L-95-148, Application for Amends to Licenses DPR-67 & NPF-16.Amends Would Extend Allowed Outage Time for Inoperable EDGs
| ML17228B177 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie |
| Issue date: | 06/21/1995 |
| From: | Sager D FLORIDA POWER & LIGHT CO. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| Shared Package | |
| ML17228B178 | List: |
| References | |
| L-95-148, NUDOCS 9506230229 | |
| Download: ML17228B177 (16) | |
Text
RXORXTY (ACCELERATED RZDS PROCESSZNG)
REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:9506230229 DOC.DATE: 95/06/21 NOTARIZED: YES FACIL:50-335 St. Lucie Plant, Unit 1, Florida Power
& Light Co.
50-389 St. Lucie Plant, Unit 2, Florida Power
& Light Co.
AUTH.NAME AUTHOR AFFILIATION SAGER,D.A.
Florida Power
& Light Co.
RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)
SUBJECT:
Application for amends to licenses DPR-67
& NPF-16.Amends would extend allowed outage time for inoperable EDGs.
DISTRIBUTION CODE:
A001D COPIES RECEIVED:LTR I
ENCL
/
SIZE:
TITLE: OR Submittal: General Distribution NOTES:
DOCKET g
05000335 P 05000389 R
0 RECIPIENT ID CODE/NAME PD2-1 LA NORRIS,J COPIES LTTR ENCL 1
1 1
1 RECIPIENT COPIES ID CODE/NAME LTTR ENCL PD2-1 PD 1
1 INTERNAL: ACRS NRR/DE/EMCB NRR/DSSA/SPLB NUDOCS-ABSTRACT EXTERNAL: NOAC 6
6 1
1 1
1 1
1 1
1 XL~QE+gE 01 NRR/DRCH/HICB NRR/DSSA/SRXB OGC/HDS3 NRC PDR 1
1 1
1 1
1 1
0 1
1 D
C U
N NOTE,TO ALL "RZDS" RECZPZENTS:
~
PLEASE HELP US TO REDUCE WASTE!
CONTACT THE DOCUMENT CONTROL
- DESK, ROOM OWFN 5DS (415-2083)
TO ELZMZNATE YOUR NAME FROM DZSTRZBUTZON LZSTS FOR DOCUMENTS YOU DON'T NEEDI TOTAL NUMBER OF COPIES REQUIRED:
LTTR 18 ENCL 17
- ~
H
P.O. Box 128, Ft. Pierce, FL 34954-012$
June 21, 1995 L-95-148 10 CFR 50.90 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.
C.
20555 RE:
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension Pursuant to 10 CFR 50.90, Florida Power ij'ight Company (FPL) requests to amend Facility Operating Licenses DPR-67 and NPF-16 for St.
Lucie Unit 1 and Unit 2, respectively, by incorporating the attached Technical Specifications (TS) revisions.
The proposed amendments will revise the action statements for a
single inoperable Emergency Diesel Generator (EDG),
TS 3.8.1.1.b, to extend the allowed outage time (AOT) from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days, and permit a
10 day AOT to be used once per refueling cycle.
This proposal is a result of a
cooperative study by participating Combustion Engineering Owners Group members which concluded that the proposed AOT extension improves plant operational flexibility while adequately controlling overall plant risk.
It is requested that the proposed amendments, if approved, be issued by February 29, 1996.
Attachment 1 is an evaluation of the proposed changes.
Attachment 2 is the "Determination of No Significant Hazards Consideration."
Attachments 3
and 4 contain copies of the appropriate technical specifications pages marked up to show the proposed changes.
Enclosed with this submittal is a
copy of CE-NPSD-996 "Joint Applications Report for Emergency Diesel Generators AOT Extensionr" May, 1995.
The proposed amendments have been reviewed by the St.
Lucie Facility Review Group and the FPL Company Nuclear Review Board.
In accordance with 10 CFR 50.91 (b)
(1),
copies of the proposed amendments are being forwarded to the State Designee for the State of Florida.
Please contact us if there are any questions about this submittal.
Very truly yours, D. A.
Vice r St.
L ger sident e Plant 950623022'rr 95062i PDR ADOCK 05000335 PDR an FPL Group company
)0
t 1,
1T II
/
i'k
~
qf St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Eme enc Diesel Generator AOT Extension L-95-148 Page 2
DAS/RLD Attachments Enclosure cc:
Stewart D. Ebneter, Regional Administrator, Region II, USNRC.
