AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.1-1 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Unit 0 (Common) Components NONE Unit I Components 1VE04Y 1VX16Y NONE Division 12 MEER Fire Damper Division 12 ESF Swgr Room Fire Damper 1VDO1CB 1VD01YA 1VDO1CB IVDO1YA 1VDO1YB 1VD16YA 1VD16YB IVEO0Y 1VXo1C 1VXOIY 1VDO07 1VD008 1VD012 1VD079 1VD012 1VD024 1VD025 1VD026 1VD063 1VD065 Diesel Generator Room 1 B Supply Fan Diesel Generator Room 1 B Outside Air Intake Damper Diesel Generator Room 1 B Outside Air Intake Damper Diesel Generator Room I1B Fire Damper Diesel Generator Room 1 B Fire Damper Division 12 MEER Outside Air Intake Damper Division 12 ESF Switchhear Room Supply Fan Division 12 ESF Swgr Room Outside Air Intake Damper Power Cable For IVD01CB Control Cable For 1VDO1CB Control Cable For 1VD01CB. 1VD01YA, 1VD01YB, 1VD02YA, and 1VDO2YB Control Cable For 1VD01CB, 1VDO1YA, 1VD01YB, 1VD02YA, and 1VD02YB Control Cable For 1VD01CB, 1VD01YA, 1VD01YB, 1VD02YA, and 1VD02YB Instrument Cable For 1VD01YA, 1VD01YB, 1VD02YA, and 1VD02YB Instrument Cable For IVDO1YA, 1VD01 YB, 1VDO2YA. and 1VD02YB Instrument Cable For 1VD01 YA, 1VD01 YB, 1VD02YA, and 1VD02YB Control Cable For 1VD01YA, 1VD01YB, 1VD02YA. and 1VD02YB Control Cable For 1VD01YA, 1VD01YB.

1VDO2YA, and 1VD02YB (Sheet 975)

BYRON-FPR

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Divsion 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.1-1 1VD066 Control Cable For 1VD01YA. 1VD01 YB, 1VD02YA, and IVD02YB 1VD076 Control Cable For 1VD01YA, 1VD01YB, 1VD02YA, and IVD02YB 1VD079 Control Cable For 1VD01 CB, 1VD01YA, 1VDO1YB, 1VD02YA, and 1VDO2YB 1VD081 Control Cable For 1VD01YA, 1VDO1YB, 1VD02YA, and 1VD02YB 1VD086 Control Cable For 1VDO1YA, 1VD01YB, 1VD02YA, and 1VD02YB 1VD090 Control Cable For 1VDO1YA, IVDO1YB, IVD02YA, and 1VD02YB 1VD095 Control Cable For 1VDO1YA, 1VD01YB, 1VD02YA. and IVD02YB 1VD01YB 1VD012 Control Cable For 1VDO1CB. IVDOIYA, 1VD01YB. IVD02YA, and IVD02YB 1VD024 Instrument Cable For 1VDO1YA. 1VDO1YB, 1VD02YA, and 1VD02YB 1VD025 Instrument Cable For 1VDO1YA, 1VDO1YB, IVD02YA, and 1VD02YB 1VD026 Instrument Cable For 1VD01YA, 1VDO1XYB, 1VD02YA, and 1VDO2YB 1VD063 Control Cable For 1VD01YA, IVD01YB, 1VD02YA, and 1VDO2YB 1VD065 Control Cable For 1VD01YA, 1VD01YB, 1VD02YA, and 1VD02YB 1VD066 Control Cable For IVDO1YA, 1VDO1YB, 1VD02YA, and 1VD02YB 1VD076 Control Cable For 1VDO1YA, 1VDO1YB.

1VD02YA, and 1VD02YB 1VD079 Control Cable For 1VD01CB, 1VDO1YA, 1VD01YB. 1VD02YA, and IVD02YB 1VD081 Control Cable For 1VD01YA, 1VDOIYB, 1VD02YA, and 1VD02YB 1VD086 Control Cable For 1VD01YA, 1VDO1YB, IVD02YA. and IVD02YB (Sheet 976)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Divislon 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.1-1 1VD090 Control Cable For 1VDO1YA, 1VD01YB, 1VDO2YA, and 1VDO2YB 1VD095 Control Cable For 1VDO1YA, 1VD01YB, 1VDO2YA, and 1VD02YB 1VD02YA 1VD012 Control Cable For IVDOICB, 1VDO1YA, 1VDO1YB, 1VD02YA, and 1VD02YB 1VD024 Instrument Cable For 1VDO1YA, 1VDO1YB, 1VD02YA, and 1VD02YB 1VD025 Instrument Cable For 1VD01YA, 1VD01YB, 1VD02YA, and 1VD02YB 1VD026 Instrument Cable For 1VDO1YA, 1VD01YB, 1VD02YA. and 1VD02YB 1VD063 Control Cable For 1VDO1YA, 1VDO1YB, 1VD02YA, and 1VD02YB 1VD065 Control Cable For 1VDO1YA, 1VDO1YB, IVD02YA, and 1VD02YB 1VD066 Control Cable For 1VDO1YA, 1VDO1YB, 1VD02YA, and IVD02YB 1VD076 Control Cable For 1VDO1YA, IVDO1YB, IVD02YA. and IVD02YB 1VD079 Control Cable For 1VDO1CB. 1VD01YA, 1VD01YB. 1VD02YA, and 1VD02YB 1VD081 Control Cable For 1VDO1YA, 1VD01YB, 1VDO2YA, and 1VD02YB 1VD086 Control Cable For 1VD01YA, 1VDOIYB, 1VD02YA, and 1VDO2YB 1VD090 Control Cable For 1VD01YA, IVD01 YB, IVD02YA, and IVD02YB 1VD095 Control Cable For 1VDO1YA, 1VDO1YB, 1VD02YA, and IVD02YB 1VD02YB 1VD012 Control Cable For 1VD01CB, 1VDOIYA, 1VD01YB, 1VD02YA, and 1VD02YB 1VD024 Instrument Cable For 1VDO1YA, 1VDO1YB, IVD02YA, and 1VD02YB 1VD025 Instrument Cable For 1VDO1YA, 1VD01YB, 1VD02YA, and 1VDO2YB (Sheet 977)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.1-1 1VD026 Instrument Cable For 1VDO1YA, 1VDO1YB, 1VDO2YA, and 1VD02YB 1VD063 Control Cable For 1VDO1YA, 1VD01YB.

1VD02YA, and IVD02YB 1VD065 Control Cable For 1VDO1YA, 1VDO1YB, 1VD02YA, and 1VD02YB 1VD066 Control Cable For 1VDO1YA, 1VDO1YB, 1VD02YA, and 1VD02YB 1VD076 Control Cable For IVDO1YA, 1VD01YB, 1VD02YA, and 1VD02YB 1VD079 Control Cable For 1VD01CB, IVD01YA, 1VDO1YB, 1VD02YA, and 1VDO2YB 1VD081 Control Cable For 1VD01YA, 1VDO1YB, 1VD02YA, and IVD02YB 1VD086 Control Cable For 1VDO1YA, 1VDO1YB, 1VD02YA, and 1VDO2YB 1VD090 Control Cable For 1VD01YA. 1VDO1 YB, 1VD02YA, and 1VD02YB 1VD095 Control Cable For 1VD01YA, 1VD01YB, 1VD02YA, and 1VD02YB 1VD16YA 1C0273 Control Cable For 1VD16YA and 1VD16YB 1VD16YB 1CO273 Control Cable For IVD16YA and 1VD16YB 1VEO1Y 1VE002 Instrument Cable For 1VE01Y and 1VE02Y 1VE026 Control Cable For IVE01Y and 1VE02Y IVE02Y 1VE002 Instrument Cable For 1VEO1Y and 1VE02Y 1VE026 Control Cable For 1VE01Y and 1VE02Y iVXO1C 1VX113 Power Cable For 1VX01C IVXOIY 1VX025 Instrument Cable For 1VXO1Y and 1VX02Y 1VX069 Control Cable For 1VXO1Y and IVX02Y 1VX074 Control Cable For 1VXO1Y and IVX02Y 1VX02Y 1VX025 Instrument Cable For 1VX01Y and 1VX02Y 1VX069 Control Cable For 1VXO1Y and IVX02Y 1VX074 Control Cable For 1VX01Y and 1VX02Y (Sheet 978)

AMENDMENT20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.1-1 Unit 2 Components NONE DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description NONE (Sheet 979)

K-.

BYRON-FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.1-2 Unit 0 (Common) Components NONE Unit I Components NONE Unit 2 Components Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE Division 22 MEER Fire Damper Division 22 ESF Swgr Room Fire Damper Control Cable For 2VD23YA and 2VD23YB Control Cable For 2VD23YA and 2VD23YB 2VD01CB 2VDOIYA 2VD01CB 2VD01YA 2VD01YB 2VD16YA 2VD16YB 2VE01Y 2VX01C 2VXO1Y 2VD007 2VD008 2VD012 2VD079 2VD012 2VD024 2VD025 2VD026 Diesel Generator Room 2B Supply Fan Diesel Generator Room 2B Outside Air Intake Damper Diesel Generator Room 2B Outside Air Intake Damper Diesel Generator Room 2B Fire Damper Diesel Generator Room 2B Fire Damper Division 22 MEER Outside Air Intake Damper Division 22 ESF Switchhear Room Supply Fan Division 22 ESF Swgr Room Outside Air Intake Damper Power Cable For 2VD01 CB Control Cable For 2VD01GCB Control Cable For 2VDO01CB, 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB Control Cable For 2VD01CB. 2VD01YA, 2VD01YB, 2VD02YA, and 2VD02YB Control Cable For 2VD01CB, 2VDO1YA, 2VD01YB. 2VD02YA, and 2VD02YB Instrument Cable For 2VD01YA. 2VDO1YB, 2VD02YA, and 2VD02YB Instrument Cable For 2VD01YA, 2VDOIYB, 2VD02YA, and 2VD02YB Instrument Cable For 2VD01YA, 2VD01 YB, 2VD02YA, and 2VD02YB (Sheet 980)

BYRON - FPR 2VD23YA 2VD23YB 2VE04Y 2VX16Y 2CO262 2CO262

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.1-2 2VD063 Control Cable For 2VD01YA, 2VDOIYB, 2VDO2YA, and 2VD02YB 2VD065 Control Cable For 2VDO1YA, 2VDOIYB, 2VD02YA, and 2VD02YB 2VD066 Control Cable For 2VD01YA, 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD076 Control Cable For 2VD01YA, 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD079 Control Cable For 2VD01CB, 2VDO1YA, 2VD01 YB, 2VD02YA, and 2VD02YB 2VD081 Control Cable For 2VDO1YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD086 Control Cable For 2VD01 YA, 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD090 Control Cable For 2VD01YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD095 Control Cable For 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VDO1YB 2VD012 Control Cable For 2VDO1CB, 2VD01YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD024 Instrument Cable For 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD025 Instrument Cable For 2VDO1YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD026 Instrument Cable For 2VD01YA, 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD063 Control Cable For 2VDO1YA, 2VD01YB, 2VDO2YA, and 2VD02YB 2VD065 Control Cable For 2VDO1YA, 2VDO1YB.

2VD02YA, and 2VD02YB 2VD066 Control Cable For 2VDO1YA. 2VDO1IYB, 2VDO2YA, and 2VD02YB 2VD076 Control Cable For 2VD01YA, 2VD01 YB, 2VD02YA, and 2VD02YB 2VD079 Control Cable For 2VDO1 CB, 2VD01 YA, 2VDO1YB, 2VD02YA, and 2VD02YB (Sheet 981)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.1-2 2VD081 Control Cable For 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD086 Control Cable For 2VDO1YA, 2VD01 YB, 2VD02YA, and 2VD02YB 2VD090 Control Cable For 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD095 Control Cable For 2VD01YA, 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD02YA 2VD012 Control Cable For 2VD01CB, 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD024 Instrument Cable For 2VD01YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD025 Instrument Cable For 2VDO1YA, 2VDO1YB, 2VDO2YA, and 2VD02YB 2VD026 Instrument Cable For 2VDO1YA, 2VD01YB, 2VD02YA. and 2VD02YB 2VD063 Control Cable For 2VD01YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD065 Control Cable For 2VDO1YA. 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD066 Control Cable For 2VD01YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD076 Control Cable For 2VDOIYA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD079 Control Cable For 2VDO1CB, 2VD01YA, 2VD01YB, 2VDO2YA, and 2VD02YB 2VD081 Control Cable For 2VD01YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD086 Control Cable For 2VDO1YA, 2VDO1 YB, 2VDO2YA, and 2VD02YB 2VD090 Control Cable For 2VDO1YA, 2VD01 YB, 2VDO2YA, and 2VD02YB 2VD095 Control Cable For 2VDO1YA, 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD02YB 2VD012 Control Cable For 2VD01CB, 2VD01YA, 2VDO1YB, 2VD02YA, and 2VD02YB (Sheet 982)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12122 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.1-2 2VD024 Instrument Cable For 2VDO1YA, 2VD01 YB, 2VD02YA, and 2VD02YB 2VD025 Instrument Cable For 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD026 Instrument Cable For 2VD01YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD063 Control Cable For 2VDO1YA, 2VD01 YB, 2VDO2YA, and 2VDO2YB 2VD065 Control Cable For 2VDO1YA, 2VDO1YB, 2VD02YA, and 2VD02YB 2VD066 Control Cable For 2VD01YA, 2VDO1YB, 2VD02YA, and 2VDO2YB 2VD076 Control Cable For 2VDO1YA, 2VD01 YB, 2VDO2YA, and 2VD02YB 2VD079 Control Cable For 2VDO1CB, 2VDO1YA, 2VD01 YB, 2VD02YA. and 2VD02YB 2VD081 Control Cable For 2VDO1YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD086 Control Cable For 2VDO1YA, 2VDO1YB, 2VD02YA. and 2VD02YB 2VD090 Control Cable For 2VD01YA, 2VDO1 YB, 2VD02YA, and 2VD02YB 2VD095 Control Cable For 2VD01YA, 2VD01YB, 2VD02YA, and 2VD02YB 2VD16YA 2CO273 Control Cable For 2VD16YA 2VE01Y 2VE002 Instrument Cable For 2VEO1Y and 2VE02Y 2VE025 Control Cable For 2VEO1Y and 2VE02Y 2VE02Y 2VE002 Instrument Cable For 2VE01Y and 2VE02Y 2VE025 Control Cable For 2VE01Y and 2VE02Y 2VXO1C 2VX1 13 Power Cable For 2VX01C 2VXO1Y 2VX025 Instrument Cable For 2VX01Y and 2VX02Y 2VX069 Control Cable For 2VX01Y and 2VX02Y 2VX074 Control Cable For 2VX01 Y and 2VX02Y 2VX02Y 2VX025 Instrument Cable For 2VXO1Y and 2VX02Y 2VX069 Control Cable For 2VX01Y and 2VX02Y (Sheet 983)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.1-2 Division 12/22 Affected Equipment Equipment Equipment In Zone Description 2VX074 Control Cable For 2VXOIY and 2VXO2Y (Sheet 984)

BYRON - FPR

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.2-1 Unit 0 (Common) Components NONE NONE Unit 1 Components 1VD01CA Diesel Generator Room 1A Supply Fan NONE 1VD09YA Diesel Generator Room 1A Outside Air Intake Damper IVDO9YB Diesel Generator Room 1A Outside Air Intake Damper 1VD23YA Diesel Generator Room IA Fire Damper 1VD23YB Diesel Generator Room 1A Fire Damper 1VE06Y Division 11 MEER Fire Damper IVX04C Division 11 ESF Switchgear Roorr/MEER Supply Fan IVX04Y Division 11 ESF Swgr Room Outside Air Intake Damper 1VX22Y Division 11 ESF Swgr Room Fire Damper 1VD01CA 1VD001 Power Cable For 1VD01 CA 1VD002 Control Cable For 1VD01CA 1VD006 Control Cable For 1VD01CA, 1VD09YA, 1VDO9YB, 1VD10YA, and 1VD10YB 1VD074 Control Cable For 1VD01CA, 1VD09YA, 1VD09YB. 1VD10YA, and 1VD10YB 1VD09YA 1VD006 Control Cable For 1VD01CA, 1VD09YA, 1VD09YB. 1VD10YA, and 1VD10YB 1VD014 Control Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD10YB 1VD017 Control Cable For 1VD09YA, IVDO9YB.

1VD10YA, and IVD10YB 1VD019 Instrument Cable For 1VD09YA, 1VDO9YB, 1VD10YA, and 1VD10YB 1VD022 Instrument Cable For 1VD09YA, 1VD09YB.

1VD10YA, and IVD10YB (Sheet 985)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.2-1 1VD023 Instrument Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD10YB 1VD056 Control Cable For 1VD09YA, IVD09YB, 1VDIOYA, and 1VD1OYB 1VD057 Control Cable For 1VD09YA, IVDO9YB, 1VD10YA, and 1VD1OYB 1VD060 Control Cable For 1VD09YA, 1VD09YB.

1VD1OYA, and 1VD10YB 1VD071 Control Cable For 1VD09YA, IVD09YB, 1VDIOYA, and 1VD1OYB 1VD074 Control Cable For 1VDO0CA, 1VDO9YA, 1VD09YB, 1VD10YA, and 1VDIOYB 1VD084 Control Cable For 1VDO9YA, 1VD09YB.

1VD1OYA, and 1VD1OYB 1VD096 Control Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD10YB 1VDO9YB IVD006 Control Cable For 1VDO1CA, 1VD09YA, 1VDO9YB, 1VD1OYA, and 1VD1OYB IVD014 Control Cable For 1VD09YA, 1VD09YB, IVD1OYA, and IVD1OYB 1VD017 Control Cable For 1VD09YA, 1VD09YB, 1VD1OYA, and 1VD1OYB 1VD019 Instrument Cable For 1VD09YA, IVD09YB, 1VD10YA, and 1VD1OYB 1VD022 Instrument Cable For 1VD09YA, 1VD09YB, 1VD1OYA, and 1VDIOYB 1VD023 Instrument Cable For 1VD09YA, 1VD09YB, 1VD1OYA. and 1VD1OYB 1VD056 Control Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD1OYB 1VD057 Control Cable For 1VD09YA. 1VD09YB, 1VD1OYA, and 1VD10YB 1VD060 Control Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD1OYB 1VD071 Control Cable For 1VD09YA, IVD09YB, 1VD10YA, and 1VD10YB Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 986)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.2-1 IVD074 Control Cable For 1VDO1CA, 1VD09YA, lVDO9YB, 1VD10YA, and 1VD10YB 1VD084 Control Cable For 1VD09YA. 1VD09YB, 1VDIOYA, and 1VD10YB 1VD096 Control Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD10YB 1VD10YA 1VD006 Control Cable For 1VD01CA, 1VD09YA, 1VD09YB, 1VD10YA, and 1VD10YB IVD014 Control Cable For 1VD09YA, 1VD09YB, 1VD1OYA, and IVD10YB 1VD017 Control Cable For 1VD09YA, 1VD09YB, 1VD10YA. and 1VD1OYB 1VD019 Instrument Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD1OYB 1VD022 Instrument Cable For 1VD09YA, 1VD09YB, IVD1OYA, and 1VD10YB 1VD023 Instrument Cable For 1VD09YA, 1VD09YB, 1VD10YA. and 1VD1OYB 1VD056 Control Cable For 1VD09YA, 1VD09YB, 1VDIOYA, and 1VD1OYB 1VD057 Control Cable For 1VD09YA, 1VD09YB, 1VDIOYA, and IVD1OYB 1VD060 Control Cable For 1VD09YA, 1VD09YB, 1VD1OYA, and IVD1OYB 1VD071 Control Cable For 1VD09YA, 1VD09YB, 1VD10YA. and 1VD1OYB 1VD074 Control Cable For 1VDO1 CA, 1VD09YA, 1VD09YB, 1VD10YA, and 1VD1OYB IVD084 Control Cable For IVD09YA, 1VD09YB, 1VD1OYA, and 1VD10YB 1VD096 Control Cable For 1VD09YA, 1VD09YB, 1VD1OYA, and 1VD1OYB 1VD1OYB 1VDO06 Control Cable For IVDOICA, IVDO9YA, 1VD09YB, 1VD1OYA, and IVD1OYB 1VD014 Control Cable For 1VD09YA, 1VD09YB.

