Text
Indiana Michigan Power Company 500 Circle Drive Buchanan, MI 49107 1395 INDIANA MICHIGAN POWER November 15, 2002 AEP:NRC:2691-24 Docket Nos.
50-315 50-316 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop O-Pl-17 Washington, DC 20555-0001 Donald C. Cook Nuclear Plant Units 1 and 2 MONTHLY OPERATING REPORT Pursuant to the requirements of Donald C. Cook Nuclear Plant Unit 1 and Unit 2 Technical Specification 6.9.1.8, the attached Monthly Operating Report for October 2002 is submitted.
Sincerely, ctA. Greenle Director, Nuclear Technical Services BWO/jen Attachments
U. S. Nuclear Regulatory Commission AEP:NRC:2691-24 Page 2 c: ANI Nuclear Engineering Department A. C. Bakken, III L. Brandon - Department of Health G. T. Gaffney - Canton S. A. Greenlee S. Hamming - Department of Labor RAF Harris INPO Records Center B. Lewis - McGraw-Hill Companies D. H. Malin B. A. McIntyre NRC Project Manager - NRR NRC Region III NRC Resident Inspector D. W. Paul - Columbus J. E. Pollock W. H. Schalk
N.R.C. OPERATING DATA REPORT DOCKET NO.
50-315 DATE 11/4/02 COMPLETED BY RAF Harris TELEPHONE 616-465-5901 OPERATING STATUS
- 1. Unit Name D.C. Cook Unit I Notes:
- 2. Reporting Period Oct-02
- 3. Licensed Thermal Power (MWt) 3250
- 4. Name Plate Rating (Gross MWe) 1152
- 5. Design Electrical Rating (Net MWe) 1020
- 6. Maximum Dependable Capacity(GROSS MWe:
1056
- 7. Maximum Dependable Capacity (Net MWe) 1000
- 8. If Changes Occur in Capacity Ratings (Items no. 3 through 7) Since Last Report Give Reasons
- 9. Power Level To Which Restricted. If Any (Net MWe)
- 10. Reasons For Restrictions.
This Mo.
Yr. to Date
- 11. Hours in Reporting Period 745.0 7296.0
- 12. No. of Hrs. Reactor Was Critical 745.0 6363.3
- 13. Reactor Reserve Shutdown Hours 0.0 0.0
- 14. Hours Generator on Line 745.0 6319.5
- 15. Unit Reserve Shutdown Hours 0.0 0.0
- 16. Gross Therm. Energy Gen. (MWH) 2405598.0 20115443.4
- 17. Gross Elect. Energy Gen. (MWH) 780400.0 6490050.0
- 18. Net Elect. Energy Gen. (MWH) 754368.0 6272484.6
- 19. Unit Service Factor 100.0 866
- 20. Unit Availability Factor 100 0 86 6
- 21. Unit Capacity Factor (MDC Net) 101.3 86.0
- 22. Unit Capacity Factor (DER Net) 99.3 84.3
- 23. Unit Forced Outage Rate 0.0 1.5
- 24. Shutdowns Scheduled over Next Six Months (Type,Date,and Duration):
- 25. If Shut Down At End of Report Period, Est'd Date of Startup:
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION Cumm.
243984.0 165884.6 463.0 163224.9 321.0 4856207504 157722870.0 151806778.5 67.4 67.4 63.7 62.4 19.3
N.R.C. OPERATING DATA REPORT DOCKET NO.
50-316 DATE 11/4/02 COMPLETED BY RAF Harris TELEPHONE 616-465-5901 OPERATING STATUS
- 1. Unit Name D.C. Cook Unit 2 Notes:
- 2. Reporting Period Oct-02
- 3. Licensed Thermal Power (MWt) 3411
- 4. Name Plate Rating (Gross MWe) 1133
- 5. Design Electrical Rating (Net MWe) 1090
- 6. Maximum Dependable Capacity(GROSS MWe 1100
- 7. Maximum Dependable Capacity (Net MWe) 1060
- 8. If Changes Occur in Capacity Ratings (Items no. 3 through 7) Since Last Report Give Reasons
- 9. Power Level To Which Restricted. If Any (Net MWe)
- 10. Reasons For Restrictions.
This Mo.
Yr. to Date
- 11. Hours in Reporting Period 745.0 7296.0
- 12. No. of Hrs. Reactor Was Critical 745.0 5999.1
- 13. Reactor Reserve Shutdown Hours 0 0 0.0
- 14. Hours Generator on Line 745.0 5874.6
- 15. Unit Reserve Shutdown Hours 0.0 0.0
- 16. Gross Therm. Energy Gen. (MWH) 2535385.4 19405861.2
- 17. Gross Elect. Energy Gen. (MWH) 826980.0 6283120.0
- 18. Net Elect. Energy Gen. (MWH) 800342.0 6075919.4
- 19. Unit Service Factor 100.0 80.5
- 20. Unit Availability Factor 100.0 80.5
- 21. Unit Capacity Factor (MDC Net) 101.3 78.6
- 22. Unit Capacity Factor (DER Net) 98.6 764
- 23. Unit Forced Outage Rate 0.0 7.2
- 24. Shutdowns Scheduled over Next Six Months (Type,Date,and Duration):
- 25. If Shut Down At End of Report Period, Ested Date of Startup:
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION Cumm.
