L-2005-034, Cycle 15 Core Operating Limits Report

From kanterella
(Redirected from L-2005-034)
Jump to navigation Jump to search
Cycle 15 Core Operating Limits Report
ML050550086
Person / Time
Site: Saint Lucie 
Issue date: 02/11/2005
From: Jefferson W
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-2005-034
Download: ML050550086 (19)


Text

FPL Florida Power& Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 February 11, 2005 L-2005-034 10 CFR 50.36 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Re:

St. Lucie Unit 2 Docket No. 50-389 Cycle 15 Core Operating Limits Report Pursuant to St. Lucie Unit 2 Technical Specification (TS) 6.9.1.1 1.d, Florida Power & Light Company (FPL) is submitting the Core Operating Limits Report (COLR) for operating cycle 15.

Technical Specification 6.9.1.11.d requires that the COLR, including any mid-cycle revisions or supplements, be provided to the NRC upon issuance for each reload cycle.

Accordingly, enclosed is a copy of the St. Lucie Unit 2, Cycle 15 Core Operating Limits Report, Revision 2.

Please contact us if there are any questions regarding this submittal.

William Xeffersc Vice President St. Lucie Plant WJ/spt Attachment fAcOI an FPL Group company

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment ST. LUCIE UNIT 2, CYCLE 15 CORE OPERATING LIMITS REPORT Revision 2 lS ared By V1/ i/ 0 !;g er 1/f//ieB Verified By vsl/os-St. Lucle UnIt 2 Cycle 15 COLR Rev 2 Page 1 oilS St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 1 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment Table of Contents Description 1.0 Introduction Page 3

2.0 Core Operating Umits 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 Moderator Temperature Coefficient CEA Position - Misalignment > 15 inches Regulating CEA Insertion Limits Linear Heat Rate TOTAL INTEGRATED RADIAL PEAKING FACTOR DNB Parameters - AXIAL SHAPE INDEX Refueling Operations - Boron Concentration SHUTDOWN MARGIN - Ta.,, Greater Than 200 0F SHUTDOWN MARGIN - T, Less Than or Equal To 200 cF 4

4 4

4 5

5 5

5 5

14 3.0 List of Approved Methods Table 3.2-2 Table 3.2-3 Fig 3.1-la Fig 3.1 -2 Fig 3.2-1 Fig 3.2-2 Fig 3.2-3 Fig 3.2-4 List of Tables and Figures Title DNB Margin Limits W(z) Factors as a Function of Core Height Allowable Time To Realign CEA vs. Initial FT CEA Insertion Umits vs. THERMAL POWER Allowable Peak Linear Heat Rate vs. Burnup AXIAL SHAPE INDEX vs. Maximum Allowable Power Level Allowable Combinations of THERMAL POWER and FrT AXIAL SHAPE INDEX Operating Limits vs. THERMAL POWER Page 6

7 8

9 10 11 12 13 St. Lucle Unit 2 Cycle 15 COLR Rev 2 Page 2 of 18 St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 2 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment

1.0 INTRODUCTION

This Core Operating Limits Report (COLR) describes the cycle-specific parameter limits for operation of St. Lucie Unit 2. It contains the limits for the following as provided in Section 2.

Moderator Temperature Coefficient CEA Position - Misalignment > 15 Inches Regulating CEA Insertion Limits Linear Heat Rate TOTAL INTEGRATED RADIAL PEAKING FACTOR-FT DNB Parameter Refueling Operations - Boron Concentration SHUTDOWN MARGIN - Tavg Greater Than 200 OF SHUTDOWN MARGIN - T.v, Less Than or Equal To 200 OF This report also contains the necessary figures which give the limits for the above listed parameters.

Terms appearing in capitalized type are DEFINED TERMS as defined in Section 1.0 of the Technical Specifications.

This report is prepared in accordance with the requirements of Technical Specification 6.9.1.11.

SL Lucle UnIt 2 Cycle 15 COLR Rev 2 Page 3 of 18 St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 3 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment 2.0 CORE OPERATING LIMITS 2.1 Moderator Temperature Coefficient (TS 3.1.1.4)

The moderator temperature coefficient (MTC) shall be less negative than -32 pcm/OF at RATED THERMAL POWER.

2.2 CEA Position - Misalignment > 15 Inches (TS 3.1.3.1)

The time constraints for full power operation with one full-length CEA misaligned from any other CEA in its group by more than 15 inches are shown in Figure 3.1 -la.