Senior Resident Inspector, USNRC, St. Lucie Plant.
Mr. W.A. Passetti, Florida Department of Health and Rehabilitative Services.
, ~
~ {
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension L-95-148 Page 3
STATE OF FLORIDA
)
)
COUNTY OF ST.
LUCIE
)
~
D. A. Sager being first duly sworn, deposes and says:
That he is Vice President, St. Lucie Plant for the Nuclear Division of Florida Power
& Light Company, the Licensee herein; That he has executed the foregoing document; that the statements made in this document are true and correct to the best of his knowledge, information and belief, and that he is authorized to execute the document on behalf of said Licensee.
D. A.
ger STATE OF, FLORIDA COUNTY OF The foregoing instrument was acknowledged before me this Z l day of ~~, 19~5 by D.A. Sager, who is personally known to me and who did take an oath.
-S1 Name of Notary Public My Commission expires / / F Commission No. M 9~ ~~ 7-k eeoc>>
- eS e~
e KAREN NEST MYCOMMISSION {F CCSS99 Apl918, { >o OO((OFOTi((((~TV: r KARENVIEST ee, 4:0- W COMMISSIONfCC859926 EXPIRES April 18, 1998
$0((OEOTI{RUTROY FAO{${VRANOF,BC.
I t
I I
~
4'
~
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension ATTACHMENT 1 EVALUATION OF PROPOSED TS CHANGES
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension L-95-148 Attachment 1
Page 1 of 4 EVALUATION OF PROPOSED TS CHANGES Introduction Florida Power and Light Company (FPL) requests that Appendix A of Facility Operating License DPR-67 for St. Lucie Unit 1 (PSL1) and NPF-16 for St. Lucie Unit 2 (PSL2) be revised to extend the action completion/allowed outage time (AOT) for a
single inoperable Emergency Diesel Generator (EDG) from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days.
In
- addition, a
one time AOT of 10 days would be permitted per refueling cycle.
The purpose of the AOT extension is to enhance overall plant safety by averting potential unscheduled plant shutdowns, and by providing for increased flexibilityin scheduling and performing maintenance and surveillance activities.
The proposed AOT extension is based on the results of a cooperative study performed by participating members of the Combustion Engineering Owners Group (CEOG).
The study included an integrated review and assessment of plant operations, deterministic design basis
- factors, and overall plant risk using Probability Safety Assessment (PSA) techniques.
Descri tion of Pro osed PSL1 and PSL2 TS Chan es The following proposed changes apply to both PSL1 and PSL2:
TS 3.8.1.1.b:
When a single EDG is discovered inoperable, the AOT to restore that EDG to OPERABLE status will be revised from the current 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to "7days."
A footnote will be added to this proposed AOT which provides for an extension, on a
once per refueling cycle frequency, "to a maximum of 10 days from inMal discovery offailure to meet the LCO."
2.
Bases a
e B
3 4
8-1 will be revised to include summary
~
statements regarding the bases for the AOTs.
Back round Each St.
Lucie Unit employs two EDG sets dedicated to provide onsite emergency alternating current (AC) power to essential safety systems in the event of a loss of offsite power.
Each EDG has a
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension L-95-148 Attachment'1 Page 2 of 4 set arrangement consisting of two diesel engines in tandem with a single generator in the middle.
The EDG sets for PSL1 and PSL2 are similar, with minor differences in the engine lubricating oil systems and generator ratings.
The St. Lucie Plant Emergency Diesel Generator Reliability Program is designed to assure that EDG reliability remains greater than or equal to the target reliability associated with 10 CFR 50.63, the "Station Blackout (SBO)" rule.
The program provides for monitoring and evaluating EDG performance and reliability, implementing remedial actions if one or more established reliability "trigger values" are
- exceeded, determining the root-cause and corrective actions for individual EDG failures, and continuous monitoring of EDG unavailability.
In addition, FPL is committed to implementing the provisions of the Maintenance Rule (10 CFR 50.61),
as it applies to the EDGs and support systems, pursuant to Generic Letter 94-01, "Removal of Accelerated Testing and Special Reporting Requirements for Emergency Diesel Generators."
