January 23, 2002 Mr. M. S. Tuckman Executive Vice-President Nuclear Generation Duke Energy Corporation PO Box 1006 Charlotte, NC 28201-1006
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE MCGUIRE NUCLEAR STATION, UNITS 1 AND 2, AND CATAWBA NUCLEAR STATION, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION (LRA)
Dear Mr. Tuckman:
By letter dated June 13, 2001, Duke Energy Corporation (Duke) submitted for Nuclear Regulatory Commission (NRC) review an application, pursuant to 10 CFR Part 54, to renew the operating licenses for the McGuire Nuclear Station, Units 1 and 2, and Catawba Nuclear Station, Units 1 and 2. The NRC staff is reviewing the information contained in this license renewal application and has identified, in the enclosure, areas where additional information is needed to complete its review. Specifically, the enclosed request for additional information (RAI) is from the following section(s) of the LRA:
Section 2.2, Plant Level Scoping Results Please provide a schedule by letter, or electronic mail for the submittal of your response within 30 days of the receipt of this letter. Additionally, the staff would be willing to meet with Duke prior to the submittal of the response to provide clarification of the staffs request for additional information.
Sincerely,
/RA/
Rani L. Franovich, Project Manager License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket Nos. 50-369, 50-370, 50-413 and 50-414
Enclosures:
As stated cc w/encl: See next page
Mr. M. S. Tuckman Executive Vice-President Nuclear Generation Duke Energy Corporation PO Box 1006 Charlotte, NC 28201-1006
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE MCGUIRE NUCLEAR STATION, UNITS 1 AND 2, AND CATAWBA NUCLEAR STATION, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION
Dear Mr. Tuckman:
By letter dated June 13, 2001, Duke Energy Corporation (Duke) submitted for Nuclear Regulatory Commission (NRC) review an application, pursuant to 10 CFR Part 54, to renew the operating licenses for the McGuire Nuclear Station, Units 1 and 2, and Catawba Nuclear Station, Units 1 and 2. The NRC staff is reviewing the information contained in this license renewal application and has identified, in the enclosure, areas where additional information is needed to complete its review. Specifically, the enclosed request for additional information (RAI) is from the following section(s) of the LRA:
Section 2.2, Plant Level Scoping Results Please provide a schedule by letter, or electronic mail for the submittal of your response within 30 days of the receipt of this letter. Additionally, the staff would be willing to meet with Duke prior to the submittal of the response to provide clarification of the staffs request for additional information.
Sincerely,
/RA/
Rani L. Franovich, Project Manager License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket Nos. 50-369, 50-370, 50-413 and 50-414
Enclosures:
As stated cc w/encl: See next page DISTRIBUTION:
See next page Document Name: C:\\Program Files\\Adobe\\Acrobat 4.0\\PDF Output\\Duke RAI - Scoping Results.wpd OFFICE PM:RLEP:DRIP LA:DRIP SC:RLEP:DRIP BC:RLEP:DRIP NAME RFranovich EGHylton PTKuo CIGrimes DATE 01/18/2002 01/17 /2002 01/23/2002 01/23/2002 OFFICIAL RECORD COPY
McGuire & Catawba Nuclear Stations, Units 1 and 2 Mr. Gary Gilbert Regulatory Compliance Manager Duke Energy Corporation 4800 Concord Road York, South Carolina 29745 Ms. Lisa F. Vaughn Duke Energy Corporation 422 South Church Street Charlotte, North Carolina 28201-1006 Anne Cottington, Esquire Winston and Strawn 1400 L Street, NW Washington, DC 20005 North Carolina Municipal Power Agency Number 1 1427 Meadowwood Boulevard P. O. Box 29513 Raleigh, North Carolina 27626 County Manager of York County York County Courthouse York, South Carolina 29745 Piedmont Municipal Power Agency 121 Village Drive Greer, South Carolina 29651 Ms. Karen E. Long Assistant Attorney General North Carolina Department of Justice P. O. Box 629 Raleigh, North Carolina 27602 Ms. Elaine Wathen, Lead REP Planner Division of Emergency Management 116 West Jones Street Raleigh, North Carolina 27603-1335 Mr. Robert L. Gill, Jr.
