NRC-02-002 Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, WI 54216-9511 Two Rivers, WI 54241 NM C 920.388.2560 920.755.2321 Committed to Nuclear Excellence Kewaunee / Point Beach Nuclear Operated by Nuclear Management Company, LLC January 3, 2002 10 CFR 50, App. E U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 Ladies/Gentlemen:
Docket 50-305 Operating License DPR-43 Kewaunee Nuclear Power Plant EMERGENCY RESPONSE DATA SYSTEM Pursuant to 10 CFR 50 Appendix E, Nuclear Management Company, LLC hereby submits a copy of the "ERDS" data point library, Figures EPMPFG-09.05-07 and EPMPFG-09.05-08, and Index EPMPFG-09.05-00 from our procedure EPMP 9.5, "Control of ERDS Hardware and Software." This submittal is being sent to ensure the NRC data library used for ERDS has incorporated the revisions to these three figures.
Pursuant to 10 CFR 50.4, two additional copies of this letter and attachment are hereby submitted to Region III. Also, as required, one copy of this letter and attachment is submitted to the Kewaunee Nuclear Power Plant NRC Senior Resident Inspector.
Sincerely, Thomas Coutu Manager-Kewaunee Plant JMF Attachment cc -
Ms. Karen B. Jackson, US NRC, Incident Response Operation, w/attach NRC Senior Resident Inspector, w/attach.
US NRC, Region III (2 copies), w/attach.
Electric Division, PSCW, w/o attach.
QA Vault, w/attach.
AO~
ATTACHMENT Letter from Thomas Coutu (NMC)
To Document Control Desk (NRC)
Dated January 3, 2002 Re: Change in ERDS Enclosed Pages:
Figure EPMPFG-09.05-00 Figure EPMPFG-09.05-07 Figure EPMPFG-09.05-08
ERDS DATA POINT LIBRARY TABLE INDEX FIGURE/TABLE NUMBER 9.5-1 9.5-2 9.5-3 9.5-4 9.5-5 9.5-6 09.05-07 09.05-08 9.5-9 9.5-10 9.5-11 9.5-12 9.5-13 9.5-14 9.5-15 9.5-16 9.5-17 9.5-18 9.5-19 9.5-20 9.5-21 9.5-22 9.5-23 9.5-24 9.5-25 9.5-26 9.5-27 9.5-28 9.5-29 9.5-30 9.5-31 9.5-32 9.5-33 9.5-34 9.5-35 9.5-36 9.5-37 9.5-38 9.5-39 9.5-40 9.5-41 9.5-42 9.5-43 09.05-44 POINT ID N8020G N7035G N803IG L8024G II 100G T0020G F8007G F8008G L8013G L8014G P8021G P8022G F8009G F801OG F8003A F8004A T0419A T0439A T0406A T0426A P8023G L8015G F0128G F8001G F8002G F0626A NOT AVAIL.
L8001A G0014G G0018G G0015G G0040G G0009G G0032G G0034G G0019G P8004A T1000A X8001A L8008A M0001A M0002G M0004A ERDSDATATYPE KEWAUNEE NUCLEAR POWER PLANT GENERIC DESCRIPTION NUCLEAR INSTRUMENTS, POWER RANGE NUCLEAR INSTRU, INTERMED. RANGE NUCLEAR INSTRU, SOURCE RANGE REACTOR VESSEL WATER LEVEL HIGHEST TEMP AT THE CORE EXIT SATURATION TEMP-HIGHEST CET REACTOR COOLANT FLOW LOOP A REACTOR COOLANT FLOW LOOP B STEAM GENERATOR A WATER LEVEL STEAM GENERATOR B WATER LEVEL STEAM GENERATOR A PRESSURE STEAM GENERATOR B PRESSURE STM GEN A MAIN FEEDWATER FLOW STM GEN B MAIN FEEDWATER FLOW STM GEN A AUXILIARY FW FLOW STM GEN B AUXILIARY FW FLOW STM GEN A INLET TEMPERATURE STM GEN B INLET TEMPERATURE STM GEN A OUTLET TEMPERATURE STM GEN B OUTLET TEMPERATURE REACTOR COOLANT SYSTEM PRESSURE PRIMARY SYSTEM PRESSURIZER LEVEL PRIMARY SYSTEM CHARGING FLOW HIGH PRESS SAFETY INJECTION FLOW HIGH PRESS SAFETY INJECTION FLOW LOW PRESS SAFETY INJECTION FLOW CONTAINMENT SUMP NARROW RNG LVL CONTAINMENT SUMP WIDE RNG LVL RADIOACTIVITY OF RELEASED GASSES RADIOACT. OF RELEASED LIQUIDS CONDENSER AIR EJECTOR RADIOACT.
RADIATION LEVEL IN CONTAINMENT RAD LEVEL OF RCS LETDOWN LINE STM GEN A STEAM LINE RAD LEVEL STM GEN B STEAM LINE RAD LEVEL STM GEN BLOWDOWN RAD LEVEL CONTAINMENT PRESSURE CONTAINMENT TEMPERATURE CONTAINMENT HYDROGEN CONCEN.
