Letter Sequence Request |
---|
|
Results
Other: ML18130A760, ML18130A820, ML18130A849, ML18130A885, NRC-2018-0187, Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation Company, LLC - Environmental Assessment, NRC-2018-0192, Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation, LLC; Environmental Assessment, NRC-2018-0193, First Energy Operating Company (FENOC) Firstenergy Nuclear Generation, LLC, Beaver Valley Power Station, Units 1 and 2
|
MONTHYEARL-17-112, Exemption Request for Physical Barrier Requirement2017-07-19019 July 2017 Exemption Request for Physical Barrier Requirement Project stage: Request ML17262A7232017-09-20020 September 2017 FENOC Fleet - Results of Acceptance Review of the Exemption Request Exemption from the Definition of Physical Barrier in 10 CFR 73.2 for Physical Security Plans Project stage: Acceptance Review L-18-061, Units. 1 & 2, Davis-Besse, and Perry, Response to Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement2018-03-16016 March 2018 Units. 1 & 2, Davis-Besse, and Perry, Response to Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement Project stage: Response to RAI L-18-125, Response to Follow-up Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement IEPID-L-2017-l-LE-0019 (CAC Nos.000976/05000334/-L-2017-LLE-0019 MG0010, 000976/05000334/L-2017-LLE-0019 MG0011,000976/02018-05-0202 May 2018 Response to Follow-up Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement IEPID-L-2017-l-LE-0019 (CAC Nos.000976/05000334/-L-2017-LLE-0019 MG0010, 000976/05000334/L-2017-LLE-0019 MG0011,000976/0 Project stage: Request ML18130A8852018-08-29029 August 2018 FENOC Fleet - Beaver Valley; Davis-Besse; Perry - Environment Assessment and Finding of No Significant Impact Related to Exemption Request for a Physical Barrier Requirement (CAC Nos. MG0010, MG0011, MG0012, and MG0013; EPID L-2018-LLE-0019 Project stage: Other ML18130A8892018-08-29029 August 2018, 4 September 2018 Environmental Assessment and Finding of No Significant Impact Related to Exemption Request for a Physical Barrier Requirement Project stage: Request ML18130A7602018-09-0404 September 2018 First Energy Operating Company (FENOC) Firstenergy Nuclear Generation, LLC, Beaver Valley Power Station, Units 1 and 2 Project stage: Other ML18130A8492018-09-0404 September 2018 Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation, LLC; Environmental Assessment Project stage: Other ML18130A8202018-09-0404 September 2018 Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation Company, LLC - Environmental Assessment Project stage: Other NRC-2018-0192, Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation, LLC; Environmental Assessment2018-09-0404 September 2018 Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation, LLC; Environmental Assessment Project stage: Other NRC-2018-0187, Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation Company, LLC - Environmental Assessment2018-09-0404 September 2018 Firstenergy Nuclear Operating Company (Fenoc); Firstenergy Nuclear Generation Company, LLC - Environmental Assessment Project stage: Other NRC-2018-0193, First Energy Operating Company (FENOC) Firstenergy Nuclear Generation, LLC, Beaver Valley Power Station, Units 1 and 22018-09-0404 September 2018 First Energy Operating Company (FENOC) Firstenergy Nuclear Generation, LLC, Beaver Valley Power Station, Units 1 and 2 Project stage: Other 2018-03-16
[Table View] |
|
---|
Category:Letter type:L
MONTHYEARL-24-226, License Renewal Application for the Perry Nuclear Power Plant Revision O - Response to Requests for Confirmatory Information (Rcls) - Set 12024-10-31031 October 2024 License Renewal Application for the Perry Nuclear Power Plant Revision O - Response to Requests for Confirmatory Information (Rcls) - Set 1 L-24-179, License Renewal Application for the Perry Nuclear Power Plant Revision 0 - Supplement 52024-10-21021 October 2024 License Renewal Application for the Perry Nuclear Power Plant Revision 0 - Supplement 5 L-24-208, License Renewal Application for the Perry Nuclear Power Plant - Responses to Request for Additional Information - Round 1 (Set 2)2024-10-0202 October 2024 License Renewal Application for the Perry Nuclear Power Plant - Responses to Request for Additional Information - Round 1 (Set 2) L-24-015, Twenty-Ninth Refueling Outage Inservice Inspection Summary Report2024-09-17017 September 2024 Twenty-Ninth Refueling Outage Inservice Inspection Summary Report L-24-038, License Amendment Request to Remove the Expired One-Time Action for Valve Leak Repair in Technical Specification (TS) 3.5.2 and to Correct Core Operating Limits Rep Ort (COLR) References2024-09-17017 September 2024 License Amendment Request to Remove the Expired One-Time Action for Valve Leak Repair in Technical Specification (TS) 3.5.2 and to Correct Core Operating Limits Rep Ort (COLR) References