Limiting Condition for Operation (LCO) 3.8.1.1, "A.C. Sources,"
requires two separate and independent EDGs to be OPERABLE in MODES 1,
2, 3,
and 4.
This redundancy ensures that at least one of the onsite AC power sources will be operable during accident conditions, coincident with an assumed loss of offsite power and single failure of the other onsite AC source.
If a single EDG becomes inoperable during the applicable
- modes, ACTION b of LCO 3.8.1.1 requires the inoperable EDG to be restored to operable status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />; otherwise, the plant must transition to Hot Standby within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and to Cold Shutdown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AOT for a single inoperable EDG is consistent with guidance provided in USNRC Regulatory Guide 1.93, "Availabilityof Electric Power Sources,"
- December, 1974.
Bases for the Pro osed Chan es FPL participated in a
CEOG effort to perform an integrated assessment of the impact of extending the AOT for an inoperable EDG from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days, with an additional provision for a 10 day AOT limited to a
once per refueling cycle frequency.
The assessment considered the impact of the AOT extension on deterministic factors associated with applicable plant design
- bases, and a probabilistic safety assessment of risks involved with
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension L 95 148 Attachment 1
Page 3 of 4 applicable plant operations.
The considerations, assumptions, methodologies, and detailed results of this study are reported in CE NPSD-996, "Joint Applications Report for Emergency Diesel Generators AOT Extension," Final Report CEOG Task 836, prepared for the CE Owners
- Group, May,
- 1995, which is enclosed with this submittal.
Plant specific calculations to assess the risk impact of the AOT extension on PSL1 and PSL2 were performed by FPL using current PSA models and methods that were initially developed in response to Generic Letter 88-20, "Individual Plant Examination for Severe Accident Vulnerabilities."
CE NPSD-996 contains the results of FPL's plant specific
- analyses, as well as generic information relevant to the proposed AOT extension that is applicable to both St.
Lucie Units.
The enclosed
- report, therefore, forms the justification/basis for the proposed license amendments.
The analyses for PSLl and PSL2 indicate that continued plant operation with a single EDG out of service will result in a small increase in "at power risk;" however, when the full scope of plant risk is considered, the risk incurred by extending the AOT for the performance of maintenance activities would be offset by risk benefits associated with averting unnecessary plant transitions to Cold Shutdown and/or by reducing risk during shutdown operations.
In addition, the proposed AOT extension for the EDG is evaluated as having a negligible impact on the large early radiological release probability for CE Pressurized Water Reactors in the event of a design basis accident.
The evaluation reported in CE NPSD-996 recognizes that the precise impact of the proposed AOT will depend upon the specific circumstances of entry into the LCO Action statement, but concludes that the extension provides plant operational flexibilitywhile adequately controlling overall plant risk.
Conclusion The risk contributions associated with extending the AOT for a
single inoperable EDG from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days with a once per cycle 10 day AOT have been quantitatively evaluated using the current plant specific Probabilistic Safety Assessment for PSL1 and PSL2.
The analyses show that the small increase in the calculated "at power risk" can be offset by averting the risk associated with an
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension L-95-148 Attachment 1
Page 4 of 4 unnecessary plant transition to Cold Shutdown, and/or reduced risk during shutdown operations that can result from improved flexibility in scheduling and performing surveillance and maintenance activities.
The integrated assessment reported in CE NPSD-996 generally conforms to guidance provided in NUREG/CR-6141, "Handbook of Methods for Risk Based Analyses of Technical Specifications,"
- December, 1994.
Relative to the average Core Damage Frequency calculated for the appropriate severe accidents, NUREG/CR-6141
- states, "A risk-based AOT assures that the single event and yearly AOT risk contributions are acceptable."
FPL believes the proposed AOT qualifies as a beneficial risk-based AOT, and that the proposed amendment is acceptable.
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension ATTACHMENT 2 DETERMINATION OF NO SIGNIFICANT HAZARDS CONSIDERATION
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension L-95-148 Attachment 2
Page 1 of 2 DETERMINATION OF NO SIGNIFICANT HAZARDS CONSIDERATION Pursuant to 10CFR50.92, a determination may be made that a proposed license amendment involves no significant hazards consideration if operation of the facility in accordance with the proposed amendment would not:
(1) involve a significant increase in the probability or consequences of an accident previously evaluated; or (2) create the possibility of a
new or different kind of accident from any accident previously evaluated; or (3) involve a
significant reduction in a margin of safety.
