LR-N13-0040, In-Service Inspection Activities - 90-Day Report, Revision 1

From kanterella
Jump to navigation Jump to search
In-Service Inspection Activities - 90-Day Report, Revision 1
ML13067A281
Person / Time
Site: Salem PSEG icon.png
Issue date: 03/01/2013
From: Fricker C
Public Service Enterprise Group
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
LR-N13-0040 S2R19, Rev 0
Download: ML13067A281 (5)


Text

PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, NJ 08038-0236 0PSEG Nuclear LLC MAR f 2013 ASME Code Case N-532-4 LR-N13-0040 U.S. Nuclear Regulatory Commission A TIN: Document Control Desk Washington, DC 20555-001

Subject:

Salem Nuclear Generating Station Unit 2 Renewed Facility Operating License No. DPR-75 NRC Docket No. 50-311 In-Service Inspection Activities Day Report, Revision 1

Reference:

LR-N13-0021, In-Service Inspection Activities-90 Day Report PSEG Nuclear LLC submitted letter LR-N13-0021 dated February 1, 2013, to transmit to the NRC the Owner's Activity Report for In-Service Inspection (ISi} activities conducted at Salem Generating Station Unit 2 during the nineteenth refueling outage.

Letter LR-N13-0021 included a typographical error in the Certificate of Conformance section of Enclosure 1. This letter corrects ADAMS Accession Nos. ML13038A231 and ML13039A335 and transmits the corrected report. to this letter contains the Salem Unit 2 Owner's Activity Report, Revision 1.

There are no commitments contained in this letter.

Should you have any questions regarding this submittal, please contact C.M. Dahms at (856) 339-5456.

MAR 1 2013 Document Control Desk Page2 LR-N13-0040 C

Mr. W. Dean, Administrator, Region I, NRC Mr. J. Hughey, Project Manager, NRC Ms. E. Bonney, NRC Senior Resident Inspector, Salem Mr. P. Mulligan, Manager IV, NJBNE Mr. L. Marabella, Corporate Commitment Tracking Coordinator Mr. T. Cachaza, Salem Commitment Tracking Coordinator Mr. Milton \\Nashington, Chief Inspector - Occupational Safety and Health Bureau of Boiler and Pressure Vessel Compliance

Document Control Desk LR-N13-0040 Salem Unit 2 Owners Activity Report - S2R19, Revision 1 In Accordance With ASME Section XI Code Case N-532-4

FORM OAR-1 OWNER'S ACTIVITY REPORT Report Number S2RF019 - Revision 1 Owner PSEG Nuclear LLC, PO Box 236, Hancocks Bridge, NJ 08038 Plant Commercial Service Date Salem Generating Station Oct. 13, 1981 UnitNo. 2 Refueling Outage No. 19 Current Inspection Interval Current Inspection Period ISi-Third (3rd)

{Containment IWE/IWL - Second (2n)}

ISi - Third (3rd)

{Containment IWE/IWL - First (l8t)}

Edition and Addenda of Section XI Applicable ISi - 1998 Edition - 2000 Addenda to the inspection plan CISI - (IWE/IWL) - 2004 Edition Date and revision of inspection plan Code Cases used ISi - July 2012, Revision 2 {CISI - October 2010, Revision O}

N-460, N-498-4, N-532-4, N-533-1, N-706, N-722-1 and N-731 CERTIFICATE OF CONFORMANCE I certify that (a) the statements made in this report are correct; (b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI; and ( c) the repair/replacement activities and evaluations supportin the completion of S2RFO 19 conform to the require nts of Section XI.

Signed dley T. Giles I ISI Program Manager Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of New Jersey and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the items described in this Owner's Activity Report, during the period May 8, 2011 to November 8, 2012, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair/replacement activities and evaluation described in this report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Ross Goodwin Commissions NB 14086 A,N,I NJ955 National Board, State, Province, and Endorsements 1 -

FORM OAR-1 OWNER'S ACTIVITY REPORT TABLE 1 ITEMS WITH FLAWS OR RELEVANT CONDITIONS THAT REQUIRED EVALUATION FOR CONTINUED SERVICE Exam Item Item Description Evaluation Description Category Number NIA NIA None NIA TABLE2 ABSTRACT OF REPAIR/REPLACEMENT ACTITIES REQUIRED FOR CONTINUED SERVICE Code Item Description Class 3/8" tubing leak downstream 3

22SW234 3/8" tubing leak downstream 3

of22SW235 l" weld leak upstream of 2SW310 on 90° elbow to 3

flange butt weld 3/8" tubing leak downstream 3

gf2SW186 3/8" tubing to tee weld leak downstream of 2RC3 2

3/8" tubing leak downstream 2

of22BF24 Description of Work Replaced 3/8" SS tubing and fittings Replaced 3/8" SS tubing 1" AL6XN elbow to flange butt weld excavated and re-welded Replaced 3/8" SS tubing and fittings Replaced 3/8" SS tubing and fittings Replaced 3/8" SS tubing and fittings 2

Date Repair/

Completed Replacement Plan Number 07/11/2012 60104374 09/18/2012 60105576 08/30/2012 60105108 11/14/2012 60106944 11/14/2012 60106394 11/20/2012 60107143