e-P. O. BOX 14000, JUNO B E ACH, F L 33406 s

.:o c:

dTE'~.2.u,A E

4 FLORIDA POWER & l.lGHT COMPANY p}

q October 29, 1982 L-82-469 Mr. James P. O'Reilly Regional Administrator, Regicn II U. S. Nuclear Regulatory Commission 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

Re: Turkey Point Units 3 & 4 Docket Nos. 50-250, 50-251 IE Inspection Report 82-29 Florida Power & Light Company has reviewed the subject inspection report and a response is attached.

There is no proprietary information in the report.

Very truly yours, F.voert E. Uhrig Vice President Advanced Systems & Technology REU/PLP/js Attachment cc: Harold F. Reis, Esquire r

8212090503 821116 PDR ADOCK 05000250 G

PDR PEOPLE.. SERVING PEOPLE

ATTACHMENT RE:

TURKEY POINT UNITS 3 AND 4 DOCKET NOS. 50-250, 50-251 IE INSPECTION REPORT 82-29 FINDING:

Technical Speci fication 6.8.1 requi res, i n pa rt, that written procedures be impl emented.

Procedure A. P. 0103.4 speci fies the method fo r placing and remo vi ng tags for administrative control of equipment.

Cont ra ry to t he above, s teps 4.5, 8.5.2 a nd 8.6 of Admi ni strative Procedure 0103.4, "In Plant Equipment Clearance Orders" were not f ully impl emented for equipment clearance order (EC0) 7-155 in effect from 7/19/82 to 7/23/82.

A danger tag was improperly pl aced, the EC0 form wa s not completed, and the clearance wa s not properly removed f rom val ve MOV-878B i n the sa fety i njection s ys t em.

RESPO NS E :

(1-1)

FPL concurs with the finding.

(1-2)

The reason for this finding was that the procedure fo r i n-pl ant clearances did not clearly define where' tags were to be placed nor did the procedure include a wo rka ble mechani sm fo r tempo rary rel eases of clea rances.

(1-3)

As corrective action, the danger tag was removed from MOV-8788 and the operator wa s counselled on the need fo r

[.

proper completion of the EC0 form.

l (1-4)

In order to prevent recurrence, Admi nistrative Procedure l

0103.4, In-Plant Equipment Clearance Orders has been revi sed to clarify the policy fo r tagging M0V's and also to include provisions for temporary clearance releases, j

(1-5)

Full compli ance wa s achieved on September 30, 1982.