1VD10YA, and 1VD1OYB Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 987)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.2-1 IVD017 Control Cable For 1VD09YA, 1VD09YB, 1VD1OYA, and 1VD10YB 1VD019 Instrument Cable For 1VD09YA, 1VD09YB, 1VD10YA, and 1VD10YB 1VD022 Instrument Cable For 1VDO9YA, 1VD09YB, 1VD10YA. and IVD10YB 1VD023 Instrument Cable For 1VD09YA. IVD09YB, 1VD10YA, and 1VDIOYB 1VD056 Control Cable For 1VDO9YA, 1VD09YB, 1VD10YA, and 1VD1OYB 1VD057 Control Cable For 1VD09YA, 1VD09YB, 1VD1OYA, and 1VD10YB 1VD060 Control Cable For 1VDO9YA, 1VD09YB, 1VD1OYA, and 1VD1OYB 1VD071 Control Cable For IVD09YA, 1VD09YB, 1VDIOYA, and IVD1OYB.

1VD074 Control Cable For 1VD01CA, 1VD09YA, 1VD09YB, 1VDIOYA, and 1VD10YB 1VD084 Control Cable For 1VD09YA, 1VD09YB, 1VDIOYA, and IVD10YB 1VD096 Control Cable For 1VD09YA, 1VDO9YB, 1VD10YA, and 1VD10YB IVX04C 1VXooi Power Cable For 1VX04C 1VX063 Control Cable For IVX04C, 1VX04Y, and 1VX05Y 1VX04Y IVX020 Instrument Cable For 1VX04Y and IVX05Y 1VX061 Control Cable For 1VX04Y and 1VX05Y 1VX063 Control Cable For 1VX04C, IVX04Y, and 1VX05Y 1VXo5Y 1VX020 Instrument Cable For 1VX04Y and IVX05Y 1VX061 Control Cable For 1VX04Y and 1VX05Y 1VX063 Control Cable For 1VX04C, 1VX04Y, and 1VX05Y Unit 2 Components Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 988)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.2-1 NONE Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE (Sheet 989)

BYRON-FPR

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.2-2 Unit 0 (Common) Components NONE NONE Unit I Components NONE NONE Unit 2 Components 2VDO1CA Diesel Generator Room 2A Supply Fan NONE 2VD09YA Diesel Generator Room 2A Outside Air Intake Damper 2VD09YB Diesel Generator Room 2A Outside Air Intake Damper 2VD23YA Diesel Generator Room 2A Fire Damper 2VD23YB Diesel Generator Room 2A Fire Damper 2VE06Y Division 21 MEER Fire Damper 2VX04C Division 21 ESF Switchgear Room/MEER Supply Fan 2VX04Y Division 21 ESF Swgr Room Outside Air Intake Damper 2VX22Y Division 21 ESF Swgr Room Fire Damper 2VDO1CA 2VD001 Power Cable For 2VD01CA 2VD002 Control Cable For 2VD01CA 2VD006 Control Cable For 2VD01 CA, 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VD074 Control Cable For 2VD01 CA, 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD09YA 2VD006 Control Cable For 2VD01CA, 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VD014 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VD017 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB (Sheet 990)

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.2-2 2VD019 Instrument Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD022 Instrument Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD023 Instrument Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD056 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VDIOYB 2VD057 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD060 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VD071 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VD074 Control Cable For 2VD01 CA, 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD10YB 2VD084 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD096 Control Cable For 2VD09YA, 2VDO9YB, 2VD1OYA, and 2VDIOYB 2VD09YB 2VD006 Control Cable For 2VD01CA, 2VD09YA, 2VD09YB, 2VDIOYA, and 2VD1OYB 2VD014 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD017 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD019 Instrument Cable For 2VD09YA, 2VD09YB, 2VDIOYA, and 2VD1OYB 2VD022 Instrument Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD023 Instrument Cable For 2VDO9YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD056 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VD057 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 991)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.2-2 2VD060 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD10YB 2VD071 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD074 Control Cable For 2VD01 CA, 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD084 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD096 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VDIOYA 2VD006 Control Cable For 2VDO1CA, 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD10YB 2VD014 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD017 Control Cable For 2VD09YA, 2VD09YB.

2VD1OYA, and 2VD1OYB 2VD019 Instrument Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD10YB 2VD022 Instrument Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD10YB 2VD023 Instrument Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VD056 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD057 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD060 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD071 Control Cable For 2VD09YA, 2VD09YB, 2VDIOYA, and 2VD1OYB 2VD074 Control Cable For 2VD01CA, 2VD09YA, 2VD09YB, 2VDIOYA, and 2VD1OYB 2VD084 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD096 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 992)

BYRON-FPR AMENDMENt1 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.2-2 2VD1OYB 2VD006 Control Cable For 2VDO1 CA, 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD014 Control Cable For 2VD09YA, 2VD09YB, 2VDIOYA. and 2VD1OYB 2VD017 Control Cable For 2VD09YA, 2VDO9YB, 2VD10YA. and 2VD10YB 2VD019 Instrument Cable For 2VDO9YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD022 Instrument Cable For 2VDO9YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD023 Instrument Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD10YB 2VD056 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD057 Control Cable For 2VD09YA. 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD060 Control Cable For 2VDO9YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD071 Control Cable For 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD074 Control Cable For 2VDO1CA, 2VD09YA, 2VD09YB, 2VD1OYA, and 2VD1OYB 2VD084 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD1OYB 2VD096 Control Cable For 2VD09YA, 2VD09YB, 2VD10YA, and 2VD10YB 2VX04C 2VX001 Power Cable For 2VX04C 2VX063 Control Cable For 2VX04C, 2VX04Y, and 2VX05Y 2VX04Y 2VX020 Instrument Cable For 2VX04Y and 2VXO5Y 2VX061 Control Cable For 2VX04Y and 2VX05Y 2VX063 Control Cable For 2VX04C, 2VX04Y, and 2VXO5Y 2VX05Y 2VX020 Instrument Cable For 2VX04Y and 2VX05Y 2VX061 Control Cable For 2VX04Y and 2VX05Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 993)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

DMsion 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.2-2 2VX063 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For 2VX04C, 2VX04Y, and 2VX05Y (Sheet 994)

BYRON - FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Divsion 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.3-1 Unit 0 (Common) Components NONE Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE Unit 1 Components 1AF013A 1AF013B 1AF013C 1AF013D 1MSOO1A 1MS001A-DIV11 1MSOO1B 1MSOOIB-DIV11 1MSOO1C 1MSOO1C-DIV11 IMSOO1D 1MS001D-DIV11 1MS013A IMS013B IMSO13C 1MS013D 1MS014A 1MS014B 1MS014C 1MS014D 1MS015A 1MSO15B IMS015C AFW Pump IA to SG 1A Stop Valve (MO)

AFW Pump 1A to SG 1B Stop Valve (MO)

AFW Pump 1A to SG IC Stop Valve (MO)

AFW Pump 1A to SG 1 D Stop Valve (MO)

Loop 1A Main Steam Isolation Valve (HO)

Loop 1A Main Steam Isolation Valve (HO);

Division 11 Actuation Circuit Loop I1B Main Steam Isolation Valve (HO)

Loop 1B Main Steam Isolation Valve (HO);

Division 11 Actuation Circuit Loop IC Main Steam Isolation Valve (HO)

Loop 1C Main Steam Isolation Valve (HO);

Division 11 Actuation Circuit Loop 1D Main Steam Isolation Valve (HO)

Loop 1D Main Steam Isolation Valve (HO);

Division 11 Actuation Circuit Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve 1AF013E 1AF013F 1AF013G 1AFO13H 1MSOO1A-DIV12 IMS001B-DIV12 1MS001C-DIV12 1MSOOID-DIV12 1MS018B 1MSo1BC 1AP06EL 1MSOO1A-DIV12 IMS001B-DIV12 1MS101A 1MS101B IMS1o1C 1MS101D 1WO027 1WO029 1WO140 1MS270 1MS271 1MS564 1MS565 1MS279 AFW Pump 1B to SG 1A Stop Valve (MO)

AFW Pump 1 B to SG I1B Stop Valve (MO)

AFW Pump 1IB to SG 1 C Stop Valve (MO)

AFW Pump 1 B to SG ID Stop Valve (MO)

Loop 1A Main Steam Isolation Valve (HO);

Division 12 Actuation Circuit Loop lB Main Steam Isolation Valve (HO);

Division 12 Actuation Circuit Loop 1 C Main Steam Isolation Valve (HO);

Division 12 Actuation Circuit Loop 1D Main Steam Isolation Valve (HO);

Division 12 Actuation Circuit Steam Generator 1B Power Operated Relief Valve (HO)

Steam Generator 1C Power Operated Relief Valve (HO)

Loop 1A MSIV Bypass Valve (AO)

Loop 1B MSIV Bypass Valve (AO)

Loop IC MSIV Bypass Valve (AO)

Loop 1 D MSIV Bypass Valve (AO)

Power Cable For 1AP06EL Control Cable For 1AP06EL Control Cable For IAP06EL Control Cable For 1MS001A-DIV12 Control Cable For 1MS001A-DIV12 Control Cable For 1MS001A-DIV12 Control Cable For 1MS001A-DIV12 Control Cable For 1 MS001 B-DIVI2 (Sheet 995)

K>

BYRON - FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.3-1 Division 12/22 Affected Equipment Equipment Equipment In Zone Description 1MS015D 1MS016A IMS016B 1MS016C 1MS016D 1MS017A 1MS0178 lMS017C IMS017D 1MS018A 1MS018D 1MS019A lMS019B IMS019C 1 MS019D 1MS185A IMS185B 1MS185C 1MS185D 1 MS1 86A IMS186B 1MS186C 1MS186D 1MS187A 1MS187B 1MS187C 1MS187D Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Steam Generator 1A Power Operated Relief Valve (HO)

Steam Generator 1D Power Operated Relief Valve (HO)

Steam Generator 1A Atmospheric Relief Isolation Valve (MV)

Steam Generator 1B Atmospheric Relief Isolation Valve (MV)

Steam Generator IC Atmospheric Relief Isolation Valve (MV)

Steam Generator 1 D Atmospheric Relief Isolation Valve (MV)

SG 1A PORV Hand Pump Isolation Valve (MV)

SG IB PORV Hand Pump Isolation Valve (MV)

SG 1C PORV Hand Pump Isolation Valve (MV)

SG 1 D PORV Hand Pump Isolation Valve (MV)

SG 1A PORV Hand Pump Isolation Valve (MV)

SG 1B PORV Hand Pump Isolation Valve (MV)

SG IC PORV Hand Pump Isolation Valve (MV)

SG 1D PORV Hand Pump Isolation Valve (MV)

SG 1A PORV Hand Pump Isolation Valve (MV)

SG 1 B PORV Hand Pump Isolation Valve (MV)

SG IC PORV Hand Pump Isolation Valve (MV)

SG ID PORV Hand Pump Isolation Valve (MV) 1MS280 1 MS281 1 MS282 1 MS283 1 MS520 1 MS292 1MS293 1 MS294 1MS295 1MS296 1MS522 1 MS309 1MS310 1 MS571 1 MS572 1MS617 1MS618 1MS619 1MS620 1MS621 1MS622 1 MS623 1 MS629 1 MS630 1MS631 1MS632 1 MS633 1MS634 1MS635 1MS320 1MS325 Control Cable For 1MS001B-DIV12 Control Cable For I1MS001 B-DIV12 Control Cable For lMSOO1B-DIV12 Control Cable For 1MSOO1B-DIV12 Control Cable For 1 MSOO1B-DIV12 Control Cable For IMSOO1C-DIV12 Control Cable For 1MS001 C-DIV12 Control Cable For 1MSOO1C-DIV12 Control Cable For 1MS001C-DIV12 Control Cable For 1MS001C-DIV12 Control Cable For 1 MS001 C-DIV12 Control Cable For 1 MSO01 D-DIV12 Control Cable For 1 MSOO1 D-DIV12 Control Cable For 1MSOO1D-DIV12 Control Cable For 1MSOO1D-DIV12 Instrument Cable For 1 MSO1 8B Instrument Cable For 1MS018B Instrument Cable For 1MS018B Instrument Cable For 1 MS01 8B Instrument Cable For 1 MS01 8B Instrument Cable For 1MS018B Power Cable For 1MSO18B Instrument Cable For 1MSO18C Instrument Cable For lMS018C Instrument Cable For IMS018C Instrument Cable For lMS018C Instrument Cable For I1MSO18C Instrument Cable For 1MSO18C Power Cable For 1MS018C Control Cable For 1MS101A Control Cable For 1MS101B (Sheet 996)

BYRON - FPR 1MSOO1C-DIV12 1MS001D-DIV12 1MS018B 1MS018C 1MS1O1A 1MS101B

AMENDMEN'T-.ý'

DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.3-1 IMSOO1A-DIV11 1 MSOOIB-DIV 11 1MSOO1C-DIV1I 1MS001D-DIV11 1MS018A 1MSOI8D 1MS265 1MS266 1MS267 1MS268 1 MS269 1MS518 1MS278 1MS284 1MS566 1MS567 1MS291 1MS297 1MS569 1MS570 1MS304 I MS305 1MS306 1MS307 1 MS308 1MS526 1MS588 I MS589 1 MS590 1MSs91 1MS592 1MS593 1MS594 l MS600 1MS601 1MS602 1 MS603 Control Cable For 1MS001A-DIV11I Control Cable For 1MSOOIA-DIV11 Control Cable For 1MS001A-DIV11 Control Cable For 1MS001A-DIV1I Control Cable For IMS001A-DIV11 Control Cable For 1 MS001A-DIV1 1 Control Cable For 1MSOO1B-DIV11 Control Cable For 1MSOOIB-DIV11 Control Cable For 1 MS001B-DIV11 Control Cable For 1MS001 B-DIV1 1 Control Cable For IMS001C-DIVI1 Control Cable For 1MS001C-DIV11 Control Cable For 1MSOOIC-DIV1 1 Control Cable For 1MSO01C-DIV11 Control Cable For 1MSOO1D-DIV11 Control Cable For 1MS001D-DIV11 Control Cable For 1MS001D-DIV1I Control Cable For 1MSOO1D-DIV11 Control Cable For 1MSOO1D-DIV11 Control Cable For I1MSOO1 D-DIV1 1 Instrument Cable For IMS018A Instrument Cable For 1 MS01 8A Instrument Cable For 1 MS01 8A Instrument Cable For 1MSO18A Instrument Cable For IMS018A Instrument Cable For 1MS018A Power Cable For 1MS018A Instrument Cable For 1IMS018D instrument Cable For 1 MS018D Instrument Cable For lMS018D Instrument Cable For 1MSO1 8D Division 12/22 Affected Equipment Equipment Equipment In Zone Description 1MSIO1C IMSIO1D 1 PI-0515A 1 PI-0516A 1PI-0525A 1PI-0535A 1PI-0545A 1PI-0546A 1PI-MS194 1MS670 1 MS330 1 MS335 1MS671 1MS115 1MS127 1 MS667 1MS121 1MS124 1MS128 1MS667 Control Cable For 1MS101B Control Cable For 1MSIO1C Control Cable For lMS101D Control Cable For 1MS101D Instrument Cable For 1PI-0515A Instrument Cable For 1PI-0516A Instrument Cable For 1 PI-0525A and 1IPI-MS194 Instrument Cable For 1PI-0535A Instrument Cable For 1PI-0545A Instrument Cable For 1PI-0546A Instrument Cable For 1PI-0525A and 1PI-MS194 (Sheet 997)

K.

BYRONVR

BYRON -FPR AMENDMENT DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.3-1 1MS604 Instrument Cable For 1 MSO18D IMS605 Instrument Cable For 1MS018D 1MS606 Power Cable For 1MSO18D 1MS101A 1MS321 Control Cable For 1MS101A 1MS322 Control Cable For 1MS1O1A 1MS324 Control Cable For 1MS101A 1MS101B 1MS326 Control Cable For 1MS1OIB 1MS327 Control Cable For 1IMS1 01 B 1MS329 Control Cable For IMS101B IMS101C 1MS331 Control Cable For 1MS101C 1MS332 Control Cable For IMS101C 1MS334 Control Cable For 1MS101C lMS101D 1MS336 Control Cable For IMS101D 1MS337 Control Cable For 1MS101D 1MS338 Control Cable For 1MS101D 1MS339 Control Cable For 1MS101D 1PI-0514A 1MS665 Instrument Cable For 1 PI-0514A, 1 PI-0514B, and 1PI-MS193 1PI-0514B 1MS665 Instrument Cable For IPI-0514A, IPI-0514B, and 1PI-MS193 1 PI-0524A 1 MS102 Instrument Cable For 1PI-0524A and 1 PI-0524B 1PI-0524B 1MS102 Instrument Cable For 1PI-0524A and 1PI-0524B 1PI-0526A 1MS125 Instrument Cable For 1PI-0526A IPI-0534A 1MS106 Instrument Cable For 1PI-0534A and 1PI-0534B 1PI-0534B 1 MS106 Instrument Cable For 1 PI-0534A and 1PI-0534B 1 PI-0536A 1 MS126 Instrument Cable For 1IPI-0536A 1PI-0544A 1MS110 Instrument Cable For IPI-0544A and 1PI-0544B 1PI-0544B 1 MS110 Instrument Cable For 1 PI-0544A and 1 PI-0544B 1PI-MS193 1MS665 Instrument Cable For 1 PI-051 4A, 1 PI-0514B, and 1 PI-MS193 Unit 2 Components Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 998)

AMENDMENT20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.3-1 NONE Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE (Sheet 999)

BYRON-FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.3-2 Unit 0 (Common) Components NONE Unit I Components NONE DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE Unit 2 Components 2AF013A 2AF013B 2AF013C 2AF013D 2MSOO1A 2MSOO1A-DIV21 2MSOO1B 2MSOO1B-DIV21 2MSOOIC 2MSOO1C-DIV21 2MS001 D 2MS001D-DIV21 2MS013A 2MS013B 2MS013C 2MS013D 2MS014A 2MS014B 2MS014C 2MS014D AFW Pump 2A to SG 2A Stop Valve (MO)

AFW Pump 2A to SG 2B Stop Valve (MO)

AFW Pump 2A to SG 2C Stop Valve (MO)

AFW Pump 2A to SG 2D Stop Valve (MO)

Loop 2A Main Steam Isolation Valve (HO)

Loop 2A Main Steam Isolation Valve (HO);

Division 21 Actuation Circuit Loop 2B Main Steam Isolation Valve (HO)

Loop 2B Main Steam Isolation Valve (HO);

Division 21 Actuation Circuit Loop 2C Main Steam Isolation Valve (HO)

Loop 2C Main Steam Isolation Valve (HO);

Division 21 Actuation Circuit Loop 2D Main Steam Isolation Valve (HO)

Loop 2D Main Steam Isolation Valve (HO);

Division 21 Actuation Circuit Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve 2AF013E 2AF013F 2AF013G 2AF013H 2MSOO1A-DIV22 2MS001B-DIV22 2MS001C-DIV22 2MSOO1D-DIV22 2MS018B 2MS018C 2MS001A-DIV22 2MSOO1B-DIV22 2MS101A 2MS101B 2MS101C 2MS101D 2MS270 2MS271 2MS564 2MS565 2MS279 AFW Pump 2B to SG 2A Stop Valve (MO)

AFW Pump 2B to SG 2B Stop Valve (MO)

AFW Pump 2B to SG 2C Stop Valve (MO)

AFW Pump 2B to SG 2D Stop Valve (MO)

Loop 2A Main Steam Isolation Valve (HO);

Division 22 Actuation Circuit Loop 2B Main Steam Isolation Valve (HO);

