L-81-321, Interim Deficiency Rept Re Omission of Locking Rings Slots on Modutronic Controller/Allen Bradley Selector Switches, Initially Reported 810624.Deficiency Being Evaluated.Addl Info Will Be Provided by 810803

From kanterella
(Redirected from L-81-321)
Jump to navigation Jump to search
Interim Deficiency Rept Re Omission of Locking Rings Slots on Modutronic Controller/Allen Bradley Selector Switches, Initially Reported 810624.Deficiency Being Evaluated.Addl Info Will Be Provided by 810803
ML20009H565
Person / Time
Site: Saint Lucie 
Issue date: 07/27/1981
From: Robert E. Uhrig
FLORIDA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, L-81-321, NUDOCS 8108100248
Download: ML20009H565 (1)


Text

Y a

P.O. DOX 529100 MI AMI, F L 33152 t ; m g(; R E 0 ;.' N -

  • ;,'l% ' 'R0,

a;, n T :., d...W

. h '9/O. g ORIDA POWER & LIGHT C FL Pl2. I D

'31 r'pr, 3 July 27, 1981 L-81-321 Mr. James P. O'Reilly, Director, Region II Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

Re: St. Lucie Unit 2 Docket No. 50-389 Modutronic Controller / Allen Bradley Selector Switches On June 24, 1981, Florida Power & Light Company (FPL) notified the Region II Office of Inspection and Enforcement of a potential 10CFR50.55(e) deficiency regarding the mounting of Modutronic Con-troller / Allen Bradley Selector Switches. During fabrication of the boxes containing the control switches, the slot to hold the locking ring was omitted. As a result the locking rings were left off.

In this condition the switch housing rotates when the switch is turned which could result in broken, damaged, or shorted connections. FPL is evaluating this deficiency and we expect to provide you, additional information by August 3,~ 1981.

Very truly yours, b-L O

g ert E. Uhrig g

lg Vice President-l Advanced Systems & Technology E.. /iUG O[68Im T REU/TCG/bs 2

Mb O

/

4 cc: Director of Inspection and Enforcement y

U. S. Nuclear Regulatory Connission G,-

g Wahsington, D. C.

20555 Harold F. Reis, Esquire

[b S.fo 8108100248 810727 PDR ADOCK 05000389 b

PEOPLE.. SERVING PEOPLE

_ -,, _ - ~ _.

,,