ML020440233
| ML020440233 | |
| Person / Time | |
|---|---|
| Site: | Palisades |
| Issue date: | 01/14/2002 |
| From: | Lahti L Nuclear Management Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| Download: ML020440233 (5) | |
Text
Committed to Nuclear Excellence Palisades Nuclear Plant Operated by Nuclear Management Company, LLC January 14, 2002 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 DOCKET 50-255 - LICENSE DPR PALISADES NUCLEAR PLANT LICENSEE REPORT OF MONTHLY OPERATING DATA Attached are the Monthly Operating Data and Summary of Operating Experience for the Palisades Nuclear Plant for the month of December 2001.
If you have any questions, please contact Mr. Rich Schmidt at (616) 764-2185.
turie A. Lahti Manager, Licensing CC Regional Administrator, USNRC, Region III NRC Resident Inspector, Palisades LBrandon, Michigan Department of Environmental Quality BWJorgensen, Michigan Department of Labor RDWhale, Michigan Public Service Commission Records Center, INPO SMMclntyre, P-26-204 Attachment 27780 Blue Star Memorial Highway
- Covert, MI 49043 Telephone: 616.764.2000 Aj+
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO 50-255 UNIT Palisades DATE 01/04/02 COMPLETED BY SFPierce TELEPHONE (616)764-2239 MONTH December 2001 DAY AVERAGE DAILY POWER LEVEL (MWe Net)
- 1.
0
- 2.
0
- 3.
0
- 4.
0
- 5.
0
- 6.
0
- 7.
0
- 8.
0
- 9.
0
- 10.
0
- 11.
0
- 12.
0
- 13.
0
- 14.
0
- 15.
0
- 16.
0 DAY AVERAGE DAILY POWER LEVEL (MWe Net)
- 17.
0
- 18.
0
- 19.
0
- 20.
0
- 21.
0
- 22.
0
- 23.
0
- 24.
0
- 25.
0
- 26.
0
- 27.
0
- 28.
0
- 29.
0
- 30.
0
- 31.
0 INSTRUCTIONS:
On this format, list the average daily unit power level in MWe-NET for each day in the reporting month.
Compute to the nearest whole megawatt.
SUMMARY
OF OPERATING EXPERIENCE FOR DECEMBER, 2001 The Plant began the month of December 2001 in mode 5, cold shutdown, to complete repairs to the primary coolant system at the control rod drive housings.
The plant remained in mode 5 through the end of the month, pending repair completion.
OPERATING DATA REPORT DOCKET NO:
50-255 DATE (Mo-Da-Yr): 01-04-02 COMPLETED BY: SFPierce TELEPHONE (616) 764-2239 OPERATING STATUS:
NOTES:
- 1. UNIT NAME Palisades
- 2. REPORTING PERIOD (YrMoDa-YrMoDa):
011201-011231
- 3. LICENSED THERMAL POWER (Mwt) 2530
- 4. NAMEPLATE RATING (GROSS Mwe) 811.7
- 5. DESIGN ELECTRICAL RATING (NET Mwe) 805
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSS Mwe) 770
- 7. MAXIMUM DEPENDABLE CAPACITY (NET Mwe) 730
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEM NUMBERS 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe):
- 10. REASONS FOR RESTRICTIONS, IF ANY:
This Month Yr-to-Date Cumulative
- 11.
HOURS IN REPORTING PERIOD 744.0 8760.0 263295.0
- 12.
NUMBER OF HOURS REACTOR WAS CRITICAL 0.0 3184.1 161226.7
- 13.
REACTOR RESERVE SHUTDOWN HOURS
- 14.
HOURS GENERATOR ON-LINE 0.0 3120.0 155790.5
- 15.
UNIT RESERVE SHUTDOWN HOURS
- 16.
GROSS THERMAL ENERGY GENERATED (MWH) 0 7547698 351124577
- 17.
GROSS ELECTRICAL ENERGY GENERATED (MWH) 0 2475668 111759028
- 18.
NET ELECTRICAL ENERGY GENERATED (MWH) 0 2355631 105693815
- 19.
UNIT SERVICE FACTOR 0.0%
35.6%
59.2%
- 20.
UNIT AVAILABILITY FACTOR 0.0%
35.6%
59.2%
- 21.
UNIT CAPACITY FACTOR (USING MDC NET)
- 0.0%
36.8%
58.0%
- 22.
UNIT CAPACITY FACTOR (USING DER NET) 0.0%
33.4%
49.9%
- 23.
UNIT FORCED OUTAGE RATE 100.0%
59.9%
26.1%
- 24. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE AND DURATION OF EACH):
- 25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION
- Based on condenser backpressure
- Weighted Average (635 MWe used as MDC Net prior to October 1985)
REPORT MONTH December 2001 DOCKET NO 50-255 UNIT Palisades DATE 01/04/02 COMPLETED BY SFPierce TELEPHONE 616-764-2239 UNIT SHUTDOWNS AND POWER REDUCTIONS No.
Date (YrMoDa)
Type1 Duration (Hours)
Reason2 Method of Shutting Down Reactor3 Licensee Event Report #
System Component Code 4 Codes Cause & Corrective Action to Prevent Recurrence 12 01/12/01 F
744 hrs A
LER 01-004 AA DRIV Primary Coolant System leakage, repairs consisted of CRDM Upper Housing replacements
- 2.
Reason:
A-Equipment Failure (Explain)
B-Maintenance or Test C-Refueling D-Regulatory Restriction E-Operator Training & License Examination F-Administrative G-Operational Error (Explain)
H-Other (Explain)
- 3.
Method:
1-Manual 2-Manual Scram 3-Automatic Scram 4-Other (Explain) 4, Exhibit G - Instructions for Preparation of Data Entry Sheets for Licensee Event Report (LER) File (NUREG-0161)
- 5.
Exhibit I - Same Source
- 1.
F: Forced S: Scheduled 1