Division 22 Actuation Circuit Loop 2C Main Steam Isolation Valve (HO);

Division 22 Actuation Circuit Loop 2D Main Steam Isolation Valve (HO);

Division 22 Actuation Circuit Steam Generator 2B Power Operated Relief Valve (HO)

Steam Generator 2C Power Operated Relief Valve (HO)

Loop 2A MSIV Bypass Valve (AO)

Loop 2B MSIV Bypass Valve (AO)

Loop 2C MSIV Bypass Valve (AO)

Loop 2D MSIV Bypass Valve (AO)

Control Cable For 2MS001 A-DIV22 Control Cable For 2MS001A-DIV22 Control Cable For 2MS001 A-DIV22 Control Cable For 2MS001 A-DIV22 Control Cable For 2MS001 B-DIV22 (Sheet 1000)

BYRON-FPR

AMENDMEN-f -

DECEMBER 2002 TABLE 2.4-4 (Cont d)

Divsion 11121 Affected Equipment Equipment Equipment In Zone Description Division 12122 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number, 18.3-2 2MS015A 2MS015B 2MSO15C 2MSO15D 2MS016A 2MS016B 2MSO1BC 2MS016D 2MS017A 2MS017B 2MS017C 2MS017D 2MS018A 2MS018D 2MS019A 2MS019B 2MS019C 2MS019D 2MS185A 2MS185B 2MS185C 2MS185D 2MS186A 2MS186B 2MS186C 2MS186D 2MS187A Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Main Steam Relief Valve Steam Generator 2A Power Operated Relief Valve (HO)

Steam Generator 2D Power Operated Relief Valve (HO)

Steam Generator 2A Atmospheric Relief Isolation Valve (MV)

Steam Generator 2B Atmospheric Relief Isolation Valve (MV)

Steam Generator 2C Atmospheric Relief Isolation Valve (MV)

Steam Generator 2D Atmospheric Relief Isolation Valve (MV)

SG 2A PORV Hand Pump Isolation Valve (MV)

SG 2B PORV Hand Pump Isolation Valve (MV)

SG 2C PORV Hand Pump Isolation Valve (MV)

SG 2D PORV Hand Pump Isolation Valve (MV)

SG 2A PORV Hand Pump Isolation Valve (MV)

SG 2B PORV Hand Pump Isolation Valve (MV)

SG 2C PORV Hand Pump Isolation Valve (MV)

SG 2D PORV Hand Pump Isolation Valve (MV)

SG 2A PORV Hand Pump Isolation Valve (MV) 2MS001C-DIV22 2MS001D-D1V22 2MS018B 2MS018C 2MS101A 2MS101B 2MS280 2MS281 2MS282 2MS283 2MS520 2MS292 2MS293 2MS294 2MS295 2MS296 2MS522 2MS309 2MS310 2MS571 2MS572 2MS617 2MS618 2MS619 2MS620 2MS621 2MS622 2MS623 2MS629 2MS630 2MS631 2MS632 2MS633 2MS634 2MS635 2MS320 2MS325 Control Cable For 2MS001B-DIV22 Control Cable For 2MSOO1 B-DIV22 Control Cable For 2MSOO1 B-DIV22 Control Cable For 2MSOO1B-DIV22 Control Cable For 2MS001B-DIV22 Control Cable For 2MS001 C-DIV22 Control Cable For 2MS001C-DIV22 Control Cable For 2MS001 C-DIV22 Control Cable For 2MSOO1C-DIV22 Control Cable For 2MSOO1C-DIV22 Control Cable For 2MSOOIC-DIV22 Control Cable For 2MSOO1D-DIV22 Control Cable For 2MS001 D-DIV22 Control Cable For 2MSOO1D-DIV22 Control Cable For 2MSOO1D-DIV22 Instrument Cable For 2MSO18B Instrument Cable For 2MSO18B Instrument Cable For 2MS01 8B Instrument Cable For 2MS01 8B Instrument Cable For 2MSO18B Instrument Cable For 2MS01 8B Power Cable For 2MSO18B Instrument Cable For 2MS018C Instrument Cable For 2MSO18C Instrument Cable For 2MS018C Instrument Cable For 2MS018C Instrument Cable For 2MSO18C Instrument Cable For 2MSO1 8C Power Cable For 2MS018C Control Cable For 2MS101A Control Cable For 2MS101B (Sheet 1001)

BYRON

AMENDMENT"'

DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.3-2 2LI-0459B 2U-0501 2U-0504 2MS001A-DIV21 2MSOO1B-DIV21 2MSOO1C-DIV21 2MS001D-DIV21 2MS018A 2MS187B 2MS187C 2MS187D 2RC371 2FW025 2FW028 2MS265 2MS266 2MS267 2MS268 2MS269 2MS518 2MS278 2MS284 2MS566 2MS567 2MS291 2MS297 2MS569 2MS570 2MS304 2MS305 2MS306 2MS307 2MS308 2MS526 2MS588 2MS589 2MS590 2MS591 2MS592 SG 2B PORV Hand Pump Isolation Valve (MV)

SG 2C PORV Hand Pump Isolation Valve (MV)

SG 2D PORV Hand Pump Isolation Valve (MV)

Instrument Cable For 2LI-0459B Instrument Cable For 2L1-0501 Instrument Cable For 2U-0504 Control Cable For 2MS001A-DIV21 Control Cable For 2MSOO1A-DIV21 Control Cable For 2MS0O1A-DIV21 Control Cable For 2MSOO1A-DIV21 Control Cable For 2MSOO1A-DIV21 Control Cable For 2MSOOIA-DIV21 Control Cable For 2MS001 B-DIV21 Control Cable For 2MS001 B-DIV21 Control Cable For 2MS001B-DIV21 Control Cable For 2MSOOIB-DIV21 Control Cable For 2MS001C-DIV21 Control Cable For 2MS001C-DIV21 Control Cable For 2MSOO1C-DIV21 Control Cable For 2MS0O1C-DIV21 Control Cable For 2MSOO1D-DIV21 Control Cable For 2MSOO1D-DIV21 Control Cable For 2MS001 D-DIV21 Control Cable For 2MS0O1D-DIV21 Control Cable For 2MSOO1 D-DIV21 Control Cable For 2MSOO1D-DIV21 Instrument Cable For 2MS018A Instrument Cable For 2MS018A Instrument Cable For 2MS018A Instrument Cable For 2MS018A Instrument Cable For 2MS018A Division 12/22 Affected Equipment Equipment Equipment In Zone Description 2MS101C 2MS101D 2PI-0515A 2PI-0516A 2PI-0525A 2PI-0535A 2PI-0545A 2PI-0546A 2PI-MS194 2MS330 2MS335 2MS674 2MS115 2MS127 2MS667 2MS121 2MS124 2MS128 2MS667 Control Cable For 2MS101C Control Cable For 2MS101D Control Cable For 2MS101D Instrument Cable For 2PI-051 5A Instrument Cable For 2PI-0516A Instrument Cable For 2PI-0525A and 2PI-MS194 Instrument Cable For 2PI-0535A Instrument Cable For 2PI-0545A Instrument Cable For 2PI-0546A Instrument Cable For 2PI-0525A and 2PI-MS194 (Sheet 1002)

BYRON - FPR

BYRON FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.3-2 2MS593 Instrument Cable For 2MSO18A 2MS594 Power Cable For 2MS018A 2MS018D 2MS600 Instrument Cable For 2MSO18D 2MS601 Instrument Cable For 2MSO18D 2MS602 Instrument Cable For 2MSO18D 2MS603 Instrument Cable For 2MS018D 2MS604 Instrument Cable For 2MSO18D 2MS605 Instrument Cable For 2MS018D 2MS606 Power Cable For 2MSO1 8D 2MS101A 2MS321 Control Cable For 2MS101A 2MS322 Control Cable For 2MS101A 2MS324 Control Cable For 2MS101A 2MS101B 2MS326 Control Cable For 2MS101B 2MS327 Control Cable For 2MS101B 2MS329 Control Cable For 2MS101B 2MS101C 2MS331 Control Cable For 2MS101C 2MS332 Control Cable For 2MS101C 2MS334 Control Cable For 2MS101C 2MS101D 2MS336 Control Cable For 2MS101D 2MS337 Control Cable For 2MS101D 2MS339 Control Cable For 2MS101D 2PI-0455B 2RC370 Instrument Cable For 2PI-0455B 2PI-0514A 2MS665 Instrument Cable For 2P1-0514A. 2PI-0514B, and 2PI-MS193 2PI-0514B 2MS099 Instrument Cable For 2PI-0514B 2MS665 Instrument Cable For 2PI-0514A, 2PI-0514B, and 2PI-MS193 2PI-0524A 2MS102 Instrument Cable For 2PI-0524A and 2PI-0524B 2PI-0524B 2MS102 Instrument Cable For 2PI-0524A and 2PI-0524B 2MS103 Instrument Cable For 2PI-0524B 2PI-0526A 2MS125 Instrument Cable For 2PI-0526A 2PI-0534A 2MS106 Instrument Cable For 2PI-0534A and 2PI-0534B Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1003)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.3-2 2PI-0534B 2PI-0536A 2PI-0544A 2PI-0544B 2PI-MS193 2MS106 2MS107 2MS126 2MS11O 2MS110 2MS111 2MS665 2TI-RCO05A 2RC612 2TI-RCO06A 2RC612 2TI-RC007A 2RC612 2TI-RC008A 2RC612 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Instrument Cable For 2PI-0534A and 2PI-0534B Instrument Cable For 2PI-0534B Instrument Cable For 2PI-0536A Instrument Cable For 2PI-0544A and 2PI-0544B Instrument Cable For 2PI-0544A and 2PI-0544B Instrument Cable For 2PI-0544B Instrument Cable For 2PI-0514A, 2PI-0514B, and 2PI-MS193 Instrument Cable For 2TI-RC005A, 2TI-RC006A, 2TI-RCOO7A. and 2TI-RCOO8A Instrument Cable For 2TI-RC005A, 2TI-RC006A, 2TI-RC007A, and 2TI-RC008A Instrument Cable For 2TI-RC005A, 2TI-RC006A, 2TI-RC007A, and 2TI-RCO08A Instrument Cable For 2TI-RCOO5A. 2TI-RCO06A, 2TI-RC007A, and 2TI-RC008A (Sheet 1004)

BYRON - FPR

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 Unit 0 (Common) Components OVC01CA Control Room HVAC Supply Fan OA NONE OVC02CA Control Room HVAC Return Fan OA OVCO32Y Train A Outside Air Damper OVC033Y Train A Supply Fan OA Outlet Damper OVC034Y MCR HVAC Main Supply Duct Fire Damper OVC043Y Train A Recirculation Charcoal Absorber Bypass Damper OVC102Y MCR HVAC Main Return Duct Fire Damper OVC17Y Train A Return Air Fan OA Inlet Damper OVC18Y Train A Purge Exaust Damper to Turbine Bldg OVC19Y Train A Return Air Fan OA Outlet Damper OVC20Y Train A Maximum Outside Air (Purge Une) Inlet Damper OVC281Y Train A Outside Air Damper OSX158B 2SX079 Control Cable For 0SX158B 0SX162A 1SX345 Control Cable For OSX162A OSX162C 2SX157 Control Cable For OSX162C OSX163A 1SX149 Control Cable For 0SX163A OSX163B 1SX153 Control Cable For OSX163B OSX163C 2SX149 Control Cable For OSX163C OSX163D 2SX153 Control Cable For OSX163D OVC01CA 1FP112 Control Cable For OVC01CA, OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC013 Power Cable For 0VCO1CA 1VC019 Control Cable For OVC01CA, OVC281Y, OVC02CA, 0VC033Y, OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y. and OVC19Y 1VC115 Control Cable For 0VC01CA, OVC02CA, OVC033Y, OVCO43Y, OVC094Y, 0VC095Y, OVC133Y, OVC17Y, OVC18Y, OVC19Y, OVC20Y, and OVC281Y (Sheet 1005)

BYRON-FPR AMENDMENTC)'

DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11M21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-1 OVC02CA 1VC016 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y IVCO19 Control Cable For OVCO1CA. OVC281Y, OVC02CA, 0VC033Y, OVC043Y. OVC094Y, OVC095Y, OVC133Y, OVC17Y, and OVC19Y 1VC021 Power Cable For OVC02CA 1VC025 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC026 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC029 Control Cable For OVC281Y and OVC02CA 1VC032 Control Cable For OVC281Y and OVC02CA IVC115 Control Cable For OVC01CA, OVC02CA, OVC033Y. OVC043Y, 0VC094Y, OVC095Y.

OVC133Y, OVC17Y, OVC18Y, OVC19Y, OVC20Y, and OVC281Y 1VC146 Control Cable For OVC20Y, OVC02CA, and OVC18Y 1VC160 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y IVC161 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC163 Control Cable For OVC281Y, OVC02CA, OVC033Y. OVC043Y, OVC17Y, and OVC19Y 1VC164 Control Cable For OVC281Y, 0VCO2CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC190 Control Cable For OVC20Y, OVC02CA, and OVC18Y 1VC191 Control Cable For OVC20Y, OVC02CA, and OVC18Y 1VC582 Control Cable For OVC20Y, OVC02CA, and OVC18Y 1VC583 Control Cable For OVC20Y, OVC02CA, and OVC18Y 1VC623 Control Cable For OVC02CA, OVC20Y, OVC281Y, 0VC033Y, 0VC043Y, OVC17Y, OVC18Y. and OVC19Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1006)

BYRON-FPR AMENDMENT2' DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 OVC033Y 1FP112 Control Cable For OV001CA, OVC281Y.

OVC033Y, OVC043Y, OVC17Y, and OVC1l9Y 1VCO15 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VC016 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC017 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VCO19 Control Cable For OVC01CA, OVC281Y, OVCO2CA, OVC033Y, OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, and OVC19Y 1VC025 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC026 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC030 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VC115 Control Cable For OVCO1CA, OVC02CA, OVC033Y, 0VC043Y, OVC094Y, OVC095Y, OVC133Y. OVC17Y, OVC18Y, OVC19Y, OVC20Y, and OVC281Y 1VC122 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC123 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC125 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC126 Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y 1VC128 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC129 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC131 Control Cable For OVC281Y. OVC033Y, OVCO43Y, OVC17Y, and OVC19Y 1VC132 Control Cable For OVC281Y. OVC033Y, OVC043Y, OVC17Y, and OVC19Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1007)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.4-1 1VC134 1VC135 1VC137 1VC138 1VC140 IVC141 1VC143 1VC144 1VC145 1VC147 1VC148 1VC149 1VC151 1VC152 1VC157 IVC160 1VC161 1VC182 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y. and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y.

OVC043Y, 0VC094Y, OVC095Y, OVC133Y, OVC17Y, OVCI8Y. and OVC19Y Control Cable For OVC20Y, 0VC281 Y, OVC033Y, OVCO43Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVCO33Y, OVC043Y, OVC17Y. and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC033Y and 0VC281 Y Control Cable For OVC281Y, OVC02CA, 0VC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC1 9Y Control Cable For OVC033Y and OVC281Y (Sheet 1008)

BYRON-FPR

AMENDMENi'2IY DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.4-1 1VC163 1VC164 1VC165 IVC166 1VC167 1VC168 1VC172 1VC173 1VC175 1VC176 1VC178 1VC179 1VC490 1VC491 1VC571 1VC623 OVc043Y 1FP112 1PR065 1PR066 1PR313 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC281Y, OVC02CA, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC02CA, oVC033Y. OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC033Y and OVC281Y Control Cable For 0VC281Y, 0VC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, OVC043Y. OVC17Y, and OVC19Y Control Cable For OVC033Y and 0VC281 Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, OVC043Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For 0VC281

0.

OVC033Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVCI9Y Control Cable For OVC033Y and OVC281Y Control Cable For OVCO2CA. OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVCO1CA, OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Power Cable For OVC281Y and 0VC043Y Power Cable For OVC281Y and 0VC043Y Power Cable For OVC20Y, OVC281Y, OVC043Y, OVC18Y, and OVC19Y (Sheet 1009)

BYRON - FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-1 1PR314 1VCo15 1VC016 1VC017 1VCO19 1VC025 1VC026 1VC030 1VC035 1VCI15 1VC122 1VC123 1VC124 1VC125 1VC126 1VC127 1VC128 1VC129 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Power Cable For OVC281Y and OVC043Y Control Cable For OVC20YO 0VC281 Y, OVC033Y, 0VC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC281Y, OVC02CA.

OVC033Y, OVC043Y, OVC17Y, and OVCI9Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVCO1CA, OVC281Y, OVC02CA, OVC033Y, OVCO43Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC02CA, OVCO33Y. OVC043Y, OVC17Y, and OVCI19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y. OVCI8Y. and OVC19Y Control Cable For OVC20Y, OVC281Y. OVC043Y, OVC18Y, and OVC19Y Control Cable For OVCO1 CA, OVC02CA, OVC033Y, OVC043Y, OVC094Y, 0VC095Y, OVC133Y. OVC17Y. OVC18Y, OVCl9Y, OVC20Y, and OVC281Y Control Cable For OVC281Y, OVCO33Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVCO43Y Control Cable For OVC281Y, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. 0VC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC043Y Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, 0VC043Y, OVC17Y, and OVC19Y (Sheet 1010)

BYRON - FPR

BYRON -FPRSAMENDMENT2tr' DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC130 Control Cable For OVC043Y 1VC131 Control Cable For OVC281Y, OVC033Y, OVC043Y. OVC17Y, and OVC19Y 1VC132 Control Cable For OVC281Y, OVCO33Y.

OVC043Y, OVC17Y, and OVC19Y 1VC133 Control Cable For OVC043Y 1VC134 Control Cable For OVC281Y. OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC135 Control Cable For OVC281Y. OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC136 Control Cable For OVC043Y 1VC137 Control Cable For 0VC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC138 Control Cable For OVC281Y. OVC033Y, OVC043Y. 0VC17Y, and OVC19Y 1VC139 Control Cable For 0VCO43Y IVC140 Control Cable For OVC281Y. OVC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC141 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y IVC142 Control Cable For OVCO43Y 1VC143 Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC144 Control Cable For OVC20Y, OVC281Y, OVC033Y.

OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, OVC18Y, and OVC19Y 1VC145 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y. OVC18Y, and OVC19Y 1VC147 Control Cable For OVC20Y. OVC281Y. OVC033Y, OVCO43Y, OVC17Y, OVC18Y, and OVC19Y 1VC148 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC149 Control Cable For OVC281Y, OVC033Y, OVC043Y. OVC17Y, and OVC19Y 1VC150 Control Cable For OVC043Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1011)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC151 1VC152 1VC153 1VC159 1VC160 1VC161 1VC163 1VC164 IVC166 1VC167 1VC172 1VC173 1VC175 1VC176 1VC178 1VC179 1VC358 1VC396 1VC454 1VC455 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC281Y, 0VC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, 0VC033Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC043Y Control Cable For OVC043Y Control Cable For OVC281Y, OVC02CA.

OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC02CA, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVCO33Y, OVCO43Y, OVC17Y. and OVC19Y Control Cable For OVC281Y, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, 0VCO33Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVCl7Y, and OVC19Y Control Cable For 0VCO43Y Control Cable For OVC043Y Control Cable For OVC20Y, OVC281Y, OVC043Y, OVC18Y. and OVC19Y Control Cable For OVC19Y, OVC20Y, OVC281Y.

OVC043Y, and OVC18Y (Sheet 1012)

BYRON-FPR

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC490 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y. and OVC19Y 1VC491 Control Cable For 0VC281Y. OVC033Y, OVC043Y, OVC17Y. and OVC19Y 1VC573 Control Cable For OVC043Y 1VC577 Control Cable For OVC19Y, OVC20Y, OVC281Y, OVC043Y, and OVC18Y 1VC623 Control Cable For OVC02CA, OVC20Y, OVC281 Y, OVC033Y. OVC043Y, OVC17Y, OVC18Y, and OVC19Y OVC094Y 1VC019 Control Cable For OVC01 CA, 0VC281 Y, OVC02CA, OVC033Y, OVC043Y, OVC094Y, OVC095Y. OVC133Y, OVC17Y, and OVC19Y 1VC 115 Control Cable For OVC01 CA, OVCO2CA, OVC033Y. OVC043Y, 0VC094Y, 0VC095Y.