2.3 Regulating CEA Insertion Limits (TS 3.1.3.6)

The regulating CEA groups shall be limited to the withdrawal sequence and to the insertion limits shown on Figure 3.1-2, with CEA insertion between the Long Term Steady State Insertion Limits and the Power Dependent Insertion Limits restricted to:

a.

Less than or equal to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> per 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> interval,

b.

Less than or equal to 5 Effective Full Power Days per 30 Effective Full Power Days, and

c.

Less than or equal to 14 Effective Full Power Days per calendar year.

2.4 Linear Heat Rate (TS 3.2.1)

The linear heat rate shall not exceed the limits shown on Figure 3.2-1.

The AXIAL SHAPE INDEX power dependent control limits are shown on Figure 3.2-2.

Excore Detector Monitoring System During operation, with the linear heat rate (LHR) being monitored by the Excore Detector Monitoring System, the AXIAL SHAPE INDEX shall be maintained within the limits of Figure 3.2-2.

Cycle specific W(z) curves to be used in the linear heat rate verification, to account for power distribution transients, are shown in Table 3.2-3 as function of core height for various cycle bumups.

For other cycle burnups, W(z) values may be interpolated or extrapolated as needed.

If the margin to the linear heat rate has decreased as determined from the last two flux maps, then the linear heat rate must be increased by an appropriate penalty.

A value of 2% is chosen as the standard penalty.

Linear heat rate margin St._Lcle U 2 Cycle 15 CLR R_ 2 Pag_

St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 4of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment decreases that are predicted to be greater than 2% per 31 Effective Full Power Days require that penalty factors of greater than 2% be used to increase the measured linear heat rate LHRM(z). The Incremental penalty factors (in excess of 2% margin decrease) are included in the W(z) function of Table 3.2-3.

Incore Detector Monitorina System During operation, with the linear heat rate being monitored by the Incore Detector Monitoring System, the Local Power Density alarm setpoints shall be adjusted to less than or equal to the limits shown on Figure 3.2-1.

2.5 TOTAL INTEGRATED RADIAL PEAKING FACTOR - FrI (TS 3.2.3)

The calculated value of FT shall be limited to < 1.70.

The power dependent FT limits are shown on Figure 3.2-3.

2.6 DNB Parameters (TS 3.2.5)

The following DNB-related parameters shall be maintained within the limits shown on Table 3.2-2:

a. Cold Leg Temperature
b. Pressurizer Pressure
c.

Reactor Coolant System Flow rate

d.

AXIAL SHAPE INDEX 2.7 Refuelina Operations - Boron Concentration (TS 3.9.1)

With the reactor vessel head closure bolts less than fully tensioned or with the head removed, the boron concentration of all filled portions of the Reactor Coolant System and the refueling canal shall be maintained uniform and sufficient to ensure that the more restrictive of the following reactivity conditions is met:

a.

Either a Kef of 0.95 or less, or

b.

A boron concentration of greater than or equal to 1720 ppm.

2.8 SHUTDOWN MARGIN - T Greater Than 200 OF (TS 3.1.1.1)

The SHUTDOWN MARGIN shall be greater than or equal to 3600 pcm.

2.9 SHUTDOWN MARGIN - T., Less Than or Equal To 200 OF (TS 3.1.1.2)

The SHUTDOWN MARGIN shall be greater than or equal to 3000 pcm.

St Lucle Unit 2 Cycle 15 COLR Rev 2 Pages5 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment Table 3.2-2 DNB MARGIN LIMITS PARAMETER FOUR REACTOR COOLANT PUMPS OPERATING Cold Leg Temperature (narrow Range)

Pressurizer Pressure*

Reactor Coolant Flow Rate AXIAL SHAPE INDEX 5350F** 5 T

  • 5490P 2225 psia 5 Ppzm
  • 2350 psia**

2 335,000 gpm Within the limits specified in Figure 3.2-4 Limit not applicable during either a THERMAL POWER ramp increase in excess of 5% of RATED THERMAL POWER or a THERMAL POWER step increase of greater than 10%

of RATED THERMAL POWER.

Applicable only if power level 2 70% of RATED THERMAL POWER.

