FPL April 18, 2008 L-2008-089 10 CFR 50.36 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555-0001 Re:
Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Industrial Wastewater Permit Number FLOO01562 Minor Modification Request Notification In accordance with Section 3.2.3 of the Turkey Point Units 3 and 4 Environmental Protection Plan (Appendix B of Facility Operating Licenses DPR-31 and DPR-41), enclosed is a copy of the request to revise the Industrial Wastewater Permit Number FLO0001562. The minor permit modification is requested to reflect the proposed plan to add about100 Megawatts (MW) of electrical generation to each of the Turkey Point nuclear units. The net power output of both Units 3 and 4 will be increased from about 700 MW to 804 MW.
Should there be any questions, please contact us.
WillianrJe.ffersofr; J r.
Vice President Turkey Point Nuclear Plant Enclosure cc:
Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant an FPL Group company CD/f
ENCLOSURE TO L-2008-089
4 April 18, 2008 Marc Harris, P.E.
Supervisor, Power Plant NPDES Permitting Industrial Wastewater Section Florida Department of Environmental Protection 2600 Blair Stone Road, MS 3545 Tallahassee, Florida 32399-2400 RE:
FPL - Turkey Point Plant State of Florida Industrial Wastewater Facility Permit No. FL001562 Request for Minor Revision Due to Minor Modification of Facility
Dear Mr. Harris:
Attached please find the following items to support ae request for a minor revision to the Florida Power & Light Company (FPL) Turkey Point Plant State of Florida Industrial Wastewater Facility Permit No. FL0001562:.
- 1)
Four (4) signed, sealed copies of FDEP Form 62-620.910(9), "Application for a Minor Revision to a Wastewater Facility or Activity Permit" including Attachment-to Request Minor Modification.
- 2)
An FPL Check payable to the Florida Department of Environmental protection for the $250 application fee.
If you have any questions or need additional information on this matter, please contact Ron Hix at (561) 691-7641.
- William J erson
- Vice President - Turkey Point Nuclear Plant Enclosures cc:
USNRC Document Control Desk FDEP - SE District - Tim Powell an FPL Group company
APPLICATION FOR A MINOR REVISION TO SA WASTEWATER FACILITY OR ACTIVITY
____PERMIT
- 1. Instructions
- a. In accordance with Rule 62-620.325, F.A.C., this form must be submitted to the appropriate Department district office or approved local program when requests for minor revisions to a permit or minor modifications to a facility are made by a permittee, except for transfer of a permit to a new permittee and addition of a major user of reclaimed water to a Part III reuse system. Application for transfer of a permit to a new permittee shall be made on DEP Form 62-620.910(11). Application for addition of a major user of reclaimed water shall be made on DEP Form 62-610.300(4)(a) 1.
- b. Each applicable item must be completed in full in order to avoid delay in processing of this form. Where attached sheets or other technical documentation are provided, indicate appropriate cross-references.
- c. Three (3) copies of this application with supporting documentation shall be submitted with this form.
- d. All information is to be typed or printed in ink. Dates are to be entered in MM/DD/YR format.
- e. This application and attachments shall be signed in accordance with Rule 62-620.305, F.A.C. Also, as applicable, this application and all attachments shall be signed and sealed by a professional engineer registered in Florida in accordance with Rule 62-620.310, F.A.C.
- 2. Facility Information
- a. Permit Number:
FL0001562
- b. Facility Identification Number:
- c. Project/Facility Name:
Florida Power & Light Company Turkey Point Plant Unit 3 & 4
- d. Contact Name:
William Jefferson Number and Street:
9760 S.W. 344 Street City/State/Zip Code:
Florida City, FL 33035 Telephone 305-246-6113
- 3. Type of Revision LI Correct Typographical Errors' - Submit one copy of each page of the permit showing revisions being requested.
[
Change Improvement Schedule' - Provide a description of the improvement, a list of the dates to be revised, and a reason for the proposed change in each date.
Li Change Expiration Date of Permit' - Provide the current and proposed expiration dates for the permit and the reasons for the proposed change.
El Change Staffing Requirements2 - Describe the proposed change and submit justification for the change in accordance with Chapter 62-699, F.A.C.
A processing fee is not required.
DEP Form 62-620 910(9) 2A processing fee is required with the application Effective October 23. 2000 in accordance with Rule 62-4.050. F.A.C.
