April 1, 2002 LICENSEE:
DUKE ENERGY CORPORATION FACILITY:
CATAWBA NUCLEAR STATION, UNITS 1 AND 2
SUBJECT:
MEETING
SUMMARY
ON THE RESULTS OF CONTROL ROOM IN-LEAKAGE TESTING (TAC NOS. MB3758 AND MB3759)
On February 21, 2002, the Nuclear Regulatory Commission (NRC) met with Duke Energy (the licensee) to discuss the results of their in-leakage testing of the control room envelope at Catawba Nuclear Station, Units 1and 2. The results of the in-leakage testing were used by the licensee for establishing the control room envelope's in-leakage assumption.
The licensee performed both integrated and component testing of the main control room envelope at Catawba Nuclear Station. The component testing consisted of portions of the control room ventilation system ductwork which was external to the control room envelope and ductwork from other systems which penetrate the control room envelope. The integrated test measured the in-leakage for the entire envelope. The integrated test results were hampered because several flows could not be measured accurately due to either the tracer gas ejection point location or inadequate mixing following injection. Thus, the accuracy of the integrated test was questionable.
The staff will utilize the information provided by the licensee in reviewing the licensees application dated December 20, 2001, for partial implementation of an alternate source term at Catawba Nuclear Station.
A list of the meeting attendees is enclosed. The handout provided by the licensee is accessible electronically from the Agencywide Documents Access and Management System (ADAMS) Public Electronic Reading Room on the internet at the NRC Web site, http://www.nrc.gov/reading-rm/adams/html by accession number ML020570184. Persons who do not have access to ADAMS or who encounter problems in accessing the documents located in ADAMS, should contact the NRC PDR Reference staff by telephone at 1-800-397-4209 or 301-415-4737, or by e-mail to pdr@nrc.gov.
/RA/
Chandu P. Patel, Project Manager, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-413 and 50-414
Enclosure:
As stated cc w/encls: See next page
April 1, 2002 LICENSEE:
DUKE ENERGY CORPORATION FACILITY:
CATAWBA NUCLEAR STATION, UNITS 1 AND 2
SUBJECT:
MEETING
SUMMARY
ON THE RESULTS OF CONTROL ROOM IN-LEAKAGE TESTING (TAC NOS. MB3758 AND MB3759)
On February 21, 2002, the Nuclear Regulatory Commission (NRC) met with Duke Energy (the licensee) to discuss the results of their in-leakage testing of the control room envelope at Catawba Nuclear Station, Units 1and 2. The results of the in-leakage testing were used by the licensee for establishing the control room envelope's in-leakage assumption.
The licensee performed both integrated and component testing of the main control room envelope at Catawba Nuclear Station. The component testing consisted of portions of the control room ventilation system ductwork which was external to the control room envelope and ductwork from other systems which penetrate the control room envelope. The integrated test measured the in-leakage for the entire envelope. The integrated test results were hampered because several flows could not be measured accurately due to either the tracer gas ejection point location or inadequate mixing following injection. Thus, the accuracy of the integrated test was questionable.
The staff will utilize the information provided by the licensee in reviewing the licensees application dated December 20, 2001, for partial implementation of an alternate source term at Catawba Nuclear Station.
A list of the meeting attendees is enclosed. The handout provided by the licensee is accessible electronically from the Agencywide Documents Access and Management System (ADAMS) Public Electronic Reading Room on the internet at the NRC Web site, http://www.nrc.gov/reading-rm/adams/html by accession number ML020570184. Persons who do not have access to ADAMS or who encounter problems in accessing the documents located in ADAMS, should contact the NRC PDR Reference staff by telephone at 1-800-397-4209 or 301-415-4737, or by e-mail to pdr@nrc.gov.
/RA/
Chandu P. Patel, Project Manager, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-413 and 50-414
Enclosure:
As stated cc w/encls: See next page DISTRIBUTION:
PUBLIC RLaufer OGC JRavel PDII-1 R/F CPatel JHayes DMcCain JZwolinksi/TMarsh CHawes HWalker SRosenberg HBerkow ACRS VKlco Accession Number: ML020840724 OFC PDII-1/PM PDII-1/LA PDII-1/ASC NAME CPatel CHawes RLaufer DATE 3/28/02 3/28/02 3/29/02 OFFICIAL RECORD COPY
Enclosure ATTENDEES LIST FEBRUARY 21, 2002 MEETING WITH DUKE ENERGY NRC Duke J. Hayes S. Schultz H. Walker J. Kammer V. Klco M. Chernoff C. Patel R. Banker J. Raval
Catawba Nuclear Station cc:
Mr. Gary Gilbert Regulatory Compliance Manager Duke Energy Corporation 4800 Concord Road York, South Carolina 29745 Ms. Lisa F. Vaughn Legal Department (PB05E)
Duke Energy Corporation 422 South Church Street Charlotte, North Carolina 28201-1006 Anne Cottingham, Esquire Winston and Strawn 1400 L Street, NW Washington, DC 20005 North Carolina Municipal Power Agency Number 1 1427 Meadowwood Boulevard P. O. Box 29513 Raleigh, North Carolina 27626 County Manager of York County York County Courthouse York, South Carolina 29745 Piedmont Municipal Power Agency 121 Village Drive Greer, South Carolina 29651 Ms. Karen E. Long Assistant Attorney General North Carolina Department of Justice P. O. Box 629 Raleigh, North Carolina 27602 Elaine Wathen, Lead REP Planner Division of Emergency Management 116 West Jones Street Raleigh, North Carolina 27603-1335 North Carolina Electric Membership Corporation P. O. Box 27306 Raleigh, North Carolina 27611 Senior Resident Inspector U.S. Nuclear Regulatory Commission 4830 Concord Road York, South Carolina 29745 Virgil R. Autry, Director Division of Radioactive Waste Management Bureau of Land and Waste Management Department of Health and Environmental Control 2600 Bull Street Columbia, South Carolina 29201-1708 Mr. C. Jeffrey Thomas Manager - Nuclear Regulatory Licensing Duke Energy Corporation 526 South Church Street Charlotte, North Carolina 28201-1006 Saluda River Electric P. O. Box 929 Laurens, South Carolina 29360 Mr. Peter R. Harden, IV VP-Customer Relations and Sales Westinghouse Electric Company 6000 Fairview Road 12th Floor Charlotte, North Carolina 28210
Catawba Nuclear Station cc:
Mr. T. Richard Puryear Owners Group (NCEMC)
Duke Energy Corporation 4800 Concord Road York, South Carolina 29745 Richard M. Fry, Director Division of Radiation Protection North Carolina Department of Environment, Health, and Natural Resources 3825 Barrett Drive Raleigh, North Carolina 27609-7721