OVC133Y, OVC17Y. OVC18Y, OVC19Y, OVC20Y, and OVC281Y IVC144 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, OVC18Y, and OVC19Y 1VC195 Control Cable For OVC094Y, OVC095Y, OVC17Y.

OVC18Y, OVC19Y, and OVC20Y 1VC198 Control Cable For OVC094Y, OVC17Y. OVC18Y.

OVC19Y, and OVC20Y OVC095Y 1VC019 Control Cable For OVC01 CA, OVC281Y.

OVC02CA, OVC033Y, OVC043Y, 0VC094Y, OVCO95Y, OVC133Y, OVC17Y, and OVC19Y IVC1I5 Control Cable For OVC01CA, OVC02CA, OVC033Y, OVC043Y, 0VC094Y, OVC095Y, OVC133Y, OVC17Y, OVC18Y, OVC19Y, OVC20Y, and OVC281Y 1VC144 Control Cable For OVC20Y. OVC281Y. OVC033Y, OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, OVC18Y, and OVC19Y 1VC195 Control Cable For OVC0g4Y, OVC095Y. OVC17Y.

OVC18Y. 0VC19Y, and OVC20Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1013)

K-BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-1 OVC133Y 1VCO19 Control Cable For OVCO1CA, OVC281Y, OVC02CA, OVCO33Y, OVC043Y, 0VC094Y, OVC095Y, OVC133Y, OVC17Y, and OVC19Y 1VC115 Control Cable For OVCO1CA, OVCO2CA, OVC033Y, OVC043Y, OVCO94Y, OVCO95Y, OVC133Y, OVC117Y, OVC18Y, OVC119Y, OVC20Y, and OVC281Y 1VC144 Control Cable For OVC20Y, 0VC281Y, oVC033Y, 0VC043Y. OVC094Y, OVC095Y, OVC133Y, OVC17Y, OVC18Y, and OVC19Y 1VC201 Control Cable For OVCl33Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y 1VC207 Control Cable For OVC133Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y OVC17Y 1FP112 Control Cable For OVCO1CA, OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC015 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VC016 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC017 Control Cable For OVC20Y, OVC281Y, OVCO33Y, OVC043Y. OVC17Y, OVC18Y, and OVC19Y 1VC019 Control Cable For OVC01CA, OVC281Y.

OVC02CA, 0VC033Y, OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y. and OVC19Y 1VC025 Control Cable For 0VC281 Y, OVC02CA.

OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC026 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC030 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VC115 Control Cable For OVCO1CA, OVC02CA, OVC033Y, OVCO43Y, OVCO94Y, OVC095Y, OVC133Y, OVC17Y, OVC18Y, OVC19Y, OVC2OY, and OVC281Y 1VC122 Control Cable For OVC281Y, OVCO33Y, OVCO43Y, OVC17Y, and OVC19Y Division 12122 Affected Equipment Equipment Equipment In Zone Description (Sheet 1014)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC123 Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC125 Control Cable For OVC281Y, OVC033Y, 0VC043Y, OVC17Y, and OVC19Y 1VC126 Control Cable For OVC281Y. 0VC033Y, 0VC043Y, OVC17Y, and OVC19Y 1VC128 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC129 Control Cable For OVC281Y, OVC033Y, OVC043Y. OVC17Y. and OVC19Y 1VC131 Control Cable For OVC281Y, 0VC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC132 Control Cable For OVC281Y. 0VC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC134 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC135 Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC137 Control Cable For 0VC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC138 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC140 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y IVC141 Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC143 Control Cable For OVC281VY OVC033Y, OVC043Y, 0VC17Y, and OVC19Y 1VC144 Control Cable For OVC20Y, OVC281Y, OVCO33Y, 0VC043Y, OVC094Y, 0VC095Y, OVC133Y, OVC17Y, OVC18Y, and OVC19Y 1VC145 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVCO43Y, OVC17Y, OVC18Y, and OVC19Y 1VC147 Control Cable For OVC20Y, OVC281Y, 0VC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VC148 Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1015)

BYRON-FPR DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-4 1VC149 Control Cable For OVC281Y. OVC033Y, OVCO43Y, OVC17Y, and OVC19Y 1VC151 Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y IVC152 Control Cable For 0VC281Y, OVC033Y, OVC043Y. 0VC17Y, and OVC19Y 1VC158 Control Cable For OVC17Y, OVC1 8Y, OVC19Y, and OVC20Y 1VC160 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC161 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC163 Control Cable For OVC281Y, OVCO2CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC164 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC166 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC167 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC172 Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y. and OVC19Y 1VC173 Control Cable For OVC281Y, 0VC033Y, OVCO43Y, 0VC17Y, and OVC19Y 1VC174 Control Cable For OVC17Y, OVC1 8Y, OVC19Y, and OVC20Y 1VC175 Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y. and OVC19Y 1VC176 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC177 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y 1VC178 Control Cable For OVC281Y, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y 1VC179 Control Cable For 0VC281Y, OVC033Y, 0VC043Y, OVC17Y, and OVC19Y Division 12122 Affected Equipment Equipment Equipment In Zone Description (Sheet 1016)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

DMsion 11/21 Affected Equipment Equipment In Zone Fire Zone Number:

18.4-1 1VC180 1VC189 1VC192 1VC195 1VC198 1VC201 1VC207 1VC490 1VC491 1VC572 1VC581 1VC623 1VC643 1VC644 1VC645 1VC646 1VC647 1VC656 Equipment Description Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y. OVC19Y.

and OVC20Y Control Cable For OVC17Y. OVC1BY, OVC19Y, and OVC20Y Control Cable For OVC094Y, OVCO95Y, OVC17Y.

OVC18Y, OVC19Y, and OVC20Y Control Cable For OVCO94Y, OVC17Y, OVCI8Y, OVC19Y, and OVC20Y Control Cable For OVC133Y, OVC17Y, OVC18Y.

OVC19Y, and OVC20Y Control Cable For OVC133Y. OVC17Y, OVC18Y.

OVCI9Y, and OVC20Y Control Cable For OVC281Y, OVCO33Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC281 Y, OVC033Y, OVCO43Y, OVC17Y. and OVC19Y Control Cable For OVC17Y, OVCI8Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC02CA, OVC20Y, OVC281Y, 0VC033Y, OVC043Y. OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC17Y, OVC18Y, 0VC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, 0VC19Y, and OVC20Y Control Cable For OVC17Y, OVCI BY, OVC19Y, and 0VC20Y Control Cable For OVC17Y, OVC1BY, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC1BY, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC1 BY, OVCI 9Y, and OVC20Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1017)

BYRON -FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC657 1VC658 1VC659 1VC660 oVCl8Y 1PR313 1VCO05 1VC017 1VC030 1VC035 IVCI08 1VCill 1VC115 1VC144 1VC145 1VC146 1VC147 1VC158 1VC174 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y. OVC1BY, OVC19Y, and OVC20Y Power Cable For OVC2OY, OVC281Y, OVC043Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVCI7Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC1BY, and OVC19Y Control Cable For OVC20Y. 0VC281 0YOVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y. OVC043Y, OVC18Y, and OVC19Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC01CA, OVC02CA, 0VC033Y, OVC043Y, 0VC094Y, 0VC095Y, OVCI33Y, OVC17Y, OVC18Y, OVC19Y, OVC20Y.

and OVC281Y Control Cable For OVC20Y, OVC281Y, OVC033Y, 0VC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, OVC1BY, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y. OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC02CA, and OVC18Y Control Cable For OVC2OY, OVC281Y, OVCO33Y, OVCO43Y, OVC17Y, OVCI1Y, and OVC19Y Control Cable For OVC17Y, OVC1BY, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y (Sheet 1018)

BYRON - FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.4-1 1VC177 1VC180 1VC181 1VC182 1VC184 1VC185 1VC189 1VC190 1VC191 IVC192 1VC195 1VC198 1VC201 1VC207 1VC454 1VC455 1VC572 1VC577 1VC581 1VC582 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC20Y, OVC02CA, and OVC18Y Control Cable For OVC20Y, OVC02CA, and OVC18Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVCO94Y, OVC095Y, OVC17Y.

0VC18Y, OVC19Y, and OVC20Y Control Cable For 0VCO94Y, OVC17Y, OVC18Y, OVC19Y. and OVC20Y Control Cable For OVC133Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC133Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC2OY, OVC281Y, OVC043Y, OVC1 8Y, and OVC19Y Control Cable For OVC19Y, OVC20Y, OVC281Y, OVCO43Y. and OVCl8Y Control Cable For OVC17Y, OVC18Y, OVCI9Y, and OVC20Y Control Cable For OVCI9Y, OVC2OY, OVC281Y, OVCO43Y, and OVCI8Y Control Cable For OVC17Y, OVCI8Y, OVC19Y, and OVC20Y Control Cable For OVC2OY, OVCO2CA, and OVC18Y (Sheet 1019)

BYRON - FPR

AMENDMENI--d DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11121 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC583 1VC623 1VC635 1VC636 1VC637 1VC638 1VC639 1VC640 1VC641 1VC642 1VC643 1VC644 1VC645 1VC646 1VC647 IVC648 1VC649 1VC650 1VC651 1VC652 1VC653 1VC654 1VC655 1VC656 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC20Y, OVC02CA, and OVC18Y Control Cable For OVC02CA, OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, 0VC1BY, and OVC19Y Control Cable For OVC20Y and OVCI BY Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC1BY Control Cable For OVC20Y and OVC1BY Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVCI BY Control Cable For OVC20Y and OVCI BY Control Cable For OVC20Y and OVC18Y Control Cable For OVC1,7Y, OVC18Y. OVC19Y, and OVC20Y Control Cable For OVC17Y, OVClBY, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC1BY, OVCl 9Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC20Y and OVC1BY Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC1BY Control Cable For OVC20Y and OVC1BY Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC1BY Control Cable For OVC20Y and OVC1BY Control Cable For OVC17Y, OVC1BY, OVC19Y, and OVC20Y (Sheet 1020)

BYRON -FPR

BYRON - FPR AMENDMENt DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.4-1 1VC657 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y 1VC658 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y 1VC659 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y 1VC660 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y OVC19Y 1FP112 Control Cable For OVCO1 CA, OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y 1 PR313 Power Cable For OVC20Y, OVC281Y, OVC043Y, OVC18Y, and OVC19Y 1VC015 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC1BY, and OVC19Y 1VC016 Control Cable For OVC281 Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y. and OVC19Y 1VC017 Control Cable For OVC20Y, 0VC281 Y. OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VCO19 Control Cable For OVCO1CA, OVC281Y, OVCO2CA, OVC033Y, OVC043Y, OVC094Y, 0VC095Y, OVC133Y, OVC17Y, and OVC19Y 1VC025 Control Cable For OVC281Y, OVC02CA, OVCO33Y. 0VC043Y, OVC17Y. and OVC19Y 1VC026 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC030 Control Cable For OVC2OY, OVC281Y, OVC033Y, 0VC043Y, OVC17Y, OVC18Y, and OVC19Y 1VC035 Control Cable For OVC20Y, OVC281Y, 0VC043Y.

OVC18Y, and OVC19Y 1VC115 Control Cable For 0VCO1CA, OVC02CA, OVC033Y, OVC043Y, 0VC094Y, OVC095Y.

OVC133Y, OVC17Y, OVC18Y, OVC19Y, OVC20Y, and OVC281Y 1VC122 Control Cable For OVC281Y, 0VC033Y.

OVC043Y, OVC17Y, and OVC19Y 1VC123 Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1021)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.4-1 1VC125 1VC126 1VC128 1VC129 1VC131 1VC132 1VC134 1VC135 1VC137 1VC138 1VC140 1VC141 1VC143 IVC144 1VC145 1VC147 1VC148 1VC149 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, 0VC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For 0VC281 Y. 0VC033Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. 0VC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For 0VC281Y, OVC033Y.

0VC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, 0VC033Y, OVC043Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC20Y, 0VC281Y, 0VC033Y, 0VC043Y, OVC094Y, 0VC095Y, OVC133Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, 0VC033Y, 0VC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, 0VC281Y, OVC033Y, OVCO43Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y (Sheet 1022)

BYRON-FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 IVC151 1VC152 1VC158 1VC160 1VC161 1VC163 1VC164 1VC166 1VC167 1VC172 1VC173 1VC174 1VC175 1VC176 IVC177 1VC178 1VC179 1VC180 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y.

OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC281Y, OVC02CA, OVC033Y, 0VC043Y, OVC17Y, and OVC1 9Y Control Cable For OVC281Y, OVC02CA, 0VC033Y, OVC043Y, OVC17Y, and OVC1 9Y Control Cable For OVC281Y, OVC02CA.

OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC02CA, OVCO33Y. OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVCO33Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y (Sheet 1023)

BYRON-FPR

AMENDMENT'OZ DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Affected Equipment Equipment In Zone Fire Zone Number:

18A-1 1VC189 1VC192 1VC195 1VC198 1VC201 1VC207 1VC454 1VC455 1VC490 1VC491 1VC572 1VC577 1VC581 1VC623 1VC643 1VC644 1VC645 1VC646 Division 11/21 Equipment Description Control Cable For OVC17Y, OVC18Y, OVC1gY, and OVC20Y Control Cable For OVC17Y, OVCIl8Y, OVC1 9Y, and OVC20Y Control Cable For OVCO94Y, OVCO95Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVCO94Y, OVC17Y, OVC1tY, OVC19Y, and OVC20Y Control Cable For OVC133Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC133Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC20Y, OVC281Y, OVC043Y, OVC1BY, and OVC19Y Control Cable For OVCI9Y, OVC20Y, OVC281Y, OVC043Y, and OVC18Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC19Y, OVC2OY, OVC281Y, OVCO43Y, and OVC18Y Control Cable For OVC17Y, OVCI8Y, OVC19Y, and OVC20Y Control Cable For OVC02CA, OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1024)

BYRON-FPR

AMENDMENR2O2 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.4-1 1VC647 1VC656 1VC657 1VC658 1VC659 IVC660 OVC20Y 1PR313 1VC015 1VC017 1VC030 1VC035 1VC108 1VC111 1VC115 1VC144 1VC145 IVC146 1VC147 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVCI7Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC1BY, OVC1 9Y, and OVC20Y Control Cable For OVC17Y, OVC18BY, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC1 BY. OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Power Cable For OVC20Y, OVC281 Y, 0VC043Y, OVC18Y. and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y.

OVC043Y, 0VC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC1BY, and OVC19Y Control Cable For OVC20Y. OVC281Y, OVC033Y, OVC043Y, OVC17Y. OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC043Y, OVC1 BY, and OVC19Y Control Cable For OVC20Y and OVC1BY Control Cable For OVC20Y and OVC18Y Control Cable For OVCO1 CA, OVCO2CA, OVC033Y, OVC043Y, 0VC094Y, 0VC095Y.

OVC133Y, OVC17Y, OVC18Y, OVC19Y, OVC20Y, and OVC281Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVCO43Y, OV017Y. OVC18Y. and 0VC19Y Control Cable For OVC20Y, OVC02CA, and OVC18Y Control Cable For OVC2OY, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC1 BY, and OVC19Y (Sheet 1025)

K-*

BYRON - FPR

AMENDMENT DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.4-1 1VC158 1VC174 1VC177 1VC180 1VC181 1VC182 1VC184 1VC185 1VC189 1VC190 1VC191 1VC192 IVC195 1VC198 IVC201 1VC207 1VC454 1VC455 1VC572 1VC577 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC20Y, OVC02CA, and OVC 18Y Control Cable For OVC20Y, OVC02CA, and OVC B8Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC094Y, OVC095Y, OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC094Y, OVC17Y, OVC1 8Y, OVC19Y, and OVC20Y Control Cable For OVC133Y, OVC17Y, OVC1 8Y, OVC19Y, and OVC20Y Control Cable For OVC133Y. OVC17Y. OVC1BY, OVC19Y, and OVC20Y Control Cable For OVC20Y, 0VC281 Y, OVC043Y, OVCI8Y, and OVC19Y Control Cable For OVC1l9Y, OVC20Y. OVC281Y, 0VC043Y, and OVC18Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC1 9Y, OVC20Y, OVC281Y, 0VC043Y, and OVC18Y (Sheet 1026)

BYRON - FPR

AMENDMENTe' DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.4-1 1 VC581 1VC582 1VC583 1VC623 1VC635 1VC636 1VC637 1VC638 1VC639 1VC640 1VC641 1VC642 1VC643 1VC644 1VC645 1VC646 1VC647 1VC648 1VC649 IVC650 IVC651 1VC652 1VC653 1VC654 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC20Y, OVC02CA, and OVC 18Y Control Cable For OVC20Y, OVC02CA, and OVC18Y Control Cable For OVC02CA, OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVCI8Y. and OVC19Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18BY Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC1 8Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y Control Cable For OVC17Y, OVCI8Y, OVCi9Y, and OVC20Y Control Cable For OVC17Y, OVC18Y, OVC1 9Y, and OVC20Y Control Cable For OVC17Y, OVC1 8Y, OVC1 9Y, and OVC20Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y Control Cable For OVC20Y and OVC18Y (Sheet 1027)

BYRON - FPR

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC655 Control Cable For OVC20Y and OVC18Y 1VC656 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y 1VC657 Control Cable For OVC17Y, OVC1 BY. OVC19Y, and OVC20Y 1VC658 Control Cable For OVC17Y, OVC18Y. OVC19Y, and OVC20Y 1VC659 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y 1VC660 Control Cable For OVC17Y, OVC18Y, OVC19Y, and OVC20Y OVC281Y 1FP112 Control Cable For OVC01CA, OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1FP143 Control Cable For OVC281Y 11FP150 Control Cable For OVC281Y I1PRO65 Power Cable For OVC281Y and OVC043Y 1PR066 Power Cable For OVC281Y and OVC043Y I PR313 Power Cable For OVC20Y, OVC281Y, OVC043Y, OVC1BY, and OVC19Y 1IPR314 Power Cable For OVC281Y and OVC043Y 1VC015 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y 1VC016 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC017 Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC1BY, and OVC19Y 1VC019 Control Cable For OVCO1CA, OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC094Y, OVC095Y, OVC133Y, OVC17Y, and OVC19Y 1VC025 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y IVC026 Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC029 Control Cable For OVC281Y and OVC02CA 1VC030 Control Cable For OVC20Y, OVC281Y, 0VC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1028)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC032 1VC035 IVC115 1VC122 1VC123 1VC125 1VC126 1VC128 1VC129 1VC131 1VC132 1VC134 1VC135 1VC137 1VC138 1VC140 1VC141 1VC143 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC281Y and OVC02CA Control Cable For OVC20Y, OVC281Y, OVCO43Y, OVC18Y, and OVC19Y Control Cable For OVCO1CA, OVC02CA, OVCO33Y, OVC043Y, OVC094Y, OVCO95Y, OVC133Y, OVC17Y, OVC18Y, OVC19Y, OVC20Y, and OVC281Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For 0VC281 Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For 0VC281 Y, OVC033Y, OVCO43Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y, 0VC17Y, and OVC19Y Control Cable For OVC281Y, 0VC033Y, OVCO43Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y. OVC17Y, and OVC19Y Control Cable For OVC281Y, OVCO33Y, OVC043Y. OVC17Y. and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and 0VC19Y Control Cable For OVC281Y, 0VC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC281Y. OVC033Y, OVCO43Y. 0VC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, oVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y (Sheet 1029)

BYRON-FPR

AMENDMBER00 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

DMsion 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.4-1 1VC144 1VC145 1VC147 1VC148 1VC149 1VC151 1VC152 1VC157 IVC160 1VC161 1VC162 1VC163 1VC164 1VC165 1VC166 1VC167 IVC168 1VC172 1VC173 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For OVC20Y, OVC281Y, OVC033Y, 0VC043Y, OVC094Y, 0VC095Y, OVC133Y, OVC17Y, OVC18Y, and OVCi9Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVC19Y Control Cable For OVC20Y, OVC281Y, OVC033Y, OVCO43Y, OVC17Y, OVCI8Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC033Y and OVC281Y Control Cable For 0VC281 Y, OVC02CA, 0VC033Y, OVC043Y, OVC17Y, and OVCl9Y Control Cable For OVC281Y, OVC02CA, OVC033Y, OVCO43Y, OVC17Y, and OVC19Y Control Cable For OVC033Y and 0VC281 Y Control Cable For 0VC281VY, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC281Y, OVC02CA, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC033Y and 0VC281 Y Control Cable For OVC281Y, OVC033Y, OVC043Y, 0VC17Y, and OVC19Y Control Cable For OVC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y Control Cable For OVC033Y and OVC281Y Control Cable For OVC281Y, 0VC033Y, OVC043Y, OVC17Y. and OVC19Y Control Cable For 0VC281Y, OVC033Y, 0VC043Y, OVC17Y, and OVC19Y (Sheet 1030)

BYRON - FPR

BYRON-FPR AMENDMENTl0 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1VC175 Control Cable For OVC281Y, OVC033Y, OVC043Y, 0VC17Y, and OVC19Y 1VC176 Control Cable For 6VC281Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC 178 Control Cable For OVC28iY, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC179 Control Cable For OVC281 Y, OVC033Y, OVC043Y, OVC17Y, and OVC19Y 1VC454 Control Cable For OVC20Y, OVC281Y, OVC043Y, OVC18Y, and OVC19Y 1VC455 Control Cable For OVC19Y, OVC20Y, OVC281Y, OVCO43Y, and OVC18Y 1VC490 Control Cable For OVC281Y, OVCO33Y, OVCO43Y, OVC17Y, and OVC19Y 1VC491 Control Cable For OVC281Y, OVCO33Y, OVCO43Y, OVC17Y, and OVC19Y 1VC571 Control Cable For OVCO33Y and 0VC281 Y 1VC577 Control Cable For OVC19Y, OVC20Y, OVC281Y, OVC043Y, and OVC18Y 1VC623 Control Cable For OVC02CA, OVC20Y, OVC281Y, OVC033Y, OVC043Y, OVC17Y, OVC18Y, and OVCI9Y Unit I Components 1AFO06A 1AF058 Control Cable For 1AF006A NONE 1AF017A 1AF097 Control Cable For 1AF017A IAF01PA 1AF013 Control Cable For 1AFO1PA-A and IAF01 PA 1AF064 Control Cable For 1AFO1PA-A and 1AF01 PA 1AF293 Control Cable For 1AF01 PA 1EF026 Control Cable For 1AFO01PA 1AF01PA-A 1AF013 Control Cable For IAF01PA-A and 1AFO1PA 1AF064 Control Cable For 1AF01lPA-A and IAF01lPA 1AP05EA 1AP180 Control Cable For 1AP05EA 1AP05EC 1S1004 Control Cable For 1APO5EC (Sheet 1031)

BYRON.