St

... -u l

-n - -------- 15 C-I Rev---

2--a-6 18 St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 6 of IS

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment COLR Table 3.2-3 W(z) Factors as a Function of Core Height Core Height 100 EFPH 2000 EFPH SOD0 EFPH 8000 EFPH 10000 EFPH

()

(130 MWD/MTU)

(2598 MWD/ TU)

(6494 MWDIMTU)

(10391 MWDlMTU) (12988 MWDIMTU) c1.59*

1.000 1.000 1.000 1.000 1.000 1.75 1.288 1.266 1.240 1.303 1.340 1.91 1279 1.255 1.231 1.292 1.321 2.07 1 270 1.246 1.221 1.280 1.302 2.23 1.262 1.236 1.211 1.268 1.280 2.39 1.253 1.226 1.204 1.255 1.259 2.55 1.243 1.217 1.197 1.241 1.245 2.70 1.234 1.209 1.189 1.227 1.231 2.86 1.226 1.206 1.184 1.217 1.215 3.02 1.219 1.203 1.181 1.211 1.210 3.18 1.213 1.199 1.180 1 206 1.207 3.34 1.206 1.194 1.177 1.201 1.202 3.50 1.199 1.188 1.175 1.197 1.197 3.66 1.193 1.182 1.171 1.192 1.191 3.82 1.188 1.175 1.167 1.187 1.186 3.98 1.182 1.167 1.163 1.181 1.183 4.14 1.176 1.160 1.157 1.175 1.181 4.30 1.169 1.154 1.152 1.167 1.177 4.45 1.162 1.148 1.145 1.160 1.173 4.61 1.153 1.142 1.139 1.152 1.168 4.77 1.145 1.135 1.132 1.144 1.163 4.93 1.136 1.128 1.124 1.135 1.157 5.09 1.127 1.121 1.117 1.126 1.150 5.25 1.118 1.113 1.109 1.117 1.144 5Al 1.108 1.106 1.103 1.110 1.142 5.57 1.101 1.102 1.102 1.109 1.148 5.73 1.100 1.102 1.102 1.115 1.161 5.89 1.103 1.104 1.108 1.130 1.177 6.05 1.105 1.108 1.122 1.146 1.190 6.20 1.111 1.120 1.137 1.162 1.203 6.36 1.122 1.137 1.150 1.177 1.215 6.52 1.136 1.152 1.163 1.191 1.226 6.68 1.150 1.167 1.176 1.205 1.237 6.84 1.163 1.182 1.190 1217 1.246 7.00 1.175 1.196 1.204 1.228 1.255 7.16 1.187 1.210 1.218 1.239 1.262 7.32 1.198 1.223 1.231 1.248 1.267 7.48 1.209 1.235 1.242 1.255 1.270 7.64 1.218 1.246 1.253 1.261 1.272 7.80 1.226 1.255 1.263 1.265 1.272 7.95 1.233 1.264 1.272 1.267 1.270 8.11 1.240 1.271 1.279 1.268 1.269 8.27 1.246 1.277 1.287 1.268 1.270 8.43 1.252 1.282 1.296 1.271 1.273 8.59 1.260 1.285 1.309 1.279 1.282 8.75 1.271 1.292 1.331 1.292 1.299 8.91 1.283 1.313 1.356 1.309 1.316 9.07 1.297 1.337 1.381 1.328 1.332 9.23 1.314 1.363 1.404 1.346 1.347 9.39 1.337 1.388 1.425 1.365 1.363 9.54 1.361 1.412 1

1.446 1.389 1.382 9.70 1.382 1.434 1.467 1.413 1.403

>9.86 1.000 1.000 1.000 1.000 1.000

'Top and Bottom 15% are excluded.

St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 7 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment

1.

I r iri T2 I r I

I II I

I II rIg r

r I,

  1. 11J.9L LJ,8888 JIL JL8 J

8I18J J~ll

  • ii*l9 j

l.l9,gg

  1. I li*gl a-, I ;

j J

L.ll-li

.LL I

IJLIJ L..IJ

-JL.9ILJILJ1I.JLI..LLIJ l~laIllIll h~l Ig~l gi. igaga sug 111 19181gil gggg1 I IgI 1.70 g9~8-1,i Uu.[rr.~s.ii1~ L..:4I~J:I,

gilg. I.a gLgIJ L1-1IJ.

lULrUJLU.l8.LI.I I L: I LIJ.J t-u L.J ILI1.81L8.4... 0-LU.J l-AIil&i 4

l 9i;riIi1W-l-,Itl 1--l9-l g.lr--iag eg-,I

' 9-4 gggg4 Iggg ggg Iggg l gmag 1 19-1-81 ggg I I4I

.I g

I Igg 111 I gaig] I gg 15 68 gall gag gggg I giI aa Ills ofll III 191118fill9I1I

'I1911111111111Jill C

gT r iTr rrlT.tg r ij ggI r r r Trg T rgl r:-,ag r

T1 lr: IrA rrgi 0

A

'i L L.IIL4ILI LIJI-. ~

I IL19 I.L-J Liii

-l..JL

-.JL iLJA4Il L

(1)

III I.-.lM tMI 1.4 LIJ L

41q-41A J, *'u 1.1 11.9r

.44.U.+.I9Il4.1411.

