 5.0-23 5.0-24 5.0-24 5.0-25 5.0-25

CAROLINA POWER & LIGHT COMPANY DOCKET NO. 50-324 BRUNSWICK STEAM ELECTRIC PLANT, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 252 License No. DPR-62 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment filed by Carolina Power & Light Company (the licensee), dated July 2, 2002, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment; and paragraph 2.C.(2) of Facility Operating License No. DPR-62 is hereby amended to read as follows:

(2)

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 252, are hereby incorporated in the license. Carolina Power & Light Company shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and shall be implemented within 60 days of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

/RA/

Allen G. Howe, Chief, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: January 13, 2003

ATTACHMENT TO LICENSE AMENDMENT NO. 252 FACILITY OPERATING LICENSE NO. DPR-62 DOCKET NO. 50-324 Replace the following pages of the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.

Remove Pages Insert Pages 5.0-21 5.0-21 5.0-22 5.0-22 5.0-23 5.0-23 5.0-24 5.0-24

SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 225 TO FACILITY OPERATING LICENSE NO. DPR-71 AND AMENDMENT NO. 252 TO FACILITY OPERATING LICENSE NO. DPR-62 CAROLINA POWER & LIGHT COMPANY BRUNSWICK STEAM ELECTRIC PLANT, UNITS 1 AND 2 DOCKET NOS. 50-325 AND 50-324

1.0 INTRODUCTION

By letter dated July 2, 2002, the Carolina Power & Light Company (the licensee) submitted a request for changes to the Brunswick Steam Electric Plant, Units 1 and 2, Technical Specifications (TS). The requested changes would revise the administrative controls of TS 5.7, High Radiation Area.

2.0 REGULATORY EVALUATION

The regulatory requirements on which the NRC staff based its acceptance are contained in Regulatory Guide (RG) 8.38, Control of Access to High and Very High Radiation Areas in Nuclear Power Plants, Section C, Regulatory Position 2.4, Alternate Methods for Access Control.

3.0 TECHNICAL EVALUATION

In its July 2, 2002, letter, the licensee stated that the requirements of sub-paragraphs d.4. of TS 5.7.1 and TS 5.7.2 are too restrictive and constitute a regulatory burden. The current TS require individuals to possess direct-reading dosimeters when entering high radiation areas under the surveillance of a radiation protection-qualified individual, at the site, who is equipped with a radiation monitoring and indicating device. The proposed revision would list the option of entering the high radiation area, under the surveillance of a radiation protection-qualified individual, without the requirement to possess a direct-reading dosimeter. This would be specified as a separate (fifth) option under TS 5.7.1.d and TS 5.7.2.d.

Several editorial changes have also been proposed to TS 5.7.1 and TS 5.7.2 to conform to the revised numbering of the control options and to improve the clarity of the requirements.

The NRC staff has reviewed the proposed changes and concludes that they are consistent with the guidance provided in RG 8.38, Section C, Regulatory Position 2.4; therefore, the NRC staff concludes that these proposed changes are acceptable.

4.0 STATE CONSULTATION

In accordance with the Commission's regulations, the State of North Carolina official was notified of the proposed issuance of the amendments. The State official had no comments.

5.0 ENVIRONMENTAL CONSIDERATION

The amendments change recordkeeping, reporting, or administrative procedures or requirements. Accordingly, the amendments meet the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(10). Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendments.

6.0 CONCLUSION

The Commission has concluded, based on the considerations discussed above, that (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendments will not be inimical to the common defense and security or to the health and safety of the public.

Principal Contributor: R. Pedersen Date: January 13, 2003

Mr. J. S. Keenan Brunswick Steam Electric Plant Carolina Power & Light Company Units 1 and 2 cc:

Mr. William D. Johnson Vice President and Corporate Secretary Carolina Power & Light Company Post Office Box 1551 Raleigh, North Carolina 27602 Mr. Donald E. Warren Brunswick County Board of Commissioners Post Office Box 249 Bolivia, North Carolina 28422 Resident Inspector U. S. Nuclear Regulatory Commission 8470 River Road Southport, North Carolina 28461 Mr. John H. ONeill, Jr.

Shaw, Pittman, Potts & Trowbridge 2300 N Street NW.

Washington, DC 20037-1128 Ms. Beverly Hall, Acting Director Division of Radiation Protection N.C. Department of Environment and Natural Resources 3825 Barrett Dr.

Raleigh, North Carolina 27609-7721 Mr. W. C. Noll Plant Manager Carolina Power & Light Company Brunswick Steam Electric Plant Post Office Box 10429 Southport, North Carolina 28461 Public Service Commission State of South Carolina Post Office Drawer 11649 Columbia, South Carolina 29211 Ms. Margaret A. Force Assistant Attorney General State of North Carolina Post Office Box 629 Raleigh, North Carolina 27602 Mr. Robert P. Gruber Executive Director Public Staff - NCUC 4326 Mail Service Center Raleigh, North Carolina 27699-4326 Mr. C. J. Gannon Director - Site Operations Carolina Power & Light Company Brunswick Steam Electric Plant Post Office Box 10429 Southport, North Carolina 28461 Mr. Norman R. Holden, Mayor City of Southport 201 East Moore Street Southport, North Carolina 28461 Mr. Dan E. Summers Emergency Management Coordinator New Hanover County Department of Emergency Management Post Office Box 1525 Wilmington, North Carolina 28402 Mr. Terry C. Morton, Manager Performance Evaluation and Regulatory Affairs CPB 7 Carolina Power & Light Company Post Office Box 1551 Raleigh, North Carolina 27602-1551 Mr. Edward T. ONeil Manager - Support Services Carolina Power & Light Company Brunswick Steam Electric Plant Post Office Box 10249 South Port, North Carolina 28461