AMENDMENT v-"

DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.4-1 1S1005 Control Cable For 1AP05EC IAP05EE 1AP311 Control Cable For 1APOSEE 1AP661 Control Cable For 1AP05EE 1AP05EF 1DG005 Control Cable For 1AP05EF 1DG152 Control Cable For 1AP05EF 1DG228 Control Cable For IAP05EF IAP05EG 1AP056 Control Cable For IAP05EG 1AP634 Control Cable For 1AP05EG 1AP05EJ lCS002 Control Cable For 1AP05EJ ICS004 Control Cable For 1AP05EJ 1 EF086 Control Cable For 1APO5EJ IAP05EK 1WO024 Control Cable For 1AP05EK IAP05EP 1AP072 Power Cable For IAP05EP and 2AP05EJ 1AP073 Power Cable For 1AP05EP and 2AP05EJ 1AP319 Power Cable For 1AP05EP and 2AP05EJ 1AP320 Power Cable For IAP05EP and 2AP05EJ 1AP321 Power Cable For 1AP05EP and 2AP05EJ 1AP322 Power Cable For 1APOSEP and 2APO5EJ 2AP586 Control Cable For 1AP05EP and 2APO5EJ 1AP05ER 1AP049 Control Cable For IAP05ER 1DG211 Control Cable For 1AP05ER 1AP07EL 1AP098 Control Cable For 1AP07EL 1CC9415 1CC067 Control Cable For 1CC9415 1CC9473A 1CC127 Control Cable For 1CC9473A 1DG0O1KA 1DG174 Control Cable For 1DGO1KA 11PO1J 1EF037 Control Cable For IPOIJ 111P005 Power Cable For 1IP01J 11POO6 Power Cable For 1IPO1J lIP03J 11P033 Power Cable ForlIlP03J 1 IP034 Power Cable For 1IP03J 1RHO1PA 1RHOO3 Control Cable For 1 RHOIPA Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1032)

AMENDMENT".-.

DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-1 1RH8701A 1RH8702A IRY455A 1 RY8000A IUL-AN012-A7 1UL-AN012-B7 1UL-AN012-C7 1VX04Y 1VXo5C 1VX05Y 1RHO91 1RH031 1RH054 1RH055 1DC100 1 RY394 1AN084 1AN084 1AN084 1VE039 1VX044 1VE039 Unit 2 Components 2APO5EE 2APO5EJ 2AP93E 2AP99E 2VX05C 2AP178 2AP401 1AP072 1AP073 1AP319 1AP320 1AP321 1AP322 2AP586 2DC242 2DC244 2DC242 2DC244 2VX044 Control Cable For 1RHO1lPA Control Cable For 1 RH8701A Control Cable For 1 RH8702A Control Cable For I1RH8702A Control Cable For 1RY455A Control Cable For 1RY8000A Control Cable For 1 UL-AN012-A7, IUL-AN012 B7, and IUL-ANO12-C7 Control Cable For IUL-AN012-A7, 1UL-AN012 B7, and 1UL-AN012-C7 Control Cable For 1UL-AN012-A7, 1UL-AN012 B7, and 1 UL-ANO012-C7 Control Cable For 1VX04Y and 1VX05Y Control Cable For 1VX05C Control Cable For 1VX04Y and 1VX05Y Power Cable For 2AP05EE Control Cable For 2AP05EE Power Cable For 1AP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For IAP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For IAP05EP and 2AP05EJ Control Cable For 1AP05EP and 2AP05EJ Control Cable For 2AP99E and 2AP93E Control Cable For 2AP99E and 2AP93E Control Cable For 2AP99E and 2AP93E Control Cable For 2AP99E and 2AP93E Control Cable For 2VX05C Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE (Sheet 1033)

K-BYRONV-R

AMENDMENT-2Ut' DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.4-2 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Unit 0 (Common) Components OSX02PA OVC173Y OVC174Y 1SX172 MCR HVAC Main Supply Duct Fire Damper MCR HVAC Main Return Duct Fire Damper Control Cable For OSX02PA OVCo1CB OVCO1Y OVC01CB OVCO1Y OVC02CB OVC02Y OVC03Y OVC044Y OVC04Y OVC16Y OVC172Y 0VC282Y 1FP115 1VC059 1VC063 1VC119 1FP115 1VC039 1VC063 Control Room HVAC Supply Fan 0B Train B Return Air Fan 0B Inlet Damper Control Room HVAC Return Fan 0B Train B Purge Exaust Damper to Turbine Bldg Train B Return Air Fan 0B Outlet Damper Train B Recirculation Charcoal Absorber Bypass Damper Train B Maximum Outside Air (Purge Une) Inlet Damper Train B Outside Air Damper Train B Supply Fan 0B Outlet Damper Train B Outside Air Damper Control Cable For 0VC01CB, 0VC282Y.

OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y Power Cable For OVC01 CB Control Cable For OVC01CB, OVC217Y, 0VC282Y, 0VC01Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y Control Cable For 0VC01CB, 0VC01Y, OVC02CB, OVC02Y, OVC03Y, OVC044Y, OVCO4Y, OVC16Y, OVC172Y, OVC175Y, 0VC182Y, OVC217Y, and 0VC282Y Control Cable For OVC01 CB, 0VC282Y, OVC01Y. 0VC03Y, OVC044Y, OVC16Y, and OVC172Y Control Cable For OVC282Y, 0VC01Y, OVC02Y, OVC03Y, 0VC044Y, 0VC04Y, OVC16Y, and OVC172Y Control Cable For 0VC01CB, OVC217Y, 0VC282Y. OVC01 Y, OVC02CB, OVC03Y, 0VC044Y, OVC16Y, OVC172Y, 0VC175Y, and OVC182Y (Sheet 1034)

BYRON - FPR

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 IVC065 Control Cable For 0VC282Y, OVCO1 Y.

OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC066 Control Cable For 0VC282Y, OVC01 Y, 0VC02Y, OVC03Y, OVCO44Y, OVC04Y, OVC16Y, and OVC172Y 1VC069 Control Cable For 0VC282Y, OVCO1 Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC070 Control Cable For 0VC282Y, OVCO1.Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC076 Control Cable For 0VC282Y, OVCO1VY, OVC02Y, OVC03Y, 0VC044Y, OVC04Y, OVC1 6Y, and OVC172Y 1VC119 Control Cable For OVC01 CB, OVCO1Y, OVC02CB, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, OVC172Y, OVC175Y, OVC182Y, OVC217Y, and 0VC282Y 1VC208 Control Cable For 0VC282Y, OVCO1Y, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC209 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVCI6Y, and OVC172Y 1VC211 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC212 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC1 6Y, and OVC172Y 1VC213 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC214 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVCO44Y. OVC16Y, and OVC172Y 1VC216 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC217 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC219 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1035)

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12122 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC220 Control Cable For 0VC282Y. OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC222 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC223 Control Cable For OVC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC225 Control Cable For OVC282Y, OVCO1 Y, OVC03Y, OVC044Y. OVC16Y, and OVC172Y 1VC226 Control Cable For 0VC282Y. OVCO1 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC228 Control Cable For 0VC282Y, 0VCO0IY, 0VC02Y, OVC03Y, OVC044Y, 0VC04Y, OVC16Y, and 0VC172Y 1VC230 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC231 Control Cable For OVC217Y. 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y 1VC232 Control Cable For 0VC282Y, OVCO1Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y. and OVC172Y 1VC233 Control Cable For OVC282Y, OVCO1 Y. OVC03Y, OVC044Y, OVCI6Y, and OVC172Y 1VC234 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC236 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC237 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC242 Control Cable For OVC01Y. OVC02Y, OVC03Y, and OVC04Y 1VC250 Control Cable For 0VC282Y, OVCO1Y, OVC02CB, OVC03Y, 0VC044Y, OVC16Y, and OVC1 72Y 1VC251 Control Cable For OVC282Y. OVCO1Y.

OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1036)

Affected Equipment EquIpment Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 niv^ 4,.,,1 L,/VIOIUII I 1io Affected Equipment Equipment Equipment In Zone Description 1 VC253 Control Cable For 0VC282Y, OVC01 Y.

OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC254 Control Cable For OVC282Y, OVC01Y, OVG02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC256 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC257 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC262 Control Cable For 0VC282Y, OVCO1 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC263 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC264 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC265 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC266 Control Cable For 0VC282Y, OVCO1VY, OVC03Y, OVC044Y, OVC1B6Y, and OVC172Y 1VC267 Control Cable For OVCO1Y, OVC02Y, OVC03Y.

and OVC04Y 1VC268 Control Cable For OVC282Y, OVCOIY, OVC03Y.

OVC044Y, OVC16Y, and OVC172Y 1VC269 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC270 Control Cable For OVC01Y. OVC02Y, OVC03Y, and OVC04Y 1VC279 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC282 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC285 Control Cable For OVCO1Y, OVC02Y, OVC03Y, OVC04Y, and OVC175Y 1VC288 Control Cable For OVCO0Y, OVC02Y, OVC03Y, OVC04Y, and OVC182Y (Sheet 1037)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cort 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.4-2 1VC291 Control Cable For OVCOIY, OVC02Y, OVCO3Y, OVCO4Y, and OVC182Y 1VC297 Control Cable For OVCOIY, OVCO2Y, OVCO3Y, OVCO4Y, and OVC217Y 1VC431 Control Cable For OVC282Y. OVCOIY, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC574 Control Cable For OVC01Y, OVC02Y, OVC03Y.

and OVC04Y 1VC584 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC614 Control Cable For 0VC02CB, 0VC282Y, OVCO1Y, OVC02Y, OVC03Y, OVC044Y, OVCO4Y, OVC16Y, and OVC172Y 1VC669 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC670 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVCO4Y 1VC671 Control Cable For OVCOIY, OVCO2Y, OVCO3Y, and OVCO4Y IVC672 Control Cable For OVCOIY, OVCO2Y, OVCO3Y, and OVC04Y 1VC673 Control Cable For OVCOIY. OVCO2Y, OVCO3Y, and OVCO4Y 1VC682 Control Cable For OVCO1Y, OVCO2Y, OVCO3Y, and 0VC04Y 1VC683 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC684 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC685 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and 0VC04Y 1VC686 Control Cable For OVCOIY, OVC02Y, OVCO3Y, and OVCO4Y OVC02CB 1VC063 Control Cable For OVC01CB, OVC217Y, 0VC282Y, OVCO1 Y, OVC02CB, OVC03Y, 0VC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y (Sheet 1038)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.4-2 1VC065 Control Cable For 0VC282Y, OVC01Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC067 Power Cable For OVC02CB 1VC069 Control Cable For 0VC282Y, OVCOIY, OVC02CB, OVC03Y, OVC044Y, 0VC16Y, and OVC172Y 1VC070 Control Cable For 0VC282Y, OVCO1 Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC077 Control Cable For 0VC282Y, OVC02CB, and OVC16Y 1VC096 Control Cable For 0VC282Y, OVC02CB, and OVC16Y 1VC119 Control Cable For OVCO1CB, OVCO1Y.

OVC02CB, OVC02Y. OVC03Y, OVC044Y, 0VC04Y, OVC16Y. 0VC172Y, 0VC175Y, OVC182Y, OVC217Y, and 0VC282Y 1VC229 Control Cable For OVC02CB, OVC02Y, and OVCO4Y 1VC250 Control Cable For OVC282Y, OVCO1Y, OVCO2CB, OVCO3Y, OVC044Y, OVCI6Y, and OVC172Y 1VC251 Control Cable For OVC282Y, OVCO1Y.

OVCO2CB, OVC03Y, OVC044Y. OVCl6Y. and OVC172Y 1VC253 Control Cable For OVC282Y. OVCO1Y, OVCO2CB, OVCO3Y, OVC044Y, OVC16Y. and OVC172Y 1VC254 Control Cable For OVC282Y, OVCOI1Y, OVCO2CB, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC280 Control Cable For OVCO2CB, OVCO2Y, and OVCO4Y 1VC281 Control Cable For OVCO2CB, OVCO2Y, and OVCO4Y (Sheet 1039)

BYRON -FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cent 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 1VC585 Control Cable For 0VC02CB, OVC02Y, and OVC04Y IVC586 Control Cable For OVC02CB, OVC02Y, and OVC04Y 1VC614 Control Cable For OVC02CB, 0VC282Y, OVC01Y, OVC02Y, OVC03Y, OVC044Y, OVCO4Y, OVC16Y, and OVC172Y OVC02Y 1PR067 Power Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC039 Control Cable For 0VC282Y, OVCOIY, OVC02Y, OVC03Y, OVC044Y, 0VC04Y, OVC16Y, and OVC172Y 1VC066 Control Cable For 0VC282Y, OVCO1Y, OVC02Y, OVC03Y, 0VC044Y, 0VC04Y, OVC16Y, and OVC172Y 1VC076 Control Cable For 0VC282Y, OVC01Y, OVC02Y, OVC03Y, OVCO44Y, OVCO4Y, OVC16Y. and OVC172Y 1VC081 Control Cable For 0VC282Y, 0VC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC119 Control Cable For OVC01CB, OVC01Y, OVC02CB. OVC02Y, OVC03Y, 0VC044Y, OVC04Y, OVC16Y, OVC172Y, OVC175Y, OVC182Y, OVC217Y. and OVC282Y 1VC228 Control Cable For 0VC282Y. OVCO1 Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC1B6Y. and OVC172Y 1VC229 Control Cable For OVC02CB, OVC02Y, and 0VCO4Y 1VC232 Control Cable For 0VC282Y, OVCO1Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC1B6Y. and OVC172Y 1VC242 Control Cable For OVCO1Y. OVCO2Y, OVC03Y, and OVC04Y 1VC264 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y (Sheet 1040)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 Division 12/22 Affected Equipment Equipment Equipment In Zone Description 1VC267 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC270 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC271 Control Cable For OVC02Y and OVC04Y 1VC272 Control Cable For OVC02Y and OVC04Y 1VC274 Control Cable For OVC02Y and OVC04Y 1VC275 Control Cable For OVC02Y and OVC04Y 1VC277 Control Cable For OVC02Y and OVCO4Y 1VC278 Control Cable For OVC02Y and OVC04Y 1VC279 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC280 Control Cable For OVC02CB, OVC02Y. and OVCO4Y 1VC281 Control Cable For OVC02CB, OVCO2Y, and OVC04Y 1VC282 Control Cable For OVCO1Y. OVC02Y, OVC03Y, and OVC04Y 1VC285 Control Cable For OVC01Y, OVC02Y, OVC03Y, OVC04Y, and OVC175Y 1 VC288 Control Cable For OVCOIY, OVC02Y, OVC03Y, OVC04Y, and OVC182Y 1VC291 Control Cable For OVC01Y, OVC02Y, OVC03Y, OVC04Y, and OVC182Y 1VC297 Control Cable For OVC01Y, OVC02Y, OVC03Y.

OVC04Y, and OVC217Y 1VC459 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC460 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVCO44Y, OVC04Y, and OVC16Y 1VC574 Control Cable For OVC01Y, OVC02Y, 0VC03Y, and 0VC04Y 1VC579 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC584 Control Cable For OVCOI1Y, OVC02Y. OVC03Y, and OVC04Y (Sheet 1041)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont' d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 1VC585 Control Cable For OVC02CB, OVC02Y. and OVC04Y 1VC586 Control Cable For OVCO2CB, OVC02Y, and OVC04Y 1VC614 Control Cable For OVC02CB, 0VC282Y, OVCO1Y, 0VC02Y, 0VC03Y, OVC044Y, OVC04Y.

OVC16Y, and OVC172Y 1VC661 Control Cable For OVC02Y and OVC04Y 1VC662 Control Cable For OVC02Y and OVC04Y 1VC663 Control Cable For OVC02Y and OVC04Y 1VC664 Control Cable For OVC02Y and OVC04Y 1VC665 Control Cable For OVC02Y and OVC04Y 1VC666 Control Cable For OVC02Y and OVC04Y 1VC667 Control Cable For OVC02Y and OVC04Y 1VC668 Control Cable For OVCO2Y and OVC04Y 1VC669 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVCO4Y 1VC670 Control Cable For OVC01Y, OVC02Y, OVC03Y.

and OVCO4Y 1VC671 Control Cable For OVCO1Y, OVCO2Y. OVCO3Y, and OVCO4Y 1VC672 Control Cable For OVCOtVY, OVCO2Y, OVCO3Y, and OVCO4Y 1VC673 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC674 Control Cable For OVC02Y and OVC04Y 1VC675 Control Cable For OVC02Y and OVC04Y 1VC676 Control Cable For OVC02Y and OVC04Y 1VC677 Control Cable For OVC02Y and OVC04Y 1VC678 Control Cable For OVC02Y and OVC04Y 1VC679 Control Cable For OVC02Y and 0VC04Y 1VC680 Control Cable For OVC02Y and 0VC04Y 1VC681 Control Cable For OVC02Y and OVCO4Y (Sheet 1042)

"K-j

BYRON -FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC682 Control Cable For OVCO1Y, OVCO2Y, OVCO3Y, and OVCO4Y 1VC683 Control Cable For OVC01Y, 0VC02Y, OVC03Y, and OVC04Y 1VC684 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC685 Control Cable For 0VC01Y, OVC02Y, OVCO3Y, and OVC04Y 1VC686 Control Cable For 0VC01Y, OVCO2Y. OVC03Y, and 0VC04Y OVC03Y 1FP115 Control Cable For OVCO1CB, 0VC282Y, OVC01Y, OVC03Y. OVC044Y. OVC16Y, and OVC172Y 1 PRO67 Power Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC039 Control Cable For OVC282Y, 0VC01Y, OVC02Y, OVC03Y, 0VC044Y, 0VC04Y, OVC16Y, and OVC172Y 1VC063 Control Cable For OVC01CB, OVC217Y, 0VC282Y, OVCO1Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, 0VC172Y, OVC175Y, and OVC182Y 1VC065 Control Cable For 0VC282Y, OVC01Y, OVC02CB, OVC03Y. OVC044Y, OVC16Y. and OVC172Y 1VC066 Control Cable For OVC282Y, OVCO1VY, OVCO2Y, OVC03Y, OVC044Y, 0VC04Y, OVC16Y. and OVC172Y 1VC069 Control Cable For OVC282Y, 0VC01Y, OVCO2CB, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC070 Control Cable For OVC282Y, OVC01Y.