19199111189 il I

Ijla 911111111199IIiIlIIl

aIir, lnrrtrl r-lrrl IFr,199!

rlrl rl~r-1]

TI,,

, 1. 2 il blrr

_.C.

i u Fla. lir rii 1-il 0

"I99111:119 1 1999 ll mgl 99199 91111999999Ill~l1' I I199]II

]1111IL IIIll l J~I 91199[I~999l g-i Fr,r

-rrI '

rI.H rg,%4, 8,lralr-i Tn irs.-

ral aIc -ri i r.

7 r IrAl Fr i-I I

2 1. '

L411 L

I L LL82

.L'LIIL]L' 21 VI 1 L[U IL

+/-1']4 !1 I

l.1-.1 8999 gLlIIig 999191189811LI I...~l l11818991991999I19119 1.6 -

LJL94Lq I:,I.

i U.LJ L5.IL.IIl L

15.

LJI.8Ies

.~..LJ L II 9

I llf illll lII$

9fi ll Ji l II 9fillIt 99896 9999919 I

9 191999 9998 glrlr ragI 19I rig;4 rrirl4rl4l1 4

lj nhI-1 4

aITrfl f1 9o99 I,I ll s 94 8 JI 1998 sees gll I999 i9l9t 1911 loo99 ilil 8999 9999 I s999 IlTrI r-Irirl -T-lrIoTrr JuLlrir]th

~ir-ir-~-irlT9l1r 921ILIL LLi J

L L

=LJ~i~

J I I JLL4LJ4L~ j ILulL.J1L IL 15 9JI 4

L SL4LI49.IULJLJL 1l LIS J

1.

4,-IJ A

'--41 WI Ilil 99199999991t111111191998111199Ill89II9III li 9898il aOs hlo il isl is I

lll of-irlr-9fij-l llrl Tgha 1r loll l[llrI lol i.

I a

I 8

I Allowable ime to Reaign CEA vs niial riTrrnr St. Lucle Unit 2 Cycle 15 COLR Rev 2 Page 8 of 18

M 0 w

r O C 0o 7 n-Co S (D (D(

CA Cg: 0-0 L

1 f

T-0.80 0.0 cc 0.70 a

lo I

X 00

-0O T

E06 O

0TEAOr STATe STtSD r 0.

1INSER(TION LIMIT INSERTION I.IMIT oj 0.10 5

3 0

20 40 60 80 100 0

20 40 60 80 100 0

20 40 (136) (106.8)

(81.8)

(54.4)

(27.2)

(0)

(136)

(108.8)

(81.6)

(54.4)

(27.21 (0)

(126) (108.8)

(61.6) 4 2

0 20 40 8o 80 10 0

20 40 80 80 100 (138)

(108.8)

(01,8)

(54.4)

(27.2)

(0)

(138) (108.8)

(81.6)

(54.4)

(27.2)

(0)

Y CEA INSERTION (INCHlE S C EA W ITHDR AW N)

I 60 80 t00 (54.4)

(27.2)

(0)

FIGURE 3.1-2 CEA Group Insertion Limits vs. THERMAL POWER

.L..e........... Ui.. C.yl 1.OR Rv 2 9

St. Lucie Unit 2 Cycle 1 5 COLR Rev 2 Page 9 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment 14.0 13.5-7 13.0-c co C 120 a) 30

= 11.5 11.0 I

I I

I a

I I

I

.1 1.

I I

I I

I

~

I a a

a I

a' I

tJAB OP a 10a I

I I

I I

I IBL

.PEIA*1O S

I I

I I

a a

a a

I I

I I

I I

I I

I I

I I

I I

I I

I a

I I

a a

-g I

a - -

- - -.a.

a a

I a

I

.II I

III I

a I

I a I

I I

III I

I a

a~~r~-

a I a a

a a

I I

I a

I I

I I

a 456AT-,-LE O

N a

a a

a a

a a

a a

a a

a a

a I

I a

I a

a a

a a

a a

a I

I a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a I

a a

a a

a a

a a

a a

a a

a a

a I

a a

a a

a a

a a

a a

a a

a a

a a

a a

a I

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

a a

t a

a I

a a

a a

a a

a a

a a

a a

a I

I I

4 I

a I

-I I

BOL Oye Life EOL (Fuel + Clad + Moderator)

FIGURE 3.2-1 Allowable Peak Linear Heat Rate vs. Burnup St. Lucle Unit 2 Cycle 15 COLR Rev 2 Page 10 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment 1.10 1.00

-a I-a) 0 tLa-a 0,

.0 0

E

,o E

a-00 0

a, 0.90 0.80 0.70 0.60 0.50 UNAGCEPTABLEDPERP IONOREcjION.'