El Change Monitoring and Reporting Requirements2 - Describe the proposed change and submit justification for the change in accordance with Chapter 62-601, F.A.C.
El Modify Approved Pretreatment Program1 - Describe the proposed modification and provide the information required by Rule 62-625.540, F.A.C.
LI Delete Point Source Outfall1 - identify the. outfall and explain why the outfall is being eliminated.
LI Modify or Expand Approved Residuals Land Application Sites2-Attach a new or updated Agricultural Use or Dedicated Site Plan as required by Chapter 62-640, F.A.C.
[
Minor Modification to the-Facility 2 - Provide a description of the proposed modification. If applicable, attach any reports, plans, and specifications which have been developed to implement this modification.
F-Other2 - Provide appropriate documentation. Describe.
- 4. Certifications
- a. Applicant or Authorized Representative I certify under penalty of law that I have personally examined and am familiar with the information submitted in this application and all attachments and that, based on my inquiry of persons immediately responsible for
- obtaining the information contained in the application, I believe that the information is true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the
, ossibl fnan mrsjmt (Si"re o A
- cantj uthorized Representative 3)
(Date)
Name (please type) William Jefferson Company Name Florida Power & Light Company Title Plant Vice President Company Address:
9760 S.W. 344 Street Phone:.
305-246-6113 City/State/Zip Code:
Florida City, FL 33035
- b. Professional Engineer Registered in Florida I certify that the engineering features of this project have been (designed) (examined) by me and found to conform to engineering principles applicable to such projects. In my professional judgement, this facility, when properly constructed, operated, and maintained, will comply with all applicable statutes of the State of Florida and rules of the Department.
Name (please type):
Harold A. Frediani, Jr.
Florida Registration Number:
36394 Company Name:
Golder Associates Inc, Cert No. 1670 Company Address:
3730 Chamblee Tucker Road City/State/Zip Code:
Atlanta, GA 30341 Phone Number:
770-492-8218
._3._._
(Seal,'Signaturet JQttej,apP~ Regist-rion Numer) 11
- e.
STATe 01 0R
'If signed by the authorized representative,.
2
'",'C 1 J/-
I ti DEP Form 62-620.910(9) attach a letter of authorization in accordance i
Effective October 23, 2000 Rule 62-620.305, F.A.C.
Attachment to Request for Minor Modification I
Introduction FPL proposes plans to add about 200 MW. of electrical generation resources to its system in order to continue to provide reliable, safe, and cost-effective service to its customers.
This increase. Will be accomplished by the Turkey Point Uprate Project which is an innovative application of technological advancements and efficiencies that will increase the net power output of both Unit 3 and Unit 4 from about 700 Megawatts (MW) to 804 MW. The extra power output will result from improving the performance of the steam turbine and from using more nuclear fuel which will result in increased thermal MWs produced in the reactor core. The additional heat will raise the temperature exchange between the primary and secondary systems, creating more steam for turning the turbines.
The Project consists of upgrades to each unit. The upgrades will include refurbishment and improvement activities to the steam turbine-electric generator, electrical systems, and cooling systems. These refurbishment and improvement activities will primarily occur during outages between 2010 and 2012. Certain improvements will also be made while the units are operating. All refurbishment and improvement activities will occur within the building and structures associated with existing Units 3 and 4.
II Heat Dissipation System Turkey Point Units 3 and 4 use cooling water from a closed-cycle cooling canal system to remove heat from the main (turbine) condensers, and to remove heat from other auxiliary equipment. The additional heat from the uprate will result in an increase in the hot water temperature leaving the nuclear units. The existing cooling canal system can accommodate the increase in heat load. The maximum predicted increase in hot water temperature entering the cooling canal system is about 2.5 deg F, from 106.1 to 108.6 deg F*. The associated maximum increase in cold water temperature returning to the units is about 0.9 deg F, from 91.9 to 92.8 deg F.
III Proposed Permit Conditions The Turkey Point cooling canal system is a permitted wastewater treatment facility; therefore, state and federal water quality standards do not apply within it. The NPDES permit is a no-discharge permit and Will remain so; therefore, the Uprate Project will have no impact on discharges to surface water. No changes in permit conditions are required. A revisionto the facility's State IWW Permit is required to reflect the increase in the megawatts for Units 3 and 4 from 700 MW to 804 MW as a result of the uprate.