OVC02CB, OVC03Y, OVC044Y. OVC16Y, and OVC172Y 1VC076 Control Cable For 0VC282Y, OVC01Y. OVC02Y, OVC03Y, 0VC044Y, OVC04Y, OVC16Y, and OVC172Y (Sheet 1043)

BYRON -FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC081 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC119 Control Cable For OVCOICB, OVC01Y, OVC02CB, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, OVC1172Y, OVC175Y, OVC182Y, OVC217Y, and 0VC282Y 1VC208 Control Cable For OVC282Y, OVC01Y. OVC03Y, OVC044Y, OVC1 6Y, and OVC172Y 1VC209 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVCO44Y. OVC16Y, and OVC172Y 1VC211 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC212 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC213 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC214 Control Cable For OVC282Y, OVCO1Y, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC216 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC217 Control Cable For 0VC282Y, OVC01Y. OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC219 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC220 Control Cable For OVC282Y, OVC01 Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC222 Control Cable For 0VC282Y, OVC01VY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC223 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC1B6Y. and OVC172Y 1VC225 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC226 Control Cable For 0VC282Y, OVCO1 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC228 Control Cable For 0VC282Y, OVC01Y, OVC02Y, OVC03Y. OVCO44Y, OVC04Y, OVC16Y, and OVC172Y (Sheet 1044)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 1VC230 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC231 Control Cable For OVC217Y, 0VC282Y, OVCO1Y, OVC03Y. 0VC044Y, OVC16Y. OVC172Y.

OVC175Y, and OVCI82Y 1VC232 Control Cable For 0VC282Y, OVC01 Y. OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, and OVC172Y 1VC233 Control Cable For 0VC282Y, OVCO1Y, OVC03Y.

OVC044Y, OVC16Y, and OVC172Y 1VC234 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC236 Control Cable For OVC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and 0VC172Y 1VC237 Control Cable For OVC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC242 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC250 Control Cable For OVC282Y, OVC01 Y, OVC02CB, OVCO3Y. OVC044Y, OVC16Y. and OVC172Y 1VC251 Control Cable For 0VC282Y, OVC01Y, OVC02CB, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC253 Control Cable For 0VC282Y, OVC01Y, 0VC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC254 Control Cable For OVC282Y, OVCO1Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC256 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC257 Control Cable For 0VC282Y, OVCO1Y, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC262 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1045)

Affected Equipment Equipment Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 BYRON -FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

DMsion 11/21 Division 12/22 Affected Equipment Equipment Equipment In Zone Description 1VC263 Control Cable For 0VC282Y, OVCOIY, OVC03Y.

OVC044Y, OVC16Y, and 0VC172Y 1VC264 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC265 Control Cable For OVC282Y, OVC01Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC266 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC267 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC268 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC269 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC270 Control Cable For OVC01Y, OVCO2Y, OVC03Y, and OVC04Y 1VC279 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1 VC282 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC285 Control Cable For OVC01Y, OVCO2Y, OVC03Y, OVC04Y, and OVC175Y 1VC288 Control Cable For OVC01Y, OVC02Y, OVC03Y, OVC04Y, and OVC182Y 1VC291 Control Cable For OVC01Y, OVC02Y, OVC03Y, OVC04Y, and OVC182Y 1VC297 Control Cable For OVC01Y, OVC02Y, OVC03Y.

OVC04Y, and OVC217Y 1VC431 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC459 Control Cable For 0VC282Y. OVC02Y, OVC03Y, OVC044Y, OVCO4Y, and OVC16Y 1VC460 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVCO44Y, OVC04Y, and OVC16Y 1VC574 Control Cable For OVCO1Y, OVC02Y, OVC03Y.

and OVC04Y (Sheet 1046)

I

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC579 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC584 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC614 Control Cable For OVC02CB, 0VC282Y, 0VC01Y, OVC02Y, OVC03Y. OVC044Y, OVC04Y, OVC16Y, and OVC172Y 1VC669 Control Cable For OVCOIY, OVCO2Y, OVC03Y, and OVCO4Y 1VC670 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC671 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC672 Control Cable For OVC01 Y, OVC02Y, OVC03Y, and OVC04Y 1VC673 Control Cable For OVCO1 Y, OVC02Y, OVC03Y, and OVCO4Y 1VC682 Control Cable For OVCOIY, OVC02Y. OVC03Y, and OVC04Y 1VC683 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC684 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC685 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC686 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y OVCO44Y 1FP115 Control Cable For OVCOICB, OVC282Y, OVCOIY, OVCO3Y, OVC044Y, OVCI6Y. and OVC172Y 1PR067 Power Cable For OVC282Y, OVCO2Y, OVCO3Y, OVCO44Y, OVCO4Y, and OVC16Y 1PR068 Power Cable For 0VC282Y, OVC044Y, and OVC16Y 1VC039 Control Cable For 0VC282Y, OVCO1Y, OVC02Y, OVC03Y, 0VC044Y, OVCO4Y, OVC16Y, and OVC172Y (Sheet 1047)

BYRON -FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.4-2 1VC063 Control Cable For OVCO1 CB, OVC217Y, 0VC282Y, OVC01Y, OVC02CB, OVC03Y.

OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y 1VC065 Control Cable For 0VC282Y, OVCO1Y, OVCO2CB, OVC03Y. 0VC044Y, OVC16Y, and OVC172Y 1VC066 Control Cable For 0VC282Y, OVCO1Y, OVCO2Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y. and OVC172Y 1VC069 Control Cable For 0VC282Y, OVCOIY, OVC02CB, OVCO3Y, 0VC044Y, OVC16Y, and OVC172Y 1VC070 Control Cable For 0VC282Y, OVC01Y, OVC02CB, 0VC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC076 Control Cable For 0VC282Y. OVC01 Y, OVC02Y, OVC03Y. OVCO44Y, OVCO4Y, OVC16Y, and OVC172Y 1VC081 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y. and OVC16Y 1VC119 Control Cable For OVCOlCB, OVC01Y, OVC02CB, OVC02Y, OVCO3Y, OVC044Y, OVC04Y, OVC16Y. 0VC172Y, OVC175Y.

OVC182Y, OVC217Y, and OVC282Y 1VC208 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC209 Control Cable For OVC282Y, OVCO1Y, OVC03Y, OVC044Y. OVC16Y, and OVC172Y 1VC210 Control Cable For OVC044Y 1VC211 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC212 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC213 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y (Sheet 1048)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12122 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 1VC214 Control Cable For 0VC282Y, OVC01Y. OVC03Y, OVC044Y, OVC16Y. and 0VC172Y 1VC215 Control Cable For OVCO44Y 1VC216 Control Cable For 0VC282Y. OVCOIY, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC217 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVCI6Y, and OVC172Y 1VC218 Control Cable For OVC044Y 1VC219 Control Cable For 0VC282Y. OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC220 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVCO44Y, OVCI6Y, and OVC172Y 1VC221 Control Cable For OVC044Y 1VC222 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVCI16Y, and OVC172Y 1VC223 Control Cable For 0VC282Y, OVCO1Y. OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC224 Control Cable For OVC044Y 1VC225 Control Cable For 0VC282Y. OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC226 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC227 Control Cable For OVC044Y 1VC228 Control Cable For 0VC282Y, OVC01 Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, and OVC172Y 1VC230 Control Cable For 0VC282Y, OVCO1Y, OVC03Y.

OVC044Y. OVC16Y, and OVC172Y 1VC231 Control Cable For OVC217Y, 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y. OVC172Y, OVCI75Y. and OVC182Y 1VC232 Control Cable For 0VC282Y, OVCO1Y. OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, and OVC172Y 1VC233 Control Cable For 0VC282Y, OVC01VY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1049)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12122 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.4-2 1VC234 Control Cable For 0VC282Y, OVCO1Y. OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC235 Control Cable For OVC044Y 1VC236 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and 0VC172Y 1VC237 Control Cable For 0VC282Y, OVC01VY, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC238 Control Cable For OVC044Y 1VC244 Control Cable For OVCO44Y 1VC245 Control Cable For OVCO44Y 1VC250 Control Cable For 0VC282Y, OVCO1Y, OVC02CB, 0VC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC251 Control Cable For 0VC282Y, OVCOIY, OVC02CB, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC253 Control Cable For 0VC282Y, OVCO1Y.

OVC02CB, OVC03Y, OVC044Y, OVC1 6Y, and OVC172Y 1VC254 Control Cable For 0VC282Y, OVCOIY.

OVC02CB, OVC03Y, 0VC044Y. OVC16Y, and OVC172Y 1VC256 Control Cable For 0VC282Y, 0VCO1Y, OVCO3Y, OVC044Y, OVC1B6Y, and OVC172Y 1VC257 Control Cable For 0VC282Y, OVCO1Y, OVCO3Y, OVC044Y, OVC1B6Y, and 0VC172Y 1VC262 Control Cable For 0VC282Y, 0VCO1Y, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC263 Control Cable For OVC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1 VC265 Control Cable For OVC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1 VC266 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC268 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1050)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC269 Control Cable For 0VC282Y, OVCO1 Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC431 Control Cable For 0VC282Y. OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC436 Control Cable For OVC044Y 1VC459 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC460 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y. OVC04Y, and OVC16Y 1VC479 Control Cable For OVC044Y 1VC576 Control Cable For OVC044Y 1VC579 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC614 Control Cable For OVC02CB, 0VC282Y, OVCO1Y, OVC02Y, OVC03Y, OVC044Y, 0VC04Y, 0VC16Y. and OVC172Y OVC04Y 1 PR067 Power Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC039 Control Cable For 0VC282Y, OVC01Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y. OVC16Y, and OVC172Y 1VC066 Control Cable For 0VC282Y, OVCO1 Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y. OVC16Y, and OVC172Y 1VC076 Control Cable For OVC282Y, OVCO1 Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16BY, and OVC172Y 1VC081 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC119 Control Cable For OVC01CB, OVCO1Y, 0VC02CB, OVC02Y, OVC03Y, 0VC044Y, OVC04Y, OVC16Y, OVC172Y, OVC175Y, OVC182Y, OVC217Y, and 0VC282Y 1VC228 Control Cable For 0VC282Y, OVCOIY, OVC02Y, OVC03Y, OVCO44Y, OVC04Y, OVC16Y, and OVC172Y (Sheet 1051)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

DMsion 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 1VC229 Control Cable For OVCO2CB, OVCO2Y, and OVC04Y 1VC232 Control Cable For 0VC282Y, OVC01Y, OVC02Y, OVC03Y, OVCO44Y, OVC04Y, OVC16Y, and OVC172Y 1VC242 Control Cable For OVCO1Y, OVC02Y, OVCO3Y, and OVC04Y 1VC264 Control Cable For OVCO1Y, OVC02Y, OVCO3Y, and OVC04Y 1VC267 Control Cable For 0VC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC270 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC271 Control Cable For OVC02Y and OVC04Y 1VC272 Control Cable For OVC02Y and OVC04Y 1VC274 Control Cable For OVC02Y and OVCO4Y 1VC275 Control Cable For OVC02Y and OVC04Y IVC277 Control Cable For OVC02Y and OVC04Y 1VC278 Control Cable For OVC02Y and OVC04Y 1VC279 Control Cable For OVCOIY, OVC02Y. OVC03Y, and OVC04Y 1VC280 Control Cable For OVC02CB, OVC02Y. and OVC04Y 1VC281 Control Cable For OVC02CB, OVC02Y, and OVC04Y 1VC282 Control Cable For OVCO1Y, OVC02Y. OVC03Y, and OVC04Y 1VC285 Control Cable For OVC01Y, OVC02Y. OVC03Y, OVC04Y, and OVC175Y 1VC288 Control Cable For OVC01Y, OVC02Y, OVC03Y, 0VC04Y, and OVC182Y 1VC291 Control Cable For OVCO1Y, OVC02Y, OVC03Y, OVC04Y, and OVC182Y 1VC297 Control Cable For OVC01Y, OVC02Y, OVC03Y, OVC04Y, and OVC217Y (Sheet 1052)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC459 Control Cable For 0VC282Y, OVC02Y, OVC03Y.

OVC044Y, OVC04Y, and OVC16Y 1VC460 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC574 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y 1VC579 Control Cable For 0VC282Y, 0VC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC584 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC585 Control Cable For OVC02CB, OVC02Y, and OVCO4Y 1VC586 Control Cable For OVC02CB, OVC02Y, and OVC04Y IVC614 Control Cable For OVC02CB, 0VC282Y, OVC01Y. OVC02Y, OVC03Y, OVC044Y, OVC04Y.

OVC16Y, and OVC172Y 1VC661 Control Cable For OVC02Y and OVC04Y 1VC662 Control Cable For OVC02Y and OVCO4Y 1VC663 Control Cable For OVC02Y and OVCO4Y 1VC664 Control Cable For OVC02Y and OVC04Y 1VC665 Control Cable For OVC02Y and OVC04Y 1VC666 Control Cable For OVC02Y and OVC04Y 1VC667 Control Cable For OVC02Y and OVC04Y 1VC668 Control Cable For OVC02Y and OVCO4Y "1VC669 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC670 Control Cable For OVCOIY, OVC02Y. 0VCO3Y, and OVC04Y 1VC671 Control Cable For OVCO1Y, OVC02Y, OVCO3Y, and OVC04Y 1VC672 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVC04Y 1VC673 Control Cable For OVCO1VY, OVC02Y, OVC03Y, and OVC04Y (Sheet 1053)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 1121 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC674 Control Cable For OVC02Y and OVC04Y 1VC675 Control Cable For OVC02Y and OVC04Y 1VC676 Control Cable For OVC02Y and OVC04Y 1VC677 Control Cable For OVC02Y and OVC04Y 1VC678 Control Cable For OVC02Y and OVC04Y 1VC679 Control Cable For OVC02Y and OVC04Y 1VC680 Control Cable For OVCO2Y and OVC04Y 1VC681 Control Cable For OVCO2Y and OVC04Y 1VC682 Control Cable For OVC01Y, OVC02Y, OVC03Y, and OVCO4Y 1VC683 Control Cable For OVCOIY, OVCO2Y, OVCO3Y, and OVCO4Y 1VC684 Control Cable For OVC01Y, OVC02Y, OVCO3Y, and OVC04Y 1VC685 Control Cable For OVCO1 Y, OVCO2Y, OVC03Y, and OVC04Y 1VC686 Control Cable For OVCO1Y, OVC02Y, OVC03Y, and OVC04Y OVC16Y 1 FP1 15 Control Cable For OVCO1CB, 0VC282Y, OVCO1Y, OVCO3Y, OVC044Y, OVC16Y. and OVC172Y 1FP127 Control Cable For 0VC282Y and OVC16Y 1FP158 Control Cable For 0VC282Y and OVC16Y 1PR067 Power Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1PR068 Power Cable For 0VC282Y, OVC044Y, and OVC16Y 1VC039 Control Cable For 0VC282Y, OVCO1Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, and OVC172Y 1VC063 Control Cable For OVCOICB, OVC217Y, 0VC282Y, OVC0IY. OVC02CB, OVC03Y.

OVC044Y, OVC16Y, OVC172Y, OVCl75Y, and OVC182Y (Sheet 1054)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Divsion 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC065 Control Cable For 0VC282Y. OVC01Y.

OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC066 Control Cable For 0VC282Y. OVC01Y. 0VC02Y, OVC03Y, OVC044Y, 0VC04Y, OVC16Y, and OVC172Y 1VC069 Control Cable For 0VC282Y. OVC01Y, OVC02CB, OVC03Y. OVC044Y.

VOM16Y. and OVC1 72Y 1VC070 Control Cable For OVC282Y, OVCO1Y.

OVC02CB, 0VC03Y. OVC044Y. OVC16Y. and OVC172Y 1VC076 Control Cable For 0VC282Y, OVCO0Y. OVC02Y.

0VC03Y, OVC044Y, OVC04Y. OVC16Y, and OVC172Y 1VC077 Control Cable For 0VC282Y, OVC02CB, and 0VC16Y 1VC081 Control Cable For 0VC282Y, OVC02Y, OVC03Y, 0VC044Y, OVC04Y, and OVC16Y 1VC096 Control Cable For 0VC282Y, OVC02CB, and OVC16Y 1VC119 Control Cable For0OVCO1CB, 0VCO1Y, OVC02CB, 0VC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, 0VC172Y, OVC175Y, OVC182Y, OVC217Y, and 0VC282Y 1VC208 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC209 Control Cable For OVC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC211 Control Cable For 0VC282Y. OVC01Y, OVC03Y, OVC044Y, OVC16Y. and 0VC172Y 1VC212 Control Cable For 0VC282Y. OVC01Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC213 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16BY, and OVC1 72Y 1VC214 Control Cable For 0VC282Y, OVCOIY. OVC03Y, OVC044Y, OVC1B6Y, and OVC172Y (Sheet 1055)

BYRON -FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC216 Control Cable For OVC282Y, OVCO1Y, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC217 Control Cable For OVC282Y, OVCO1 Y, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC219 Control Cable For OVC282Y, OVC01VY, OVCO3Y, OVCO44Y. OVC16Y, and OVC172Y 1VC220 Control Cable For OVC282Y, OVC01Y, OVC03Y.

OVC044Y, OVC16Y, and 0VC172Y 1VC222 Control Cable For 0VC282Y, OVCOI1Y OVC03Y.

OVC044Y, OVC16Y, and OVC172Y 1VC223 Control Cable For OVC282Y, OVC01Y, OVC03Y.

OVC044Y, OVC16Y. and OVC172Y 1VC225 Control Cable For 0VC282Y, OVCO1Y. OVC03Y.

OVCO44Y, OVCI16Y. and OVC172Y 1VC226 Control Cable For 0VC282Y. OVCO1Y. OVC03Y.

OVC044Y. OVC1B6Y, and OVC172Y 1VC228 Control Cable For 0VC282Y, OV001Y. 0VCO2Y.

OVC03Y, OVC044Y, OVC04Y, OVC16Y. and OVC172Y 1VC230 Control Cable For 0VC282Y, OVCO1 Y. OVC03Y, OVC044Y, OVC1B6Y, and OVC172Y 1VC231 Control Cable For 0VC217Y, 0VC282Y, OVCO1Y.

OVC03Y, OVC044Y. OVC16Y, OVC172Y.

OVC175Y, and OVC182Y 1VC232 Control Cable For 0VC282Y. OVCO1Y. OVC02Y, OVC03Y, 0VC044Y. OVC04Y. OVC16Y, and OVC172Y 1VC233 Control Cable For 0VC282Y. OVCO1Y. OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC234 Control Cable For OVC282Y. OVCO1Y, OVC03Y.