.* *, a a

J a

  • J.

A i

a I.

S S

I a

a X,

L J- --; --

a a

a a

a a

a a

a

,a, a

a.

a

a..

a a

a

,a_,,_

a. _

a a

at a/, a,1 a 1_ _

a t-._--*

J a

a a

a a

a a

a a

a a a a/ a a a

a a

a X I I

a a a a a a a

I a

a I I

a a

as g

I I

a a

a a@ a a

a a

a a a

a a

a a

a a

a a a

I I

Iz a

a a

a a a

b..a..I.

a a

a a

r a

-5,.50)

I (0

5l0...aa 4.50 a a a

a a a

a a a

a a a a l

a a a

al a

a a

a a

a a

a a

/.

a* *.

a a a, aL a az a

a a

a a

a a

a

  • a a a a

a a a

a a a a

a a_

a--

-l-F

+

F a>>

T t

a-r

+

a a

l I

--al l

0l

@l a, a a

a

(

a, a aE IO a

a a\\

a a,

a a

a a

a a

a a

a a

a a a a

a a a

a a

a a a

a a

a a a a a..

w

^..v.

a a

a a

a as a a a

a a

a a a a a a a

a a

a al a a

a a a a

a a

a a

a a a a a a a

a a

a a a a a

a a a I

a n rnI n

al a*

a a

a I

Is I

I a

a a

a s

l Ij 'a a a a

a a

a a

a a

e --

0.7 050-0.30 l

-0. 0.

(0.300.0.58 0.40I

-0.7

-0.5

-0.3

-0.1 0.1 0.3 0.5 Peripheral AXIAL SHAPE INDEX (Not Applicable Below 40% Power)

FIGURE 3.2-2 AXIAL SHAPE INDEX vs. Maximum Allowable Power Level AXIAL SHAPE INDEX limits for Linear Heat Rate when using Excore Detector Monitoring System) 0.7 Note:

St. Lucle Unit 2 Cycle 15 COIR Rev 2 Page 11 of 18 St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 11 of 18