Each standard is discussed as follows:
(1)
Operation of the facility in accordance with the proposed amendment would not involve a
significant increase in the probability or consequences of an accident previously evaluated.
The proposed amendments for St. Lucie Unit 1 and Unit 2 will extend the action completion/allowed outage time (AOT) for a
single inoperable Emergency Diesel Generator (EDG) from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7
days, with provisions for a 10 day AOT once per refueling cycle.
The EDGs are designed as backup AC power sources for essential safety systems in the event of a loss of offsite power.
As such, the EDGs are not accident initiators, and an extended AOT to restore operability of an inoperable diesel generator would not increase the probability of occurrence of accidents previously analyzed.
The proposed technical specification revisions involve the AOT for a
single inoperable
- EDG, and do not change the conditions, operating configuration, or minimum amount of operating equipment assumed in the plant safety analyses for accident mitigation.
In
- addition, a Probability Safety Assessment (PSA) was performed to quantitatively assess the risk impact of the proposed amendment.
The impact on the early radiological release probability for design basis events was also evaluated.
It was concluded that the risk contribution from this proposed AOT is very small, and that the impact will be negligible.
Therefore, operation of either facility in accordance with its proposed amendment would not involve a significant increase in the probability or consequences of an accident previously evaluated.
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension L-95-148 Attachment 2
Page 2 of 2 (2)
Operation of the facility in accordance with the proposed amendment would not create the possibility of a new or different kind of accident from any accident previously evaluated.
The proposed amendments will not change the physical plant or the modes of plant operation defined in either Facility License.
The changes do not involve the addition or modification of equipment, nor do they alter the design of plant systems.
Therefore, operation of either facility in accordance with its proposed amendment would not create the possibility of a new or different kind of accident from any accident previously evaluated.
(3)
Operation of the facility in accordance with the proposed amendment would not involve a significant reduction in a margin of safety.
The proposed amendments are designed to improve EDG reliability by providing flexibility in the scheduling and performance of preventive and corrective maintenance activities.
The surveillance intervals or the operability requirements are not changed by the proposal; only the AOT for a
single inoperable EDG will be extended.
The proposed changes do not alter the basis for any technical specification that is related to the establishment of, or the maintenance of, a
nuclear safety margin.
- Moreover, an integrated assessment of the risk impact of extending the AOT for a single inoperable EDG has determined that the risk contribution is very small and can be offset by improvements in EDG reliability.
Therefore, operation of either facility in accordance with its proposed amendment would not involve a significant reduction in a margin of safety.
Based on the above discussion and the supporting Evaluation of Technical Specification
- changes, FPL has determined that the proposed license amendments involve no significant hazards consideration.
St. Lucie Unit 1 and Unit 2 Docket Nos.
50-335 and 50-389 Proposed License Amendments Emer enc Diesel Generator AOT Extension ATTACHMENT 3 ST ~ LUCIE UNIT 1 MARKED-UP TECHNICAL SPECIFICATION PAGES Page 3/4 8-1 Page B 3/4 8-1
'jj',"".'.PArGES".!!!3/4',',g8',:,.'3P'~j,"AND)',B';':i':::.3/'4 im'.:8;-;:'~)j
~~));:,CONTAIN),,"';.:::,::,'CHANGES::;:.':,;:.::,:.:,jPREVXOUSIiY:::"::,:~)
- )>>SUBMITTED'-;;
- .BY~jFPL"';:L'ETHER~L'-",,.9,5;,,:;j'ji
-;'!::087'"'::ii';,(:4'/3/,;:,9,'5,),'j"'Pr,,UrRSUANr TP,,:::;.,":;:.TO'$~::,'GL')) )
,;:;:::;::;;:,':93:.;.-":05.':.,';::)AND;,,::;::,!NUrREG:;!.';::,-':,::;13.6,6::,:.:;::.'j::;TrHESE;':m~:,;
'"')',,'CHANGES"""'i'gA'BE""""!re"'i5'XNDX'CA'TEDjill)i>j>BY<!4'i VERTXCAL )LXNES XN> THE HARGINsj
~g'AND$ARE'....,PENDXNG':,:::,,::NrRC:~A'PPROVr,ArL":~ 'j';,