OVC044Y, OVC16Y. and OVC172Y 1VC236 Control Cable For 0VC282Y. OVC01Y,. OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC237 Control Cable For 0VC282Y. OVC01Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC243 Control Cable For OVC16Y, OVC172Y, and 0VC282Y (Sheet 1056)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12=22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 IVC250 Control Cable For 0VC282Y. OVCOIY, OVC02CB, OVCO3Y, 0VC044Y, OVC16Y, and OVC172Y 1VC251 Control Cable For OVC282Y, OVCO1Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC252 Control Cable For OVC16Y, OVC172Y, and 0VC282Y 1VC253 Control Cable For OVC282Y, OVC01Y.

OVC02CB, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC254 Control Cable For 0VC282Y, OVC01VY, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC255 Control Cable For OVC16Y, OVC172Y, and OVC282Y 1VC256 Control Cable For 0VC282Y, OVCO1 Y, OVC03Y, 0VC044Y, OVC16Y, and 0VC172Y 1VC257 Control Cable For 0VC282Y, 0VCO1 Y, OVC03Y, 0VC044Y, OVC16Y, and 0VC172Y 1VC258 Control Cable For OVC16Y, OVC172Y, and 0VC282Y 1VC262 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVCI72Y 1VC263 Control Cable For 0VC282YV OVC01Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC265 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC266 Control Cable For 0VC282Y. OVC0IY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC268 Control Cable For 0VC282Y. OVC01Y. OVC03Y.

OVC044Y, OVC16Y. and OVC172Y 1VC269 Control Cable For 0VC282Y, OVC01VY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC431 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC1B6Y. and OVCI72Y (Sheet 1057)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 I

(Sheet 1058)

Division 12/22 Affected Equipment Equipment Equipment In Zone Description IVC459 Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1VC460 Control Cable For OVC282Y, OVC02Y, OVC03Y, 0VC044Y, OVC04Y, and OVC16Y 1VC575 Control Cable For OVC16Y, 0VC172Y, and 0VC282Y 1VC579 Control Cable For OVC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC1 6Y 1VC614 Control Cable For OVC02CB, 0VC282Y, OVCO1Y, OVC02Y, 0VC03Y, OVC044Y, OVC04Y, OVC16Y, and OVC172Y OVC172Y 1FP115 Control Cable For OVCO1CB, 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC039 Control Cable For 0VC282Y, OVC01Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, and OVC172Y 1VC063 Control Cable For OVC01CB, OVC217Y, 0VC282Y, OVC01Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y 1VC065 Control Cable For 0VC282Y, OVC01Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC066 Control Cable For 0VC282Y. OVC01Y, OVC02Y, OVC03Y, OVC044Y. OVC04Y, OVC16Y, and OVC172Y 1VC069 Control Cable For OVC282Y, OVCO1Y, OVCO2CB, OVCO3Y, OVCO44Y. OVC16Y, and OVC172Y 1VC070 Control Cable For OVC282Y, OVCO1Y.

OVCO2CB, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC076 Control Cable For OVC282Y, OVCO1Y, OVCO2Y, OVCO3Y, OVCO44Y. OVCO4Y, OVC16Y, and OVC172Y

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 IVC119 Control Cable For OVC01CB, OVCO1 Y, OVC02CB, OVC02Y, OVC03Y, OVCO44Y, 0VC04Y, OVC16Y, OVC172Y, OVC175Y, 0VC182Y, OVC217Y, and 0VC282Y 1VC208 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC209 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC211 Control Cable For 0VC282Y, OVC01VY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC212 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC1B6Y, and OVC172Y 1VC213 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC1B6Y, and OVC172Y 1VC214 Control Cable For 0VC282Y. OVCOIY, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC216 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC217 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and 0VC172Y 1VC219 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVCO44Y, OVC16Y, and 0VC172Y 1VC220 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC1 6Y, and OVC172Y 1VC222 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC223 Control Cable For OVC282Y, OVCOIY, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC225 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC226 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC228 Control Cable For 0VC282Y. OVCO1Y, OVC02Y, OVC03Y, 0VC044Y, 0VC04Y, OVC16Y, and OVC172Y 1VC230 Control Cable For 0VC282Y, OVC01 Y, OVC03Y, OVC044Y. OVC16Y, and OVC172Y (Sheet 1059)

BYRON. FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

DMslon 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC231 Control Cable For OVC217Y, 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC1 6Y, OVC172Y, OVC175Y, and OVC182Y 1VC232 Control Cable For 0VC282Y, OVC01Y, OVC02Y, OVC03Y, 0VC044Y, 0VC04Y, OVC16Y, and OVC1 72Y 1VC233 Control Cable For 0VC282Y, OVCOIY. OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC234 Control Cable For 0VC282Y. OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC236 Control Cable For 0VC282Y, OVC01Y, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC237 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC243 Control Cable For OVC16Y, OVC172Y, and OVC282Y 1VC250 Control Cable For OVC282Y, OVCOIY, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC251 Control Cable For 0VC282Y, OVC01Y, OVC02CB, OVC03Y, OVCG44Y, OVCI6Y, and OVC172Y 1VC252 Control Cable For OVCI16Y. OVC172Y. and 0VC282Y 1VC253 Control Cable For 0VC282Y, OVC01Y, OVC02CB, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC254 Control Cable For OVC282Y, OVC01Y.

OVC02CB, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC255 Control Cable For OVC1B6Y, OVCI72Y, and 0VC282Y 1VC256 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y, 0VC16Y, and OVC172Y 1VC257 Control Cable For 0VC282Y. OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1060)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number-.

18.4-2 1VC258 Control Cable For OVC16Y, 0VC 172Y, and 0VC282Y 1VC262 Control Cable For 0VC282Y, OVCO1Y. OVC03Y, OVC044Y. OVC16Y, and OVC172Y 1VC263 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC265 Control Cable For 0VC282Y. OVC01Y. OVC03Y, OVC044Y, OVC16Y. and OVC172Y 1VC266 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC1 6Y, and OVC172Y 1VC268 Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVC044Y. OVC16Y, and OVC172Y 1VC269 Control Cable For OVC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC431 Control Cable For 0VC282Y, OVCO1 Y, OVC03Y, OVC044Y. OVCI16Y, and OVCI72Y 1VC575 Control Cable For OVC16Y, OVC172Y. and 0VC282Y 1VC614 Control Cable For OVC02CB. OVC282Y.

OVCO1Y. OVC02Y. OVC03Y, OVC044Y. OVCO4Y, OVC16Y, and OVC172Y OVC175Y 1VC063 Control Cable For OVCO1CB, OVC217Y, OVC282Y, 0VC01Y. OVC02CB, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y 1VC119 Control Cable For OVC01CB, OVC01Y, OVC02CB. OVCO2Y, OVC03Y, 0VCO44Y, OVC04Y, OVC16Y, OVC172Y, OVC175Y, OVC182Y, OVC217Y. and 0VC282Y 1VC231 Control Cable For OVC217Y, OVC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y 1VC285 Control Cable For OVCO1Y, OVC02Y, OVC03Y, OVC04Y, and OVC175Y (Sheet 1061)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Divislon 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.4-2 OVC182Y 1VC063 Control Cable For OVC01CB. OVC217Y.

0VC282Y, OVC01Y, OVC02CB, OVC03Y, 0VC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC1 82Y 1VC119 Control Cable For OVC01CB, OVCO1Y, OVC02CB, OVC02Y, OVC03Y. OVCO44Y, 0VC04Y, OVC16Y, OVC172Y, OVC175Y, OVC182Y, OVC217Y, and 0VC282Y 1VC231 Control Cable For OVC217Y, OVC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y 1VC288 Control Cable For 0VCO1Y, OVC02Y, OVCO3Y, OVC04Y, and OVC182Y IVC291 Control Cable For OVC01Y, OVCO2Y, OVC03Y, OVC04Y, and OVC182Y OVC217Y 1VC063 Control Cable For OVC01CB, OVC217Y, 0VC282Y, OVCOIY, OVC02CB, OVC03Y.

OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y IVC1I9 Control Cable For OVC01CB, OVCO1Y, OVC02CB. 0VC02Y, OVC03Y, 0VC044Y, OVC04Y, OVC16Y, OVC172Y, 0VC175Y, OVC182Y, OVC217Y. and 0VC282Y 1VC231 Control Cable For OVC217Y, 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y, and OVC182Y 1VC297 Control Cable For OVC01Y, OVC02Y, OVC03Y, OVC04Y, and OVC217Y 0VC282Y 1FP115 Control Cable For OVCO1CB, OVC282Y, OVCO1Y, OVC03Y. OVC044Y, OVC16Y, and OVC172Y 1 FP127 Control Cable For 0VC282Y and OVC16Y I FP158 Control Cable For 0VC282Y and OVC16Y 1 PRO67 Power Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC16Y 1 PR068 Power Cable For 0VC282Y, OVC044Y, and OVC16Y (Sheet 1062)

BYRON -FPSAMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.4-2 1VC039 Control Cable For 0VC282Y, OVC01 Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, OVC16Y, and OVC172Y 1VC063 Control Cable For OVC01CB, OVC217Y, OVC282Y, OVCO1Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, OVC172Y, OVC175Y. and OVC182Y 1VC065 Control Cable For 0VC282Y, OVC01 Y.

OVC02CB. OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC066 Control Cable For 0VC282Y, OVC01Y, OVC02Y, OVCO3Y, OVCO44Y, OVC04Y, OVC16Y, and OVC172Y 1VC069 Control Cable For 0VC282Y, OVC01Y, OVC02CB, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC070 Control Cable For OVC282Y, OVC0I Y, OVCO2CB, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC076 Control Cable For OVC282Y, OVC01Y, OVCO2Y, OVCO3Y, OVCO44Y, OVCO4Y, OVC16Y, and OVC172Y 1VC077 Control Cable For 0VC282Y, OVC02CB, and OVC16Y 1VC081 Control Cable For 0VC282Y, OVC02Y, OVC03Y.

OVC044Y, OVC04Y, and OVC16Y 1VC096 Control Cable For 0VC282Y, OVC02CB, and OVC16Y IVC119 Control Cable For OVCOlCB, OVCO1Y, OVC02CB, OVC02Y, 0VC03Y, OVC044Y, OVC04Y, OVC16Y, 0VC172Y, OVC175Y, OVCI182Y, OVC217Y, and 0VC282Y 1VC208 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC209 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC211 Control Cable For 0VC282Y, OVCO1 Y, 0VCO3Y.

0VC044Y, OVC16Y, and OVC172Y (Sheet 1063)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Dision 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.4-2 1VC212 Control Cable For 0VC282Y, OVC01VY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC213 Control Cable For 0VC282Y, OVCO1Y. OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC214 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC216 Control Cable For OVC282Y, OVCOIY, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC217 Control Cable For OVC282Y, OVCO1Y, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC219 Control Cable For OVC282Y, OVCOIY, OVCO3Y.

OVCO44Y, OVC16Y, and OVC172Y 1VC220 Control Cable For OVC282Y, OVCOI1Y, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC222 Control Cable For OVC282Y, OVCO1Y, OVCO3Y, OVCO44Y, OVC16Y, and OVC172Y 1VC223 Control Cable For OVC282Y, OVCO1Y, OVCO3Y, OVCO44Y, OVC16Y. and OVC172Y 1VC225 Control Cable For OVC282Y, OVCOIY. OVCO3Y, OVCO44Y, OVC16Y. and OVC172Y 1VC226 Control Cable For OVC282Y, OVCO1Y, OVCO3Y, OVCO44Y. OVC16Y, and OVC172Y 1VC228 Control Cable For OVC282Y, OVCO1Y, OVCO2Y.

OVCO3Y, OVCO44Y, OVCO4Y, OVC1 6Y. and OVC172Y 1VC230 Control Cable For OVC282Y, OVCO1Y, OVCO3Y.

OVCO44Y, OVCM6Y. and OVC172Y 1VC231 Control Cable For OVC217Y, OVC282Y, OVCO1Y, OVCO3Y, OVCO44Y. OVC16Y. OVC172Y, OVC175Y, and OVC182Y 1VC232 Control Cable For OVC282Y, OVCO1Y. OVCO2Y, OVCO3Y. OVCO44Y, OVC04Y, OVC16Y. and OVC172Y 1VC233 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC234 Control Cable For OVC282Y, OVCO1VY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1064)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

DMslon 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 1VC236 Control Cable For 0VC282Y, 0VC01Y, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC237 Control Cable For OVC282Y, 0VC01Y, OVC03Y, OVC044Y, OVC1 6Y, and OVC172Y 1VC243 Control Cable For OVC16Y, OVC172Y, and 0VC282Y 1VC250 Control Cable For OVC282Y, OVCO1 Y.

OVCO2CB, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC251 Control Cable For OVC282Y, OVCOI1Y, OVCO2CB, OVCO3Y, OVC044Y, OVC16Y, and OVC172Y 1VC252 Control Cable For OVC16Y, OVC172Y, and OVC282Y 1VC253 Control Cable For OVC282Y, OVCO1Y, OVC02CB, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC254 Control Cable For 0VC282Y. OVCO1Y, OVC02CB. OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC255 Control Cable For OVC16Y, OVC172Y, and 0VC282Y IVC256 Control Cable For 0VC282Yo OVC01 Y, OVC03Y, 0VC044Y, OVC16Y, and OVC172Y 1VC257 Control Cable For 0VC282Y, OVC01Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y 1VC258 Control Cable For OVC16Y, OVC172Y, and 0VC282Y 1VC262 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVCO44Y, OVCI6Y, and OVC172Y 1VC263 Control Cable For 0VC282Y, OVCO1 Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC265 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y 1VC266 Control Cable For OVC282Y, OVCO1Y, 0VCO3Y, OVC044Y, OVC16Y, and OVC172Y (Sheet 1065)

AMENDMER 00 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.4-2 Division 12/22 Affected Equipment Equipment Equipment In Zone Description 1VC268 1VC269 1VC431 1VC459 1VC460 1VC575 1VC579 1VC614 Control Cable For 0VC282Y, OVCO1Y, OVC03Y, OVC044Y, OVC16Y, and OVC172Y Control Cable For OVC282Y, OVC01VY, OVC03Y, OVC044Y, OVC16Y, and OVC172Y Control Cable For 0VC282Y, OVCOIY, OVC03Y, OVCO44Y, OVC16Y, and OVC172Y Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVCO44Y, OVC04Y, and OVC16Y Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y, and OVC1 6Y Control Cable For OVC16Y. OVC172Y, and 0VC282Y Control Cable For 0VC282Y, OVC02Y, OVC03Y, OVC044Y, OVC04Y. and OVC16Y Control Cable For OVC02CB, 0VC282Y, OVC01Y, OVC02Y, OVC03Y, OVC044Y, OVCO4Y, OVCI6Y, and OVC172Y Unit I Components IAPO5EP 1AP072 1AP073 1AP319 1AP320 1AP321 1AP322 2AP586 Unit 2 Components 2AFO1 PA 2AF013 2AF064 2EF026 2AF01PA-A 2AF013 2AF064 Power Cable For 1APO5EP and 2AP05EJ Power Cable For 1APO5EP and 2APO5EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For 1AP05EP and 2APOSEJ Power Cable For 1AP05EP and 2AP05EJ Control Cable For 1AP05EP and 2AP05EJ Control Cable For 2AFO1 PA-A and 2AFO1 PA Control Cable For 2AFO01PA-A and 2AFO1 PA Control Cable For 2AF01PA Control Cable For 2AF01 PA-A and 2AF01 PA Control Cable For 2AF01 PA-A and 2AFO1 PA BYRON-FPR NONE NONE (Sheet 1066)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 2AP05ED 2AP05EE 2APO5EG 2AP05EJ 2AP05EP 2AP05ER 2AP05ES 2AP05EV 2AP07EE 2AP93E 2AP99E 2DG01KA 18.4-2 2AP082 2AP178 2AP049 2AP050 2AP312 2DG211 1AP072 1AP073 1AP319 1AP320 1AP321 1AP322 2AP075 2AP586 2CS002 2EF086 2AP634 2DG005 2DG019 2DG152 2DG211 2DG228 2SI004 2AP098 2AP141 2DC242 2DC242 2DG017 2DG018 2DG019 2DG157 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For 2AP05ED Power Cable For 2AP05EE Control Cable For 2AP05EG Control Cable For 2AP05EG Control Cable For 2AP05EG Control Cable For 2AP05EG and 2AP05ES Power Cable For 1AP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For IAP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Power Cable For 1AP05EP and 2AP05EJ Control Cable For 2AP05EJ Control Cable For 1AP05EP and 2AP05EJ Control Cable For 2APO5EP Control Cable For 2AP05EP Control Cable For 2AP05ER Control Cable For 2AP05ES Control Cable For 2DGOIKA and 2AP05ES Control Cable For 2APO5ES Control Cable For 2AP05EG and 2AP05ES Control Cable For 2APO0ES Control Cable For 2AP05EV Control Cable For 2AP07EE Control Cable For 2AP07EE Control Cable For 2AP99E and 2AP93E Control Cable For 2AP99E and 2AP93E Control Cable For 2DGOIKA Control Cable For 2DG01 KA Control Cable For 2DG01 KA and 2AP05ES Control Cable For 2DGOIKA (Sheet 1067)

BYRON - FPR

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.4-2 2IP01J 21P03J 2RY455A 2SX169A 2UL-AN012-A7 2UL-AN012-B7 2UL-AN012-C7 2VPO1CC 2VX04C 2DG175 2DG200 2EF037 21P005 21P006 21P033 21P034 2DC100 2SX295 2AN084 2AN084 2AN084 2VP063 2VX004 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Control Cable For 2DGOIKA Control Cable For 2DG01 KA Control Cable For 21PO1J Power Cable For 21P01J Power Cable For 21POIJ Power Cable For 21P03J Power Cable For 21P03J Control Cable For 2RY455A Control Cable For 2SX169A Control Cable For 2UL-AN012-A7, 2UL-AN012 B7, and 2UL-AN012-C7 Control Cable For 2UL-ANO12-A7, 2UL-ANO12 B7, and 2UL-ANO1 2-C7 Control Cable For 2UL-ANO12-A7, 2UL-AN012 B7. and 2UL-ANO1 2-C7 Control Cable For 2VP01CC Control Cable For 2VX04C (Sheet 1068)

\\-

BYRON -FPR

AMENDMENT 20 DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cont 'd)

Affeted quipent Division 11121 Affected Equipment Equipment In Zone Fire Zone Number:

18.5-1 Unit 0 (Common) Components NONE Unit 1 Components NONE Unit 2 Components NONE Equipment Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1069)

K-

AMENDMENT 20 DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cont 'd)

Affeted quipent DK~sion 11/21 Affected Equipment Equipment In Zone Fire Zone Number 18.5-2 Unit 0 (Common) Components NONE Unit 1 Components NONE Unit 2 Components NONE Equipment Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1070)

AMENDMER0 DECEMBER 2002 BYRON -FPR TABLE 2.4-4 (Cont d)

Affected Equipment Affected Equipment Equipment In Zone Fire Zone Number:

18.10A-1 Unit 0 (Common) Components NONE Unit 1 Components NONE Unit 2 Components NONE Division 11/21 Equipment Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1071)

AMENDMENT"Z; DECEMBER 2002 BYRON -FPR TABLE 2.4-4 (Cont 'd)

Affeted quipent DMsion 11/21 Affected Equipment Equipment In Zone Fire Zone Number 18.10A-2 Unit 0 (Common) Components NONE Unit I Components NONE Unit 2 Components NONE Equipment Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1072)

AMENDMENT DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cant 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.10OB-1 Unit 0 (Common) Components NONE Unit 1 Components NONE Unit 2 Components NONE Division 12122 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1073)

Affected Equipment Affected Equipment Equipment In Zone Fire Zone Number: 18.10B-2 Unit 0 (Common) Components NONE Unit 1 Components NONE Unit 2 Components NONE BYRON - FPR TABLE 2.4-4 (Cont 'd)

Affected Equipment DMsion 11/21 Equipment Description AMENDMENR20 DECEMBER 2002 Division 12122 Equipment In Zone NONE NONE NONE (Sheet 1074)