BORATED WATER STORAGE TANK LEVEL WIND SPEED AT REACTOR SITE WIND DIRECTION AT REACTOR SITE AIR STABILITY AT REACTOR SITE ERDS PLANT/SIMULATOR DATA REV.
A A
A A
A A
A A
A A
A A
A A
C C
C C
A A
A B
B A
A A
C C
C C
C C
C C
A A
A A
A A
A A
LIBRARY SHEET REVISION DATE 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 12/21/01 12/21/01 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 03/06/95 03/06/95 03/06/95 03/06/95 04/08/94 04/08/94 04/08/94 01/13/97 01/13/97 04/08/94 04/08/94 04/08/94 03/06/95 03/06/95 03/06/95 03/06/95 03/06/95 03/06/95 03/06/95 03/06/95---
04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 04/08/94 05/10/01 Date:
DEC 21 2001 4 1 ^f 4 Figure EPMPFG-09.05-00 Rev. L
=-Jý
REACTOR COOLANT FLOW LOOP A KEWAUNEE NUCLEAR POWER PLANT FIELD KNPP ERDS DATA ITEM LLENGTH DATE:
(8) 05/26/95 REACTOR UNIT:
(3)
KW1 DATA FEEDER:
(10)
N/A NRCERDSPARAM:
(12)
CORE FLOW POINT ID3:
(12)
(40)
RCLA AVERAGE FLOW (LOOP A)
GENERIC/COND DESC:
(32)
REACTOR COOLANT FLOW LOOP A ANALOG/DIGITAL:
(1)
A (A, D)
ENGR UNITS/DIG ST:
(12)
PCT ENGR UNITS CONVERS:
(40)
N/A MIN INSTR RANGE:
(10) 0 MAX INSTR RANGE:
(10) 110 ZERO PT REF:
(6)
N/A REF PT NOTES:
(40)
N/A PROC OR SENS:
(1)
P (P, S)
NUMBER OF SENSORS:
(3) 3 HOW PROCESSED:
(40)
AVERAGE SENSOR LOCATIONS:
(40)
CONTAINMENT ALARM/TRIP SET PT:
(40) 90% REACTOR TRIP NI DET PWR SUPPLY CUTOFF PWR LVL:
(15)
N/A NI DET PWR SUPPLY TURN ON PWR LVL:
(15)
N/A INSTR FAIL MODE:
(30)
LOW TEMP COMP FOR DP )LMTRS:
(3)
N (Y, N, N/A)
LEVEL REF LEG:
(3)
N/A (DRY, WET)
UNIQUE SYS DESC:
(600)
INSTRUMENTS:
FT-41 1, FT-412, FT-413.
100% FLOW = 99,332 GPM (NOTE: THIS NUMBER WILL CHANGE ANNUALLY BASED ON S/G TUBE PLUGGING OR SLEEVING PERFORMED.)
Date:
DEC 2 12001 Figure EPMPFG-09.05-07 Rev. I ragey I oi I
REACTOR COOLANT FLOW LOOP B KEWA'UNEE NUCLEAR POWER PLANT I
FIELD KNPP ERDS DATA ITEM LENGTH DATE:
(8) 05/26/95 REACTOR UNIT:
(3)
KW1 DATA FEEDER:
(10)
N/A NRC ERDS PARAM:
(12)
CORE FLOW POINT ID:
(12)
(40)
RCLB AVERAGE FLOW (LOOP B)
GENERIC/COND DESC:
(32)
REACTOR COOLANT FLOW LOOP B ANALOG/DIGITAL:
(1)
A (A,
D)
ENGR UNITS/DIG ST:
(12)
PCT ENGR UNITS CONVERS:
(40)
N/A MIN INSTR RANGE:
(10) 0 MAX INSTR RANGE:
(10) 110 ZERO PT REF:
(6)
N/A REF PT NOTES:
(40)
N/A PROC OR SENS:
(1)
P (P,
S)
NUMBER OF SENSORS:
(3) 3 HOW PROCESSED:
(40)
AVERAGE SENSOR LOCATIONS:
(40)
CONTAINMENT ALARM/TRIP SET PT:
(40) 90% REACTOR TRIP NI DET PWR SUPPLY CUTOFF PWR LVL:
(15)
N/A NI DET PWR SUPPLY TURN ON PWR LVL:
(15)
N/A INSTR FAIL MODE:
(30)
LOW TEMP COMP FOR DP XMTRS:
(3 N
(Y, N, N/A)
LEVEL REF LEG:
(3)
N/A (DRY, WET)
UNIQUE SYS DESC:
(600)
INSTRUMENTS:
FT-414, FT-415, FT-416.
100% FLOW = 98,568 GPM (NOTE: THIS NUMBER WILL CHANGE ANNUALLY BASED ON S/G TUBE PLUGGING OR SLEEVING PERFORMED.)
m ofI Figure EPMPFG-09.05-08 Rev. I Date: