Technical Specification (TS) Bases Change
ML023370521
Person / Time
Site: McGuire, Mcguire  
Issue date: 11/21/2002
From: Jamil D
Duke Power Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML023370521 (3)


Text

?

Duke OPower A Duke E-gy Company D.M. Jamil Vice President, McGuire November 21, 2002 United States Nuclear Regulatory Commission ATTENTION:

Document Control Desk Washington, DC 20555-0001

SUBJECT:

Duke Power McGuire Nuclear Station 12700 Hagers Ferry Road Huntersville, NC 28078-9340 (704) 875-4000 (704) 875-5333 OFFICE (704) 875-4809 FAX Duke Energy Corporation McGuire Nuclear Station Units 1 and 2 Docket Nos.

50-369 and 50-370 Technical Specification (TS) Bases Change Attached is McGuire Technical Specification (TS) Manual Section 3.3.1 (RTS Instrumentation),

Table 3.3.1-1, page 2 of 7.

We ask that you please re-issue this page under approved Technical Specification Amendment 194/175 which was issued on September 18, 2002.

On March 2,

2000, TS Amendment 191/172 was issued.

Included in this amendment was a change on Table 3.3.1 page 2 of 7 to the single loop and two loop Low NC Flow allowable value from >90%

to >87% and the Nominal Trip Setpoint from 91% to 88%.

TS Amendment 194/175 was prepared prior to the issuance of the 191/172 TS Amendment, and when the 194/175 TS Amendment was issued the NC Flow setpoint values were inadvertently changed back to the old values.

Please contact Jeff Thomas at (704) 875-4535 if you have any questions.

Very truly yours, D.M. Jamil Attachments Ao I

U.

S. Nuclear Regulatory Commission November 21, 2002 Page 2 Xc w/attachments:

L.

A.

Reyes U.

S. Nuclear Regulatory Commission Regional Administrator, Region II Atlanta Federal Center 61 Forsyth St.,

SW, Suite 23T85 Atlanta, GA 30303 R.

E. Martin U.

S. Nuclear Regulatory Commission Mail Stop 0-8G9 11555 Rockville Pike Rockville, MD 20852-2738 B.

0. Hall, Section Chief Division of Radiation Section 1645 Mail Service Center Raleigh, NC 27699-1645 S.

M. Shaeffer Senior Resident Inspector U.

S. Nuclear Regulatory Commission McGuire Nuclear Station

Table 3.3.1-1 (page 2 of 7)

Reactor Trip System Instrumentation RTS Instrumentation 3.3.1 APPLICABLE MODES OR OTHER NOMINAL SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE TRIP FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE SETPOINT

6.

Overtemperature AT

7. Overpower AT 1,2 1,2 4

4

8.

Pressurizer Pressure

a.

Low 1(f)

b.

High

9.

Pressurizer Water Level - High

10. Reactor Coolant Flow Low
a.

Single Loop

b.

Two Loops

11. Undervoltage RCPs 1,2 1(f) 1(g) 1(h) 1(f) 4 4

3 3 per loop 3 per loop 1 per bus E

SR 3.3.1.1 SR 3.3.1.3 SR 3.3.1.6 SR 3.3.1.7 SR 3.3.1.12 SR 3.3.1.16 SR 3.3.1.17 E

SR 3.3.1.1 SR 3.3.1.3 SR 3.3.1.6 SR 3.3.1.7 SR 3.3.1.12 SR 3.3.1.16 SR 3.3.1.17 M

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.1.10 SR 3.3.1.16 E

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.1.10 SR 3.3.1.16 M

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.1.10 N

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.1.10 SR 3.3.1.16 M

SR 3.3.1.1 SR 3.3.1.7 SR 3.3.1.10 SR 3.3.1.16 M

SR 3.3.1.9 SR 3.3.1.10 SR 3.3.1.16 Refer to Note 1 (Page 3.3.1-18)

Refer to Note 2 (Page 3.3.1-19)

Refer to Note 1 (Page 3.3.1-18)

Refer to Note 2 (Page 3.3.1-19)

  • 1935 psig 1945 psig

< 2395 psig 2385 psig

< 93%

  • 87%
  • 87%

>5016 V 92%

88%

I 88%

5082 V I

(continued)

(f)

Above the P-7 (Low Power Reactor Trips Block) interlock.

(g)

Above the P-8 (Power Range Neutron Flux) interlock.

(h)

Above the P-7 (Low Power Reactor Trips Block) interlock and below the P-8 (Power Range Neutron Flux) interlock.

Amendment Nos. 194/175 McGuire Units 1 and 2 3.3.1-15