Duke Energy Corporation Mail Stop EC-12R P. O. Box 1006 Charlotte, North Carolina 28201-1006 Mr. Alan Nelson Nuclear Energy Institute 1776 I Street, N.W., Suite 400 Washington, DC 20006-3708 North Carolina Electric Membership Corporation P. O. Box 27306 Raleigh, North Carolina 27611 Senior Resident Inspector U.S. Nuclear Regulatory Commission 4830 Concord Road York, South Carolina 29745 Mr. Virgil R. Autry, Director Dept of Health and Envir Control 2600 Bull Street Columbia, South Carolina 29201-1708 Mr. C. Jeffrey Thomas Manager - Nuclear Regulatory Licensing Duke Energy Corporation 526 South Church Street Charlotte, North Carolina 28201-1006 Mr. L. A. Keller Duke Energy Corporation 526 South Church Street Charlotte, North Carolina 28201-1006 Saluda River Electric P. O. Box 929 Laurens, South Carolina 29360 Mr. Peter R. Harden, IV VP-Customer Relations and Sales Westinghouse Electric Company 6000 Fairview Road - 12th Floor Charlotte, North Carolina 28210 Mr. T. Richard Puryear Owners Group (NCEMC)
Duke Energy Corporation 4800 Concord Road York, South Carolina 29745 Mr. Richard M. Fry, Director North Carolina Dept of Env, Health, and Natural Resources 3825 Barrett Drive Raleigh, North Carolina 27609-7721 County Manager of Mecklenburg County 720 East Fourth Street Charlotte, North Carolina 28202 Michael T. Cash Regulatory Compliance Manager Duke Energy Corporation
McGuire Nuclear Site 12700 Hagers Ferry Road Huntersville, North Carolina 28078 Senior Resident Inspector U.S. Nuclear Regulatory Commission 12700 Hagers Ferry Road Huntersville, North Carolina 28078 Dr. John M. Barry Mecklenburg County Department of Environmental Protection 700 N. Tryon Street Charlotte, North Carolina 28202 Mr. Gregory D. Robison Duke Energy Corporation Mail Stop EC-12R 526 S. Church Street Charlotte, NC 28201-1006 Mary Olson Nuclear Information & Resource Service Southeast Office P.O. Box 7586 Asheville, North Carolina 28802 Paul Gunter Nuclear Information & Resource Service 1424 16th Street NW, Suite 404 Washington, DC 20036 Lou Zeller Blue Ridge Environmental Defense League P.O. Box 88 Glendale Springs, North Carolina 28629 Don Moniak Blue Ridge Environmental Defense League Aiken Office P.O. Box 3487 Aiken, South Carolina 29802-3487
Request for Additional Information McGuire Nuclear Station, Units 1 and 2, and Catawba Nuclear Station, Units 1 and 2 2.2 Plant Level Scoping Results 2.2.1-1Section 8.1.2 of the McGuire Updated Final Safety Analysis Report (UFSAR) states that Each unit has two redundant and independent 4160 Volt Essential Auxiliary Power Systems. All of the loads listed in Table 8-1 are supplied power during a blackout or accident condition, are fed from the 4160 Volt Essential Auxiliary Power System, either at 4160 Volts or through transformers at a lower voltage. Table 8-1 of the McGuire UFSAR lists both the control rod drive ventilation fans and the incore instrumentation room air handling units as receiving essential auxiliary power during a blackout. As such, it appears that the control rod drive ventilation (VR) and the incore instrumentation area ventilation (VT) systems are relied upon to be operational during a loss of offsite power event and should be within the scope of license renewal. Table 2.2-3 of the McGuire license renewal application (LRA) lists these systems as Not within the Scope of License Renewal. Please provide the basis for excluding these systems from the scope of license renewal.