L-24-207, License Renewal Application for the Perry Nuclear Power Plant-Response to Request for Additional Information - Set 12024-09-16016 September 2024 License Renewal Application for the Perry Nuclear Power Plant-Response to Request for Additional Information - Set 1 L-24-201, Spent Fuel Storage Cask Registration2024-09-0909 September 2024 Spent Fuel Storage Cask Registration L-24-200, License Renewal Application for Revision to Supplement 4 for Editorial Corrections2024-09-0505 September 2024 License Renewal Application for Revision to Supplement 4 for Editorial Corrections L-24-188, Submittal of Quality Assurance Program Manual, Revision 302024-08-27027 August 2024 Submittal of Quality Assurance Program Manual, Revision 30 L-24-190, Spent Fuel Storage Cask Registration2024-08-26026 August 2024 Spent Fuel Storage Cask Registration L-24-199, Discharge Monitoring Report (NPDES) Permit No. PA00256152024-08-22022 August 2024 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-24-186, Response to RAI for Exemption Request from 10 CFR 50.71(e)(4) Final Safety Analysis Update Schedule2024-08-15015 August 2024 Response to RAI for Exemption Request from 10 CFR 50.71(e)(4) Final Safety Analysis Update Schedule L-24-174, Response to Perry Nuclear Power Plant License Renewal Environmental Report Severe Accident Mitigation Alternatives 2nd Round Request for Additional Information2024-08-15015 August 2024 Response to Perry Nuclear Power Plant License Renewal Environmental Report Severe Accident Mitigation Alternatives 2nd Round Request for Additional Information L-24-178, License Renewal Application Revision O - Supplement 42024-08-0808 August 2024 License Renewal Application Revision O - Supplement 4 L-24-189, License Renewal Application for Revision O - Supplement 12024-08-0707 August 2024 License Renewal Application for Revision O - Supplement 1 L-24-171, Spent Fuel Storage Cask Registration2024-07-30030 July 2024 Spent Fuel Storage Cask Registration L-24-108, License Renewal Application, Revision 0 - Supplement 32024-07-24024 July 2024 License Renewal Application, Revision 0 - Supplement 3 L-24-182, Discharge Monitoring Report (NPDES) Permit No. PA00256152024-07-23023 July 2024 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-24-161, Discharge Monitoring Report (NPDES) Permit No. PA00256152024-07-19019 July 2024 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-24-014, Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling Svstem Evaluation Models2024-07-16016 July 2024 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling Svstem Evaluation Models L-24-032, Cycle 23 and Refueling Outage 23 Inservice Inspection Summary Report2024-07-15015 July 2024 Cycle 23 and Refueling Outage 23 Inservice Inspection Summary Report L-24-063, License Amendment Request to Remove the Table of Contents from the Technical Specifications2024-07-0808 July 2024 License Amendment Request to Remove the Table of Contents from the Technical Specifications L-24-164, BV-2, Post Accident Monitor Report2024-06-27027 June 2024 BV-2, Post Accident Monitor Report L-24-020, License Renewal Application for the Perry Nuclear Power Plant Revision 0, Supplement 22024-06-27027 June 2024 License Renewal Application for the Perry Nuclear Power Plant Revision 0, Supplement 2 L-24-036, Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models2024-06-27027 June 2024 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models L-24-094, Reactor Vessel Surveillance Capsule Withdrawal Schedule2024-06-24024 June 2024 Reactor Vessel Surveillance Capsule Withdrawal Schedule L-24-024, Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models2024-06-19019 June 2024 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models L-24-152, Response to NRC Regulatory Issue Summary 2024-01 Preparation and Scheduling of Operator Licensing Examinations2024-06-17017 June 2024 Response to NRC Regulatory Issue Summary 2024-01 Preparation and Scheduling of Operator Licensing Examinations L-23-214, Submittal of Relief Request for Impractical American Society of Mechanical Engineers Boiler and Pressure Vessel Code Section XI Examination Requirements2024-06-0505 June 2024 Submittal of Relief Request for Impractical American Society of Mechanical Engineers Boiler and Pressure Vessel Code Section XI Examination Requirements L-24-021, Cycle 30 Core Operating Limits Report2024-05-23023 May 2024 Cycle 30 Core Operating Limits Report L-24-121, Discharge Monitoring Report (NPDES) Permit No. PA00256152024-05-23023 May 2024 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-24-019, Unit No.1 - Report of Facility Changes, Tests, and Experiments2024-05-22022 May 2024 Unit No.1 - Report of Facility Changes, Tests, and Experiments L-24-116, Response to License Renewal Environmental Report Severe Accident Mitigation Alternatives Requests