rU c CD O z FD W0 c 1.2 -

2 3

UNACCEPTABLE

)l CD o 11 -

OPERATION C

......... 1 REGION zr r e@(1710

s o-w Z I-f I -

-,O...~

c O

rr REGION l

1.06 1

-1.85

~~~.

4....,*---**--v-zs.9-,,,................


;*..e*v**@@Kb 4

F LIMIT CURVE

3. 2 A

Comb-naton....s of T OE (1.83t E

0.80 FT St Lui U'~ 2 Cycle' 15 COL Rev Pae 12-ro---l LL ACCEPTABLE r- *-........

L OP R T O

'oP RATON a

.7...

i.........

REIN.....

Wi' t i --.t i-3 1- ;- -.

- F-;- -
-

o,,,..,,,..,................

I.----.-.-e. ' s.

0.6....

1.65 1.7 1.75 1.8 1.85 Measured F. T FIGURE 3.2-3 Allowable Combinations of THERMAL POWER and FT St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 12 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment 1.1U W

0~

-J w

0w

'4-0 C

0 0Cu L..

LL 1.00 0.90 0.80 0.70 0.60 0.50 n040

.,, i,,;

I I

-L. -. -. -. -. L J

J I

I I

I I

I S

I I

I I

I I

I 1 I:

1 1

I 1 I

I I

I I

I I

I I

I I

, I, I

,nR TO ON R.

I S

I I

I I

I I

w UNA¢CEPTABLE ':

- -NACCE-ABLE

~~OPERATION L

.I j.

,~~~~~~~~

- -E@

N

-I//-

-'- -l E

4

  • j I

I I.

I -

+.

I I

I

-- - -I L

L L

I L

L I

S I

I W

X I

l v

=

a~

I I

I I

I S

I S

I I

I r

I S

I S

I I

S S

a z*

a

.:.. OEAIN:

-0.7

-0.5

-0.3

-0.1 0.1 0.3 0.5 Peripheral AXIAL SHAPE INDEX (Y1)

(Not Applicable Below 40% Power)

FIGURE 3.2-4 AXIAL SHAPE INDEX Operating Limits vs. THERMAL POWER (Four Reactor Coolant Pumps Operating)

(AXIAL SHAPE INDEX limits for DNB) 0.7 St Lucle Unit 2 Cycle 15 COLR Rev 2 Page 13 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment 3.0 LIST OF APPROVED METHODS The analytical methods used to determine the core operating limits are those previously approved by the NRC, and are listed below.

1.

WCAP-1 1596-P-A, 'Qualification of the PHOENIX-P/ANC Nuclear Design System for Pressurized Water Reactor Cores,' June 1988 (Westinghouse Proprietary)

2.

NF-TR-95-01, "Nuclear Physics Methodology for Reload Design of Turkey Point & St.

Lucie Nuclear Plants," Florida Power & Light Company, January 1995 (NRC SER dated June 9, 1995), & Supplement 1, August 1997

3.

CENPD-1 99-P, Rev.1 -P-A, 'C-E Setpoint Methodology: CE Local Power Density and DNB LSSS and LCO Setpoint Methodology for Analog Protection Systems,' January 1986

4.

CENPD-266-P-A, NThe ROCS and DIT Computer Code for Nuclear Design,' April 1983

5.

CENPD-275-P, Revision 1-P-A, 'C-E Methodology for Core Designs Containing Gadolinia-Urania Burnable Absorbers," May 1988, & Revision 1-P Supplement 1 -P-A, April 1999

6.

CENPD-188-A, 'HERMITE: A Multi-Dimensional Space - Time Kinetics Code for PWR Transients,' July 1976

7.

CENPD-1 53-P, Rev. 1-P-A, 'Evaluation of Uncertainty in the Nuclear Power Peaking Measured by the Self-Powered, Fixed Incore Detector System," May 1980

8.

CEN-123(F)-P, 'Statistical Combination of Uncertainties Methodology Part 1: C-E Calculated Local Power Density and Thermal Margin/Low Pressure LSSS for St.

Lucie Unit 1,' December 1979

9.

CEN-123(F)-P, 'Statistical Combination of Uncertainties Methodology Part 2:

Combination of System Parameter Uncertainties In Thermal Margin Analyses for St.

Lucie Unit 1,' January 1980

10.

CEN-123(F)-P, 'Statistical Combination of Uncertainties Methodology Part 3: C-E Calculated Departure from Nucleate Boiling and Linear Heat Rate Limiting Conditions for Operation for St. Lucie Unit 1,' February 1980

11.

CEN-1 91 (B)-P, 'CETOP-D Code Structure and Modeling Methods for Calvert Cliffs Units 1 and 2,' December 1981 St. Lucle Unit 2 Cycle 15 COLR Rev 2 Page 14 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment

12.

Letter, J. W. Miller (NRC) to J. R. Williams, Jr. (FPL), Docket No. 50-389, Regarding Unit 2 Cycle 2 Ucense Approval (Amendment No. 8 to NPF-16 and SER), November 9,1984 (Approval of CEN-123(F)-P (three parts) and CEN-191(B)-P)

13.

CEN-371(F)-P, "Extended Statistical Combination of Uncertainties,' July 1989

14.