218130.0 140104.1 00 136276.5 0.0 426233210.5 138109630.0 133140973.3 63.1 63.1 58 8 57.1 24.0
AVERAGE DAILY POWER LEVEL (MWe-Net)
DOCKET NO.
UNIT DATE COMPLETED BY TELEPHONE 50-315 ONE 04-Nov-02 RAF Harris 616-465-5901 MONTH Oct-02 AVERAGE DAILY POWER LEVEL 1003 999 1002 1012 947 886 1010 1011 1020 1005 1014 1013 1023 1023 1015 1024 DAY 10/17/02 10/18/02 10/19/02 10/20/02 10/21/02 10/22/02 10/23/02 10/24/02 10/25/02 10/26/02 10/27/02 10/28/02 10/29/02 10/30/02 10/31/02 AVERAGE DAILY POWER LEVEL 1028 1027 1027 1025 1021 1029 1029 1030 1030 1027 1030 1026 1035 1032 1031 DAY 10/1/02 10/2/02 10/3/02 10/4/02 10/5/02 10/6/02 10/7/02 10/8/02 10/9/02 10/10/02 10/11/02 10/12/02 10/13/02 10/14/02 10/15/02 10/16/02
AVERAGE DAILY POWER LEVEL (MWe-Net)
DOCKET NO.
UNIT DATE COMPLETED BY TELEPHONE 50-316 1TWO 4-Nov-02 RAF Harris 616-465-5901 MONTH Oct-02 AVERAGE DAILY POWER LEVEL 1062 1052 1054 1061 1065 1063 1072 1071 1056 1061 1067 1063 1077 1069 1074 1081 DAY AVERAGE DAILY POWER LEVEL 10/17/02 10/18102 10/19/02 10/20/02 10/21/02 10/22/02 10/23/02 10/24/02 10/25/02 10/26/02 10/27/02 10/28/02 10/29/02 10/30/02 10/31/02 1089 1077 1080 1074 1079 1087 1081 1087 1092 1087 1089 1088 1094 1099 1099 DAY 10/1/02 10/2/02 10/3/02 10/4/02 10/5/02 10/6/02 10/7/02 10/8/02 1019/02 10/10/02 10/11/02 10/12/02 10/13102 10/14/02 10/15102 10/16/02
DOCKET NO.
UNIT NAME DATE COMPLETED BY TELEPHONE PAGE 50-315 D.C. Cook Unit 1' November 6, 2002 B. O'Rourke 616-465-5901 1 of 1 UNIT SHUTDOWNS AND POWER REDUCTIONS - October 2002 METHOD OF SHUTTING LICENSEE DURATION DOWN EVENT SYSTEM COMPONENT CAUSE AND CORRECTIVE ACTION NO.
DATE TYPE1 HOURS REASON2 REACTOR 3 REPORT NO.
CODE4 CODE5 TO PREVENT RECURRENCE None 1 TYPE:
F: Forced S: Scheduled 2 REASON:
A: Equipment Failure (Explain)
B: Maintenance or Test C: Refueling D: Regulatory Restriction E: Operator Training and License Examination F: Administrative G: Operational Error (Explain)
H: Other (Explain) 3 METHOD:
1: Manual 2: Manual Scram 3: Automatic Scram 4: Other (Explain) 4 SYSTEM:
Exhibit G - Instructions for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 0161) 5 COMPONENT:
Exhibit I: Same Source
DOCKET NO.
UNIT NAME DATE COMPLETED BY TELEPHONE PAGE 50-316 D.C. Cook Unit 2 November 6, 2002 B. O'Rourke 616-465-5901 1 of 1 UNIT SHUTDOWNS AND POWER REDUCTIONS - October 2002 METHOD OF SHUTTING LICENSEE DURATION DOWN EVENT SYSTEM COMPONENT CAUSE AND CORRECTIVE ACTION NO.
DATE TYPE1 HOURS REASON 2 REACTOR3 REPORT NO.
CODE 4 CODE 5 TO PREVENT RECURRENCE None 1 TYPE:
F: Forced S: Scheduled 2 REASON:
A: Equipment Failure (Explain)
B: Maintenance or Test C: Refueling D: Regulatory Restriction E: Operator Training and License Examination F: Administrative G: Operational Error (Explain)
H: Other (Explain) 3 METHOD:
1: Manual 2: Manual Scram 3: Automatic Scram 4: Other (Explain) 4 SYSTEM:
Exhibit G - Instructions for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 0161) 5 COMPONENT:
Exhibit I: Same Source