E~quipment Description

AMENDMENT2"/

DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cont d)

Affeted quipent Division 11/21 Affected Equipment Equipment In Zone Fire Zone Number 18.10C-1 Unit 0 (Common) Components NONE Unit 1 Components NONE Unit 2 Components NONE Equipment Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1075)

Affected Equipment Affected Equipment Equipment In Zone Fire Zone Number 18.10C-2 Unit 0 (Common) Components NONE Unit I Components NONE Unit 2 Components NONE BYRON-FPR TABLE 2.4-4 (Cont 'd)

Affected Equipment DMsion 11/21 Equipment Descdption AMENDMENT 20 DECEMBER 2002 Divsion 12/22 Equipment In Zone Equipment Description NONE NONE NONE (Sheet 1076)

AMENDMENT 20 DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cont 'd)

DMsion 11/21 Affected Equipment Equipment In Zone Fire Zone Number 18.ID-1 Unit 0 (Common) Components NONE Unit 1 Components NONE Unit 2 Components NONE Equipment Description Division 12122 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1077)

AMENDMENT 20 DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cont 'd)

Affected Equipment Affected Equipment Equipment In Zone Fire Zone Number:

18.1OD-2 Unit 0 (Common) Components NONE Unit I Components NONE Unit 2 Components NONE Division 11/21 Equipment Description Divislon 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1078)

AMENDMENT 20 DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cont d)

Affeted quipent Division 11/21 Affected Equipment Equipment In Zone Fire Zone Number:

18.10E-1 Unit 0 (Common) Components NONE Unit 1 Components IAPO5ER IAPBUI Unit 2 Components NONE Equipment Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE Power Cable For 1AP05ER 1AP06ES IAPBU3 Power Cable For 1AP06ES NONE (Sheet 1079)

DMsion 11/21 Affected Equipment Equipment In Zone Fire Zone Number: 18.10E-2 Unit 0 (Common) Components NONE Unit I Components NONE Unit 2 Components 2AP05EG 2APBU1 BYRON - FPR TABLE 2.4-4 (Cont 'd)

Affected Equipment Equipment Descripton NONE NONE 2AP06EF Power Cable For 2AP05EG AMENDMENT 20 DECEMBER 2002 Divsion 12/22 Equipment In Zone 2APBU3 Equipment Description Power Cable For 2AP06EF (Sheet 1080)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.11-0 Division 12/22 Affected Equipment Equipment Equipment In Zone Description Unit 0 (Common) Components OSX02PA OSX02PA Essential Service Water Makeup Pump OA OSX02PA-K Diesel Engine for Essential Service Water Makeup Pump GA OSX02PB-K Diesel Engine for Essential Service Water Makeup Pump OB OSX03AA ESW Makeup Pump GA Diesel Jacket Water Heat Exchanger OSX03AB ESW Makeup Pump 0B Diesel Jacket Water Heat Exchanger OSX04AA ESW Makeup Pump GA Diesel Gear Oil Cooler OSX04AB ESW Makeup Pump GB Diesel Gear Oil Coder 1SX172 Control Cable For OSX02PA ISX338 Control Cable For OSX02PA ISX363 Control Cable For OSX02PA 1SX364 Instrument Cable For OSX02PA 1SX453 Power Cable For 0SX02PA 1SX454 Power Cable For OSX02PA 1SX461 Power Cable For OSX02PA 1SX462 Power Cable For OSX02PA 1SX541 Power Cable For OSX02PA 1SX542 Power Cable For OSX02PA ISX543 Power Cable For OSXO2PA 1SX544 Power Cable For OSX02PA 1SX572 Control Cable For OSX02PA Unit I Components NONE Unit 2 Components GSX02PB OSX02PB 1SX097 1SX334 1SX352 1SX354 1 SX451 1 SX452 1SX459 1SX460 1SX537 1SX538 1 SX539 1SX540 1SX571 Essential Service Water Makeup Pump GB Control Cable For OSX02PB Control Cable For OSX02PB Control Cable For OSX02PB Instrument Cable For OSX02PB Power Cable For OSX02PB Power Cable For OSX02PB Power Cable For OSX02PB Power Cable For OSX02PB Power Cable For OSX02PB Power Cable For OSX02PB Power Cable For OSX02PB Power Cable For OSX02PB Control Cable For OSX02PB NONE NONE NONE (Sheet 1081)

BYRON - FPR

BYRON-FPR TABLE 2.4-4 (Cont 'd)

AMENDMENT 20 DECEMBER 2002 Affeted quipent DMslon 11/2l Affected Equipment Equipment In Zone Fire Zone Number. 18.11-1 Unit 0 (Common) Components ODO08TB Equipment Description SX Makeup Pump Diesel Oil Storage Tank OA Unit I Components NONE Unit 2 Components NONE Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1082)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description FireZone Number. 18.11-2 Unit 0 (Common) Components ODOO8TA SX Makeup Pump Diesel Oil Storage Tank OA Unit 1 Components NONE Unit 2 Components NONE DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1083)

BYRON-FPR

BYRON-FPRAMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number. 18.14A-1 Unit 0 (Common) Components NONE OSX02PB 1SX168 Control Cable For OSX02PB and OSX162B ISX250 Control Cable For OSX02PB 1SX268 Control Cable For OSX02PB 0SX157A 1SX080 Power Cable For OSX157A 1SX084 Control Cable For 0SX157A 1SX085 Control Cable For 0SX157A OSX162B 1SX167 Power Cable For OSX1 62B 1SX168 Control Cable For OSX02PB and OSX162B 1SX169 Control Cable For OSX1 62B OSX163E 1SX161 Control Cable For OSX163E OSX163F ISX165 Control Cable For 0SX163F Unit 1 Components NONE 1AP92E Division 12 480V ESW Cooling Tower MCC 132Z1 1AP98E Division 12 480V ESF Unit Substation 132Z 1VX06C ESW Cooling Tower OB Division 12 Electric Substation Bus 132Z Supply Fan 1VX33Y ESW Cooling Tower 0B Division 12 Electric Substation Bus 132Z Outside Air Intake 1VX35Y ESW Cooling Tower 0B Division 12 Electric Substation Bus 132Z Return Air Damper IAP06EN 1AP183 Power Cable For 1AP06EN IAP406 Control Cable For 1AP06EN IAP92E 1AP290 Power Cable For 1AP92E 1DC243 Control Cable For 1AP98E and 1AP92E 1DC245 Control Cable For 1AP98E and IAP92E 1AP98E 1APBU5 Power Cable For IAP98E 1DC243 Control Cable For 1AP98E and 1AP92E 1DC245 Control Cable For 1AP98E and 1AP92E (Sheet 1084)

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont d)

Divsion 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.14A-1 1VX06C IVX045 Power Cable For 1VX06C 1VX046 Control Cable For 1VX06C, 1VX33Y, and 1VX35Y 1VX049 Control Cable For 1VX06C IVX050 Control Cable For 1VX06C, 1VX33Y, and 1VX35Y 1VX054 Control Cable For lVX06C, 1VX33Y, and IVX35Y 1VX33Y 1VX046 Control Cable For 1VX06C, IVX33Y, and IVX35Y 1VX05O Control Cable For IVX06C, 1VX33Y, and 1VX35Y 1VX052 Control Cable For IVX33Y and IVX35Y 1VX054 Control Cable For 1VX06C, 1VX33Y, and 1VX35Y 1VX055 Control Cable For 1VX33Y and IVX35Y 1VX056 Control Cable For 1VX33Y and 1VX35Y 1VX085 Instrument Cable For 1VX33Y and 1VX35Y 1VX087 Instrument Cable For 1VX33Y and 1VX35Y 1VX088 Instrument Cable For 1VX33Y and 1VX35Y 1VX094 Control Cable For 1VX33Y and 1VX35Y 1VX35Y 1VX046 Control Cable For 1VX06C, 1VX33Y, and 1VX35Y IVX050 Control Cable For 1VX06C, IVX33Y, and 1V)X35Y 1VX052 Control Cable For 1VX33Y and IVX35Y IVX054 Control Cable For 1VX06C, 1VX33Y, and 1VX35Y 1VX055 Control Cable For 1VX33Y and 1VX35Y IVX056 Control Cable For 1VX33Y and 1VX35Y 1VX085 Instrument Cable For 1VX33Y and 1VX35Y 1VX087 Instrument Cable For 1VX33Y and IVX35Y 1VX088 Instrument Cable For 1VX33Y and 1VX35Y 1VX094 Control Cable For 1VX33Y and 1VX35Y (Sheet 1085)

BYRON - FPR TABLE 2.4-4 (Cont 'd)

Divsion 11/21 Affected Equipment Equipment In Zone Fire Zone Number:

18.14A-1 Unit 2 Components NONE Equipment Description AMENDMENTY DECEMBER 2002 DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description NONE (Sheet 1086)

BYRON - FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.14A-2 Unit 0 (Common) Components NONE OSX157B 2SX080 Power Cable For OSX1 57B 2SX084 Control Cable For OSX157B 2SX085 Control Cable For 0SX1 57B OSX162D 2SX167 Power Cable For 0SX162D 2SX168 Control Cable For OSX1 62D 2SX169 Control Cable For OSX1 62D OSX163G 2SX161 Control Cable For OSX163G 0SX163H 2SX165 Control Cable For 0SX163H Unit I Components NONE NONE Unit 2 Components NONE 2AP92E Division 22 480V ESW Cooling Tower MCC 232Z1 2AP98E Division 22 480V ESF Unit Substation 232Z 2VX06C ESW Cooling Tower 0B Division 22 Electric Substation Bus 232Z Supply Fan 2VX33Y ESW Cooling Tower 0B Division 22 Electric Substation Bus 232Z Outside Air Intake 2VX35Y ESW Cooling Tower 0B Division 22 Electric Substation Bus 232Z Return Air Damper 2AP06EV 2AP183 Power Cable For 2AP06EV 2AP406 Control Cable For 2AP06EV 2AP92E 2AP290 Power Cable For 2AP92E 2DC243 Control Cable For 2AP98E and 2AP92E 2DC245 Control Cable For 2AP98E and 2AP92E 2AP98E 2APBU5 Power Cable For 2AP98E 2DC243 Control Cable For 2AP98E and 2AP92E 2DC245 Control Cable For 2AP98E and 2AP92E (Sheet 1087)

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.14A-2 2VX06C 2VX045 Power Cable For 2VX06C 2VX046 Control Cable For 2VX06C, 2VX33Y. and 2VX35Y 2VX049 Control Cable For 2VX06C 2VX050 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX054 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX33Y 2VX046 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX050 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX052 Control Cable For 2VX33Y and 2VX35Y 2VX054 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX055 Control Cable For 2VX33Y and 2VX35Y 2VX056 Control Cable For 2VX33Y and 2VX35Y 2VX085 Instrument Cable For 2VX33Y and 2VX35Y 2VX087 Instrument Cable For 2VX33Y and 2VX35Y 2VX088 Instrument Cable For 2VX33Y and 2VX35Y 2VX094 Control Cable For 2VX33Y and 2VX35Y 2VX35Y 2VX046 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX050 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX052 Control Cable For 2VX33Y and 2VX35Y 2VX054 Control Cable For 2VX06C, 2VX33Y, and 2VX35Y 2VX055 Control Cable For 2VX33Y and 2VX35Y 2VX056 Control Cable For 2VX33Y and 2VX35Y 2VX085 Instrument Cable For 2VX33Y and 2VX35Y 2VX087 Instrument Cable For 2VX33Y and 2VX35Y 2VX088 Instrument Cable For 2VX33Y and 2VX35Y 2VX094 Control Cable For 2VX33Y and 2VX35Y (Sheet 1088)

AMENDMENT 1Y' DECEMBER 2002 BYRON - FPR TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.14A-2 Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1089)

K-

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number.

18.14B-1 Unit 0 (Common) Components OSX02PA 1SX156 Control Cable For OSX02PA and 0SX162A NONE ISX251 Control Cable For OSX02PA ISX258 Control Cable For OSX02PA 0SX158A ISX077 Power Cable For OSX158A ISX078 Control Cable For 0SX158A 1SX079 Control Cable For 0SX158A OSX162A lSX155 Power Cable For 0SX162A 1SX156 Control Cable For OSX02PA and 0SX162A 1SX157 Control Cable For 0SX162A OSX163A 1SX149 Control Cable For 0SX1 63A OSX163B 1SX153 Control Cable For 0SX163B Unit 1 Components 1AP93E Division 11 480V ESW Cooling Tower MCC NONE 131ZI 1AP99E Division 11 480V ESF Unit Substation 131Z 1VX05C ESW Cooling Tower OA Division 11 Electric Substation Bus 131Z Supply Fan 1VX30Y ESW Cooling Tower OA Division 11 Electric Substation Bus 131Z Outside Air Intake IVX32Y ESW Cooling Tower OA Division 11 Electric Substation Bus 131Z Return Air Damper 1APO5EA 1AP178 Power Cable For IAP05EA 1AP401 Control Cable For 1AP05EA 1AP93E 1AP288 Power Cable For 1AP93E IDC242 Control Cable For IAP99E and 1AP93E 1DC244 Control Cable For 1AP99E and 1AP93E 1AP99E 1APBU6 Power Cable For 1AP99E IDC242 Control Cable For 1AP99E and 1AP93E 1DC244 Control Cable For 1AP99E and 1AP93E (Sheet 1090)

BYRON-FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.14B-1 1VX05C 1VXM 11 Control Cable For 1VX05C, 1VX30Y, and 1VX32Y 1VX016 Control Cable For 1VX05C, 1VX30Y, and 1VX32Y 1VX040 Power Cable For IVXO5C IVX041 Control Cable For 1VX05C, 1VX30Y, and 1VX32Y 1VX044 Control Cable For 1VXO5C 1VX30Y 1VX011 Control Cable For 1VX05C, 1VX3OY, and 1VX32Y 1VX013 Control Cable For 1VX30Y and 1VX32Y 1VX014 Control Cable For 1VX30Y and IVX32Y 1VX016 Control Cable For 1VX05C, 1VX30Y, and 1VX32Y IVX017 Control Cable For 1VX30Y and 1VX32Y 1VX041 Control Cable For 1VX05C, 1VX30Y, and 1VX32Y 1VX081 Instrument Cable For 1VX30Y and 1VX32Y 1VX083 Instrument Cable For 1VX30Y and 1VX32Y 1VX084 Instrument Cable For 1VX30Y and 1VX32Y 1VX090 Control Cable For 1VX30Y and 1VX32Y 1VX32Y 1VX011 Control Cable For 1VX05C, 1VX30Y, and 1VX32Y 1VX013 Control Cable For 1VX30Y and IVX32Y 1VX014 Control Cable For 1VX30Y and IVX32Y 1VXO16 Control Cable For 1VX05C, IVX30Y, and 1VX32Y 1VX017 Control Cable For 1VX30Y and 1VX32Y 1VX041 Control Cable For 1VX05C, 1VX30Y, and IVX32Y 1VX081 Instrument Cable For 1VX30Y and 1VX32Y 1VX083 Instrument Cable For 1VX30Y and 1VX32Y 1VX084 Instrument Cable For IVX30Y and 1VX32Y IVX090 Control Cable For 1VX30Y and 1VX32Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1091)

AMENDMENTý6 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number:

18.14B-1 UnIt 2 Components NONE DMsion 12/22 Affected Equipment Equipment Equipment In Zone Description NONE (Sheet 1092)

K-.

BYRON - FPR

BYRON -FPR AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Division 12/22 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.14B-2 Unit 0 (Common) Components OSX158B 2SX077 Power Cable For OSX158B NONE 2SX078 Control Cable For 0SX1 58B 2SX079 Control Cable For OSX1658B OSX162C 2SX155 Power Cable For OSX1 62C 2SX156 Control Cable For 0SX1I62C 2SX157 Control Cable For 0SX162C OSX163C 2SX149 Control Cable For OSX163C OSX163D 2SX153 Control Cable For 0SX163D Unit 1 Components NONE NONE Unit 2 Components 2AP93E Division 11 480V ESW Cooling Tower MCC NONE 231Zl 2AP99E Division 21 480V ESF Unit Substation 231Z 2VX05C ESW Cooling Tower OA Division 21 Electric Substation Bus 231Z Supply Fan 2VX30Y ESW Cooling Tower OA Division 21 Electric Substation Bus 231Z Outside Air Intake 2VX32Y ESW Cooling Tower OA Division 21 Electric Substation Bus 231Z Return Air Damper 2APO5EE 2AP178 Power Cable For 2AP05EE 2AP401 Control Cable For 2AP05EE 2AP93E 2AP288 Power Cable For 2AP93E 2DC242 Control Cable For 2AP99E and 2AP93E 2DC244 Control Cable For 2AP99E and 2AP93E 2AP99E 2APBU6 Power Cable For 2AP99E 2DC242 Control Cable For 2AP99E and 2AP93E 2DC244 Control Cable For 2AP99E and 2AP93E (Sheet 1093)

BYRON - FPR AMENDMENT 20/

DECEMBER 2002 TABLE 2.4-4 (Cont d)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number 18.14B-2 2VX05C 2VX01 1 Control Cable For 2VX05C, 2VX30Y, and 2VX32Y 2VX016 Control Cable For 2VX05C, 2VX30Y, and 2VX32Y 2VX040 Power Cable For 2VX05C 2VX041 Control Cable For 2VX05C, 2VX30Y, and 2VX32Y 2VX044 Control Cable For 2VX05C 2VX3OY 2VXO11 Control Cable For 2VX05C, 2VX30Y, and 2VX32Y 2VX013 Control Cable For 2VX30Y and 2VX32Y 2VX014 Control Cable For 2VX30Y and 2VX32Y 2VX016 Control Cable For 2VXOSC, 2VX30Y. and 2VX32Y 2VX017 Control Cable For 2VX30Y and 2VX32Y 2VX041 Control Cable For 2VX05C, 2VX30Y, and 2VX32Y 2VX081 Instrument Cable For 2VX30Y and 2VX32Y 2VX083 Instrument Cable For 2VX30Y and 2VX32Y 2VX084 Instrument Cable For 2VX30Y and 2VX32Y 2VX090 Control Cable For 2VX30Y and 2VX32Y 2VX32Y 2VX01 1 Control Cable For 2VXO5C, 2VX3OY, and 2VX32Y 2VX013 Control Cable For 2VX30Y and 2VX32Y 2VX014 Control Cable For 2VX30Y and 2VX32Y 2VX016 Control Cable For 2VX05C, 2VX3OY, and 2VX32Y 2VX017 Control Cable For 2VX30Y and 2VX32Y 2VX041 Control Cable For 2VX05C, 2VX30Y, and 2VX32Y 2VX081 Instrument Cable For 2VX30Y and 2VX32Y 2VX083 Instrument Cable For 2VX30Y and 2VX32Y 2VX084 Instrument Cable For 2VX30Y and 2VX32Y 2VX090 Control Cable For 2VX30Y and 2VX32Y Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1094)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11/21 Affected Equipment Equipment Equipment In Zone Description Flre Zone Number 18.14B-2 Division 12/22 Affected Equipment Equipment Equipment In Zone Description (Sheet 1095)

BYRON-FPR

BYRON-FPR TABLE 2.4-4 (Cont 'd)

AMENDMENR00 DECEMBER 2002 Affected Equipment Affected Equipment Equipment In Zone Fire Zone Number. 18.23-0 Unit 0 (Common) Components NONE Unit I Components 1CDO1T Unit 2 Components 2CD01T DMsIon 11/21 Equipment Descdption Unit I Condensate Storage Tank Unit 2 Condensate Storage Tank Division 12/22 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1096)

AMENDMENT 20 DECEMBER 2002 TABLE 2.4-4 (Cont 'd)

Division 11121 Affected Equipment Equipment Equipment In Zone Description Fire Zone Number: 18.39-0 Unit 0 (Common) Components NONE Unit I Components NONE Unit 2 Components NONE Division 12122 Affected Equipment Equipment Equipment In Zone Description NONE NONE NONE (Sheet 1097 final)

BYRON - FPR