Letter, J. A. Norris (NRC) to J. H. Goldberg (FPL), Docket No. 50-389, 'St. Lucie Unit 2 - Change to Technical Specification Bases Sections '2.1.1 Reactor Core' and

'3/4.2.5 DNB Parameters' (TAC No. M87722)," March 14, 1994 (Approval of CEN-371 (F)-P)

15.

CENPD-161-P-A, 'TORC Code, A Computer Code for Determining the Thermal Margin of a Reactor Core," April 1986

16.

CENPD-162-P-A, "Critical Heat Flux Correlation for C-E Fuel Assemblies with Standard Spacer Grids Part 1, Uniform Axial Power Distribution," April 1975

17.

CENPD-207-P-A, "Critical Heat Flux Correlation for C-E Fuel Assemblies with Standard Spacer Grids Part 2, Non-uniform Axial Power Distribution,* December 1984

18.

CENPD-206-P-A, STORC Code, Verification and Simplified Modeling Methods," June 1981

19.

CENPD-225-P-A, 'Fuel and Poison Rod Bowing," June 1983

20.

CENPD-1 39-P-A, OC-E Fuel Evaluation Model Topical Report," July 1974

21.

CEN-161 (B)-P-A, "Improvements to Fuel Evaluation Model," August 1989

22.

CEN-161(B)-P, Supplement 1-P-A, 'Improvements to Fuel Evaluation Model,"

January 1992

23.

CENPD-1 32, Supplement 3-P-A, 'Calculative Methods for the C-E Large Break LOCA Evaluation Model for the Analysis of C-E and W Designed NSSS," June 1985

24.

CENPD-133, Supplement 5-A, 'CEFLASH-4A, A FORTRAN77 Digital Computer Program for Reactor Blowdown Analysis," June 1985

25.

CENPD-134, Supplement 2-A, *COMPERC-11, a Program for Emergency Refill-Reflood of the Core," June 1985

26.

CENPD-135-P, Supplement 5, "STRIKIN-Il, A Cylindrical Geometry Fuel Rod Heat Transfer Program," April 1977 St_

e t 2 e 1_ CL Rv 2

_e 1 o St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 15 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment

27.

Letter, R. L. Baer (NRC) to A. E. Scherer (CE), 'Evaluation of Topical Report CENPD-135, Supplement #5," September 6, 1978

28.

CENPD-137, Supplement 1-P, NCalculative Methods for the C-E Small Break LOCA Evaluation Model," January 1977

29.

CENPD-1 33, Supplement 3-P, NCEFLASH-4AS, A Computer Program for the Reactor Blowdown Analysis of the Small Break Loss of Coolant Accident," January 1977

30.

Letter, K. Kniel (NRC) to A. E. Scherer (CE), 'Evaluation of Topical Reports CENPD-133, Supplement 3-P and CENPD-1 37, Supplement 1-P,m September 27, 1977

31.

CENPD-1 38, Supplement 2-P, 'PARCH, A FORTRAN-IV Digital Program to Evaluate Pool Boiling, Axial Rod and Coolant Heatup," January 1977

32.

Letter, C. Aniel (NRC) to A. E. Scherer (CE), 'Evaluation of Topical Report CENPD-138, Supplement 2-P,m April 10, 1978

33.

Letter, W. H. Bohike (FPL) to Document Control Desk (NRC), "St. Lucie Unit 2, Docket No. 50-389, Proposed Ucense Amendment, MTC Chanae from -27 ycm to

-30 pcm," 1-91-325, December 17,1991

34.

Letter, J. A. Norris (NRC) to J. H. Goldberg (FPL), 'St. Lucie Unit 2 - Issuance of Amendment Re: Moderator Temperature Coefficient (TAC No. M82517)," July 15, 1992

35.

Letter, J. W. Williams, Jr. (FPL) to D. G. Eisenhut (NRC), "St. Lucie Unit No. 2, Docket No. 50-389, Proposed License Amendment, Cycle 2 Reload,' L-84-148, June 4,1984

36.

Letter, J. R. Miller (NRC) to J. W. Williams, Jr. (FPL), Docket No. 50-389, Regarding Unit 2 Cycle 2 License Approval (Amendment No. 8 to NPF-16 and SER), November 9, 1984 (Approval of Methodology contained in L-84-1 48)

37.

Letter, A. E. Scherer Enclosure 1-P to LD-82-001, "CESEC-Digital Simulation of a Combustion Engineering Nuclear Steam Supply System," December 1981

38.

Safety Evaluation Report, "CESEC Digital Simulation of a Combustion Engineering Steam Supply System (TAC No.: 01142)," October 27, 1983

39.

CENPD-282-P-A, Volumes 1, 2, and 3, and Supplement 1, "Technical Manual for the CENTS Code," February 1991, February 1991, October 1991, and June 1993, respectively S. _ul n~ 2 Cyl 15

_OL Re 2___

Pag._

16 o_ 18 St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 16 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment

