Text

From:

Peter Tam To:

INTernet:dosaj@nimo.com; INTernet:leonardm@nimo.com; internet:wolniakd@nimo.com Date:

4/5/02 3:18PM

Subject:

NMP1 Amendment Re. RETS (TAC MB2442)

John:

We are essentially done with reviewing your 10/19/01 amendment application. Our reviewer Audrey Hayes made a number of observations and would like to discuss with your people in a conference call:

ODCM, Change #21

1. You changed the word "or," (NUREG-1302 3.11.4.a) to "and" in the third sentence of proposed TS Section 3.6.15.d, page I 3.1-24 (Controls) of the proposed ODCM.
2. In the same section, you omitted NUREG-1302 3.11.4.a descriptive wording regarding the content of the special report.

TS, Change 36

1. Proposed TS 6.12.1.d.1: You proposed alternate wording (radiation monitoring and indicating device) for the NUREG-1433 wording (A radiation monitoring device that continuously displays radiation dose rates in the area.) You subsequently use "radiation monitoring and indicating device" throughout the remainder of the proposed TS.
2. Proposed TS 6.12.1.d.2: You proposed alternate wording (alarming dosimeter) for the NUREG-1433 wording (A radiation monitoring device that continuously integrates the radiation dose rates in the area and alarms when the devices dose alarm setpoint is reached...) You subsequently use "alarming dosimeter" throughout the remainder of the proposed TS.
3. Proposed TS 6.12.1.d.4(b): You omitted the NUREG-1433 7.7.1.4 (ii) wording "...and with the means to communicate with individuals in the area who are covered by such surveillance."
4. Proposed TS 6.12.2.a and TS 6.12.2.1.2: You omitted "continuously" with respect to NUREG-1433 5.7.2.a wording "..shall be provided with a locked or continuously guarded door or gate..."
5. Proposed TS 6.12.2.d.4: You omitted NUREG-1433 5.7.2.d.4 wording "...in the area."

Please call me to schedule a conference call. This e-mail only serves to communicate issues to be discussed in the conference call. It does not convey a formal NRC staff position and does not formally request for additional information. Disposition of the above issues will be discussed in the conference call.

Peter S. Tam, Senior Project Manager Project Directorate I-1 Division of Licensing Project Management Office of Nuclear Reactor Regulation

e-mail: pst@nrc.gov Tel.: 301-415-1451 CC:

Audrey Hayes; Stephen Klementowicz Mail Envelope Properties (3CAE069A.501 : 10 : 20510)

Subject:

NMP1 Amendment Re. RETS (TAC MB2442)

Creation Date:

4/5/02 3:18PM From:

Peter Tam Created By:

PST@nrc.gov Recipients Action Date & Time nimo.com Transferred 04/05/02 03:18PM dosaj (INTernet:dosaj@nimo.com) leonardm (INTernet:leonardm@nimo.com) wolniakd (internet:wolniakd@nimo.com) nrc.gov owf2_po.OWFN_DO Delivered 04/05/02 03:18PM ACH2 CC (Audrey Hayes)

Opened 04/09/02 10:44AM SXK CC (Stephen Klementowicz)

Opened 04/05/02 03:36PM Post Office Delivered Route nimo.com INTernet owf2_po.OWFN_DO 04/05/02 03:18PM nrc.gov Files Size Date & Time MESSAGE 3928 04/05/02 03:18PM Options Auto Delete:

No Expiration Date:

None Notify Recipients:

Yes Priority:

Standard Reply Requested:

No Return Notification:

None Concealed

Subject:

No Security:

Standard To Be Delivered:

Immediate Status Tracking:

Delivered & Opened