NPDES Permit PA0025615, Notice of Non-Compliance Outfall 211
ML023470143
Person / Time
Site: Beaver Valley
Issue date: 11/26/2002
From: Lash J
FirstEnergy Corp
To:
Office of Nuclear Reactor Regulation, State of PA, Dept of Environmental Protection, Bureau of Water Quality Management
References
PA0025615
Download: ML023470143 (6)


Text

Firs tEnegy P.O. Box 4, Route 168 ShippingportM PA 15077 November 26, 2002 DMR Clerk Department of Environmental Protection Bureau of Water Quality Management 400 Waterfront Drive Pittsburgh, PA 15222 NPDES Permit PA0025615, Notice of Non-Compliance Outfall 211

Dear Sir or Madam:

During the month of October, Outfall 211 (Oil/Water Separator 23) exceeded the monthly maximum pH effluent limit of 9.0 and the daily maximum Oil and Grease effluent limit of 20.0 mg/L. The pH was determined to be 10.16 S.U. and the Oil and Grease determined to be 22.0 mg/L on October 14, 2002.

The oil/water separator receives water from the Unit 2 turbine building and equipment drains. During a cold weather verification test on October 13, 2002, water from a manhole collecting rainwater and groundwater was pumped to the oil/water separator.

The water had a high pH caused by the rainwater passing through gravel containing calcium carbonate. The manhole also contained oil collected in the manhole from a nearby transformer.

Upon discovery of the problem, the pumping was terminated. Corrective action including addition of sodium bicarbonate to the inlet of the oil/water separator was initiated to bring the pH back to within permit effluent limits. Samples collected on October 24, 2002 were all within NPDES permit effluent limits.

Attn: DMR Clerk Page 2 Beaver Valley has initiated corrective actions to prevent future occurrences. All water movement outside of its normal intended flowpath will be sampled and reviewed by chemistry staff prior to discharge. If you have any questions, contact me at 724 682 5113.

Sincerely, DJS C:

E. Hubley S.F. Brown Central File

PERMIltTE NAMEIAVM$3SS iV*PwftXL"%iIfm NAME FIRST 'E"l!J--RGy CORP ADDRESS~

Pp-RUTE 161S FAcILIT BRAVER VALLEY T'~Y LocATmOS H 1 P P 1'N P OR T ATTNt:

reATTHIEW J HAR.TlhAN I

~PARAMETER OAMAflOAPUTAITM OICAO JMtNA1M W SYM INPOESI1 0MB NW.2 DISHAGEMONITORING REPORT (D~ffl)

MA~JOR

~UMBR F

FINAL

____________________DIESEL G~EN i.TURBINE DRAINS 40-MM MONITORIN PERIOD PA 150'--OO FROM

~

TO

~

~

'uD~'AC NOTE: Reed knetuetlon befor corol~etng theform.

QtuANTITY OR LOAD=N QUALITY OR CONCENTRATION 0

N. lrac SAMPL.E

%I-II I f i EXXIAALysi,9I TYPE EPA Faim 3320-1 (Rev. 3iW) PmIous edltlofis may be used.

OOO4JcThit4wait(Y6hn.

PAGE

W 00054,'M, r3rj4W4-Kft(f&m.

PACE PF 15077-OOLM EPA Fwm 3320-1 (Rev. 3W) Pmvimn edftlons may be used.

  • PERMTTTE NAMEIAOM SS N.aul, D9'e NATMOAL POLLUTANT DecHOW" £ummA1O nmIES NAME rIR!;T ENERGY CORP DISCHARGE MONITORNG REOT IOMR)r AOMRSS INSHAR RHTEUMSME OHPN TPA 150777-70004.

EMTNME

ýIAcIUWy B~EAVER VALLEY PO WEFR STATION MONITORING PERIOD LOCATIONSHIPP 1OPOPT.

PA 157-04RMT ATTN'. MATTHEW J2 HARTMAN' Farm Approvd.

OMB No. 2040-OM0 M1AJOR (SUtBR 05,

111T 2 SERVICE WATE.R BACKWASH NO) DISCHARG~E I,<- A NOTE: Road luftnacton befot. comphtl this foim.