40.

CEN-121 (B)-P, rCEAW, Method of Analyzing Sequential Control Element Assembly Group Withdrawal Event for Analog Protected Systems," November 1979 (NRC SER dated December 21,1999, Letter K. N. Jabbour (NRC) to T. F. Plunkett (FPL), TAC No. MA4523)

41.

CEN-133(B), "FIESTA, A One Dimensional, Two Group Space-Time Kinetics Code for Calculating PWR Scram Reactivities," November 1979 (NRC SER dated December 21, 1999, Letter K. N. Jabbour (NRC) to T. F. Plunkett (FPL), TAC No.

MA4523)

42.

CEN-348(B)-P-A, Supplement 1-P-A, "Extended Statistical Combination of Uncertainties," January 1997

43.

CEN-372-P-A, "Fuel Rod Maximum Allowable Gas Pressure," May 1990

44.

CENPD-1 83-A, "C-E Methods for Loss of Flow Analysis," June 1984

45.

CENPD-1 90-A, "C-E Method for Control Element Assembly Ejection Analysis," July 1976

46.

CENPD-199-P, Rev. 1-P-A, Supplement 2-P-A, "CE Setpoint Methodology", June 1998

47.

CENPD-382-P-A, "Methodology for Core Designs Containing Erbium Burnable Absorbers," August 1993

48.

CEN-396(L)-P, "Verification of the Acceptability of a 1-Pin Bumup Limit of 60 MWD/KG for St. Lucie Unit 2," November 1989 (NRC SER dated October 18,1991, Letter J. A. Norris (NRC) to J. H. Goldberg (FPL), TAC No. 75947)

49.

CENPD-269-P, Rev. 1-P, "Extended Burnup Operation of Combustion Engineering PWR Fuel," July 1984

50.

CEN-289(A)-P, 'Revised Rod Bow Penalties for Arkansas Nuclear One Unit 2,"

December 1984 (NRC SER dated December 21, 1999, Letter K. N. Jabbour (NRC) to T. F. Plunkett (FPL), TAC No. MA4523)

51.

CENPD-137, Supplement 2-P-A, "Calculative Methods for the ABB CE Small Break LOCA Evaluation Model," April 1998

52.

CENPD-140-A, 'Description of the CONTRANS Digital Computer Code. for Containment Pressure and Temperature Transient Analysis," June 1976

53.

CEN-365(L), "Boric Acid Concentration Reduction Effort, Technical Bases and Operational Analysis," June 1988 (NRC SER dated March 13, 1989, Letter J. A.

Norris (NRC) to W. F. Conway (FPL), TAC No. 69325)

StLc_ U~t2 yce 5 OL

-Rv 17 of 18-----

St. Lucie Unit 2 Cycle 1 5 COLR Rev 2 Page 17 of 18

St. Lucie Unit 2 Docket No. 50-389 L-2005-034 Attachment

54.

DP-456, F. M. Stem (CE) to E. Case (NRC), dated August 19,1974, Appendix 6B to CESSAR System 80 PSAR (NRC SER, NUREG-75/112, Docket No. STN 50-470, "NRC SER - Standard Reference System, CESSAR System 80," December 1975)

55.

CENPD-387-P-A, Revision 000, "ABB Critical Heat Flux Correlations for PWR Fuel,"

May 2000

56.

CENPD-1 32, Supplement 4-P-A, "Calculative Methods for the CE Nuclear Power Large Break LOCA Evaluation Model," March 2001

57.

CENPD-137, Supplement 2-P-A, "Calculative Methods for the ABB CE Small Break LOCA Evaluation Model," April 1998

58.

CENPD-404-P-A, Rev. 0, "Implementation of ZIRLOQm Cladding Material in CE Nuclear Power Fuel Assembly Designs," November 2001

59.

WCAP-9272-P-A, "Westinghouse Reload Safety Evaluation Methodology'" July 1985

60.

WCAP-10216-P-A, Revision 1A, "Relaxation of Constant Axial Offset Control; FQ Surveillance Technical Specification," February 1994

61.

WCAP-1 1397-P-A, (Proprietary), "Revised Thermal Design Procedure," April 1989

62.

WCAP-14565-P-A, (Proprietary),

"VIPRE-01 Modeling and Qualification for Pressurized Water Reactor Non-LOCA Thermal-Hydraulic Safety Analysis," October 1999

63.

WCAP-14565-P-A, Addendum 1-A, Revision 0, "Addendum 1 to WCAP-14565-P-A Qualification of ABB Critical Heat Flux Correlations with VIPRE-01 Code," August 2004

64.

Letter, W. Jefferson, Jr. (FPL) to Document Control Desk (USNRC), "St. Lucie Unit 2 Docket No. 50-389: Proposed License Amendment WCAP-9272 Reload Methodology and Implementing 30% Steam Generator Tube Plugging Limit," L-2003-276, December, 2003 (NRC SER dated January 31, 2005, Letter B. T. Moroney (NRC) to J. A. Stall (FPL), TAC No. MCI1566)

St. _

Lu _

_n

_ 2 Cyl 15 CL Rev 2_._a__

1_

_f 18_

St. Lucie Unit 2 Cycle 15 COLR Rev 2 Page 18 of 18