2.2.1-2Table 2.2-3 lists Diesel Building (#7434) as not being within the scope of license renewal. Table 2.2-1 lists the Diesel Generator Buildings as being within the scope of license renewal. It is not clear what the difference between these buildings is. Table 3-1 of the McGuire UFSAR lists the diesel building as being a seismically designed category I structure. Similarly Table 3-7 of the UFSAR lists the diesel building ventilation system as being safety class 2E. It is not clear whether the UFSAR is referencing the diesel generator buildings in these tables or diesel building (#7434).
Please explain the basis for excluding the diesel building (#7434) from the scope of license renewal.
2.2.1-3Section 12.1.2.1 of the McGuire UFSAR states that the Radwaste Facility is shielded by two-foot thick concrete walls. Similarly, the same section indicates that Retired Steam Generator Storage Facility is shielded by 2-1/2 foot thick concrete walls. These shield walls are necessary because these facilities could contain significant levels of radioactivity. Are these walls necessary to ensure the capability to mitigate the consequences of accidents that could result in potential offsite exposure comparable to those referred to in 10 CFR 50.34(a)(1), 10 CFR 50.67(b)(2), or 10 CFR 100.11? If so, please provide the basis for their exclusion from the scope of license renewal.
2.2.1-410CFR54.4(a)(3) states that all systems, structures, and components relied on in safety analyses or plant evaluations to perform a function that demonstrates compliance with the Commission's regulations for fire protection (10 CFR 50.48), environmental qualification (10 CFR 50.49), pressurized thermal shock (10 CFR 50.61), anticipated transients without scram (10 CFR 50.62), and station blackout (10 CFR 50.63) are within the scope of license renewal. Table 2.2-3 of the LRA lists the mechanical systems that the applicant has determined are not within the scope of license renewal.
This table lists the condensate and condensate storage systems as not within the scope of license renewal. In its February 19, 1992, safety evaluation report on McGuires response to the Station Blackout Rule, the staffs acceptance of McGuires response was partially based on the licensees statement that adequate water sources were available to provide a four hour coping period. The specific water sources credited include the auxiliary feedwater condensate storage tank, the upper surge tanks, and the condenser hotwell.
As such, it appears that the condensate and condensate storage systems should be within the scope of license renewal because they are relied upon during a station blackout event. Please provide the basis for excluding them from the scope of license renewal.
2.2.1-5Table 2.2-4 of the Catawba license renewal application (LRA) states that the Retired Steam Generator Storage Facility is not within the scope of license renewal. However, Section 12.3.2.2 of the Catawba UFSAR states that the Retired Steam Generator Storage Facility is shielded by 21/2 thick concrete walls. These shield walls are apparently necessary because this facility could contain significant levels of radioactivity.
Are these walls necessary to ensure the capability to mitigate the consequences of a design basis event that could result in potential offsite exposure comparable to those referred to in 10 CFR 50.34(a)(1), 10 CFR 50.67(b)(2), or 10 CFR 100.11? If so, please provide the basis for the exclusion of the Retired Steam Generator Storage Facility from the scope of license renewal.
DISTRIBUTION:
HARD COPY RLSB RF E. Hylton E-MAIL:
PUBLIC J. Johnson W. Borchardt D. Matthews C. Carpenter C. Grimes B. Zalcman J. Strosnider (RidsNrrDe)
E. Imbro G. Bagchi K. Manoly W. Bateman J. Calvo C. Holden P. Shemanski S. Rosenberg G. Holahan B. Boger D. Thatcher G. Galletti B. Thomas J. Moore R. Weisman M. Mayfield A. Murphy W. McDowell S. Droggitis N. Dudley RLEP Staff R. Martin C. Patel C. Julian (RII)
R. Haag (RII)
A. Fernandez (OGC)
J. Wilson M. Khanna C. Munson R. Elliott B. Rogers
Division of Regulatory Improvement Programs COVER PAGE DATE:
January 17, 2002
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE MCGUIRE NUCLEAR STATION, UNITS 1 AND 2, AND CATAWBA NUCLEAR STATION, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION ORIGINATOR:
Rani Franovich SECRETARY:
S. Chey