PAGE!

of EPA Farm 3320-1 (Rev. 319) Pmevnos edfton rmay be used.

PARAMETER QUANTITY OR LOADING QxUAUTY OR CONCENTrRATION No.. "

SAMPL EX Y9 TYPE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS

~

-- ~*~

~

SAMPLE-THRU TREATMENT PLAN'ý.' MASUREMENTU

,a0050 1

0 0

-'KeMt" EFFLUENT GROSS VAut)n~tJ SAMPLE MEASUREMENT rPERMIvv SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLEL MEASUREMENT NAMEITILE PRINCIPAL VXEUMWE OFFICE or"a" TELEPHONE DATE pi Id mmmdi folo dimrfmi i in faY. Iummmwds withwf an min dimeg.

loom- "Wthat l

qu fifli pm peram 11~mt gagtm o s'

o and ymt b kInrfluitS abuilki. UNit -

wmn7 Inq"h7 tdmw pnn ipuiwu w nmma -mg emsystn.

w~

amV "adp cloeWb hI

\\

g

~ CA XCII AE O

TYPED OR PRINTW lnadni On posobiblly oflfin.P 1 pn h Iu I

ulmm It vm whhnswtn OMlss. R OR AtfTHO0tZE AGENT YEARHA COMMENTS. AND EXPLANATION OF ANY VIOLATIONS (ROMf O ONeye eff atahmet$ 3=1e

NAME F IR'S T EN E RGY G-0R P, P'A ROUTE 168 7, H rIFpT!'F

'F I

P R T Fomi Appraed.

t#AllOAL m~LvTANT ctsCHARw ftmmmtI$

gysTV4NPOESJ MAJOROMN.

DISCHARGE MONITORING REPORT DR PA 1'5077-0004 F~~NME F

FNAL.

BLOWDOWN FROM THE HYAC UNIT FACIlY IAVE VALEY

~ER

.TATIONMONITORING PERIOD Lo#4'3HIPF-IrPOWER PýAT I~

7-00F~

ON Q DISCHARGE I _I Ar-rM.7 DAY,~zt~

M N~~~4N l

~IUUIWfIU U~

UTpUIgIlwl PARAMETER QUANTITY OR LOADING, QUALITY OR CONCENTRATION NO

'r"foghc SAMPLE

_Ht AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITSEXA,.

TP

~~ Ii

~SAMPLE

~..~

MEASUREMENT 0 0 40 1

0 0

~E~r~

ErFLUENT GROSS VALU! REUIEMN U I SAMPLE G"?3 C)

MEASUREMENT Yk E~TLUENT GRO359 VALU!fT-cUAý E'

'~

MG/L 7"

J~fL SAMPLE CAS CU)MEASUREMENT

-01042

.1 0.

0 R

FFLUENT GR'7055 VALVRURMEtd,-~M/

.( AS JZN)

MEASUREMENT AI 01092:

1 0

0 PMT EFFLUENT GROSS VALt PEOUWR.MEqT tlGI

~~~"~~

WN~4

.U4M..

SAMPLE 7Tj:RtJ TR EATMENT VPLAN-IEASUR.EMENT

~LA~OQO

~04w5 1-.

0t 0

PDMI DI)ISSOLVED MEASUREMENT 22-6

'70295.1 0

0 PE-R -M-ItT.;

T EFFLVENr GROSS VALU, OuR'~

M-O/

SAMPLE MEASUREMENT NAMEITITLE PRINCIPAL EXEUIV OFFICER a cel of" In

'.d TELEPHONE DATE ftMoe owm peume dir yme uI o

ly gifieelsumgi.

  • Tor~mem* Uno Ih rn.

-mi wd ent my iffS

-,~ odwift porwashr pantt~

so m i wo.

ow sy rYPm OR PRINTED 0glsp"=y ffn nbemr~u.ved~u

-OF~R OR AUTHORIED AGMlE NME YEAR M

A COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference.1 ettechmets he")l 0 0 057 / CMI-k 7it-*(t&M.

PAGE OF:

EPA Form 3320-1 (Rev. 3M9) Previous edftions may be used.

404X*4 j-, -r-rki MA-r-ru="

I U&wriwAm f

nw aim: 11941a RIVIRMUMM uvwff* campmourMlluirr 10M.

General Instructions

1. If form has been partially completed by preprinting, disregard instructions directed at entry of that information already preprinted.
2. Enter "Permittee Name/Mailing'Address (and facility-name/location, if different)," "Permit Number," and "Discharge Number" where indicated. (A separate form is required for each discharge.)
3. Enter dates beginning and ending "Monitoring Period" covered by form where indicated.
4. Enter each "Parameter" as specified in monitoring requirements of permit.
5. Enter "Sample Measurement" data for each parameter under "Quantity" and "Quality" in units specified in permit.

"Average" is normally arithmetic average (geometric average for bacterial parameters) of all samplez measure ments for each parameter obtained duritSg "Monitoring Period"; "Maximum" and "Minimum" are normally ex treme high and low measurements obtained during "Monitoring Period." (Note to municipals with secondary treatment requirementt-Enter 30-day average of sample measurements under "Average," and enter maximum 7-day average 6f sample measurements obtained during monitoring period under "Maximum."')

6. Enter "Permit Requirement" for each parameter under "Quantity" and "Quality" as specified in permit.
7. Under "No Ex" enter number of sample measurements during rfionitoring period that exceed maximum (andlor minimuni or 7-day average as appropriate) permit requirement for each parameter. If none, enter. "0"
8. Enter "Frequency of Analysis" both as ",dinple Measurement" (actual frequency of sampling' and analysis used during monitoring period) and as "Permit Requirement" specified in permit. (e.g., Enter "Cont," for c'ontinuous rnonitoring, "1/7" for one day per week, "1130" for one day per month, "1/90" for one day per quarter, etc.)
9. Enter "Sample 7Tpe" both as "Sample Measurement" (actual sample type used during monitoring period) and as "Permit Requirement," (e.g., Enter "Grab" for individual sample, "24HC' for 24-hour composite, "N/A" for con tinuous monitoring,.etc.)

10., Where violations of permit requirements are reported, attach a brief explanation to describe cause and corrective actions taken, and reference each violation by date.

11. If "no discharge" occiirs during moipnitoring period, enter "No Discharge" across form in place of data entry.
12. Enter "Name/Title ofPrincipal Ergcutive Officer", with "Signature of Principal Executive Officer of Authorized Agent," "Teephone Number," and "Date" at bottom of form.
13. Mail signed Report to Office(s) by date(s) specifled in permit. Retain copy for your 'records.
14. MNore detailed instructions for use of this Discharge Monitoring Report, (DMR) form may be obtained from Of lice(s) specified in permit.

Legal Notice This report is required by law (33 U.S.C. 1318; 40 C.F.R. 125.27)4 Failure to! report or failure to report truthfully can result In civil penaties not to exteed $10,000 per day of violation; or in criminal penalties:not to exceed $25,000 per day of violation, or byimprisonment, for not more than one year, or by both.

SEPA Form 3320-1 (Rev. 3/99)

SPaperwork Reduction Act Notice Public reporting burden for this collection of information is estimated to vary from a range of 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> as an average per response for some minor facilities, to 110 hours0.00127 days <br />0.0306 hours <br />1.818783e-4 weeks <br />4.1855e-5 months <br /> as an average per response for some major facilities, with a weighted average for major and minor facilities of 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> per response, including time for reviewing instructions, searching existing data sources, gathering and maintaining.the data needed, and completing and reviewing the collection of information. Send comments regarding the burden estimate or any other aspect of this collection of information, including suggestions for reducing this burden,. to Chief, Information Policy Branch, PM-223, U.S. Environmental Protection Agency, 401 M Street, SW, Washington, DC 20460; and to the Office of Information apdRegulatory Affairs, Office of Management and Budget Washington, DC 20503.