for Additional Information and Request for Clarification2024-05-16016 May 2024 Response to License Renewal Environmental Report Severe Accident Mitigation Alternatives Requests for Additional Information and Request for Clarification L-24-111, Response to Regulatory Issue Summary 2024-01, Preparation and Scheduling of Operator Licensing Examinations2024-05-15015 May 2024 Response to Regulatory Issue Summary 2024-01, Preparation and Scheduling of Operator Licensing Examinations L-24-072, Combined Annual Radiological Environmental Operating Report and Radioactive Effluent Release Report - 20232024-05-15015 May 2024 Combined Annual Radiological Environmental Operating Report and Radioactive Effluent Release Report - 2023 L-24-031, Unit No.1 - Steam Generator Tube Circumferential Crack Report - Spring 2024 Refueling Outage2024-05-14014 May 2024 Unit No.1 - Steam Generator Tube Circumferential Crack Report - Spring 2024 Refueling Outage L-24-107, CFR 50.55a Request 1-TYP-5-RRP-l, for Alternative Method of Nondestructive Examination for River Water Outlet Piping Weld Repair2024-05-13013 May 2024 CFR 50.55a Request 1-TYP-5-RRP-l, for Alternative Method of Nondestructive Examination for River Water Outlet Piping Weld Repair L-23-269, Application to Revise Technical Specifications to Adopt TSTF-569, Revision of Response Time Testing Definitions2024-05-0707 May 2024 Application to Revise Technical Specifications to Adopt TSTF-569, Revision of Response Time Testing Definitions L-24-085, Nudear Power Plant, Submittal of Emergency Plan, Revision 622024-05-0606 May 2024 Nudear Power Plant, Submittal of Emergency Plan, Revision 62 L-24-103, Response to NRC Regulatory Issue Summary 2024-01, Preparation & Scheduling of Operator Licensing Exams2024-05-0202 May 2024 Response to NRC Regulatory Issue Summary 2024-01, Preparation & Scheduling of Operator Licensing Exams L-24-069, Occupational Radiation Exposure Report for Year 20232024-04-30030 April 2024 Occupational Radiation Exposure Report for Year 2023 L-24-054, Submittal of 2023 Annual Radioactive Effluent Release Report 2023 Annual Radiological Environmental Operating Report and 2023 Annual Environmental Operating Report (Non-Radiological)2024-04-29029 April 2024 Submittal of 2023 Annual Radioactive Effluent Release Report 2023 Annual Radiological Environmental Operating Report and 2023 Annual Environmental Operating Report (Non-Radiological) L-24-089, Emergency Preparedness Plan2024-04-23023 April 2024 Emergency Preparedness Plan L-24-088, Discharge Monitoring Report (NPDES) Permit No. PA0025615 for March 20242024-04-22022 April 2024 Discharge Monitoring Report (NPDES) Permit No. PA0025615 for March 2024 L-24-097, Submittal of 2023 Annual Radiological Effluent Release Report2024-04-22022 April 2024 Submittal of 2023 Annual Radiological Effluent Release Report L-24-096, Submittal of Annual Radiological Environmental Operating Report2024-04-22022 April 2024 Submittal of Annual Radiological Environmental Operating Report L-24-018, Submittal of Core Operating Limits Report, Cycle 24, Revision 02024-04-16016 April 2024 Submittal of Core Operating Limits Report, Cycle 24, Revision 0 L-24-066, Response to Request for Additional Information Regarding 10 CFR 50.55a Request Number VR-9, Feedwater Check Valve Exercising Test Frequency2024-04-15015 April 2024 Response to Request for Additional Information Regarding 10 CFR 50.55a Request Number VR-9, Feedwater Check Valve Exercising Test Frequency L-24-083, Response to License Renewal Environmental Report Requests for Additional Information and Request for Clarification2024-04-15015 April 2024 Response to License Renewal Environmental Report Requests for Additional Information and Request for Clarification L-24-082, Withdrawal of Exemption Request2024-04-0303 April 2024 Withdrawal of Exemption Request 2024-09-09
[Table view] |
Text
FENOC 347 White Pond Drive Akron. Ohia 44320 Somuel L. Belcher 330-435-7393 President & Chiel Nuclear Officer July 19,2017 L-17-112 10 cFR 73.5 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001
SUBJECT:
Beaver Valley Power Station, Unit Nos. 1 and 2 Docket No. 50-334, License No. DPR-66 Docket No. 50412, License No. NPF-73 Davis-Besse Nuclear Power Station Docket No. 50-346, License No. NPF-3 Perry Nuclear Power Plant Docket No. 50-440, License No. NPF-58 Exemption Request for a Phvsical Barrier Requirement Pursuant to 10 CFR 73.5, "Specific exemptions," FirstEnergy Nuclear Operating Company (FENOC) is requesting a permanent exemption from a requirement of 10 CFR 73.2, "Definitions" for Beaver Valley Power Station Unit Nos. 1 and 2, Davis-Besse Nuclear Power Station, and Perry Nuclear Power Plant. The regulation requires, in part, fences topped by three strands or more of barbed wire or similar material on brackets to be angled inward or outward between 30 and 45 degrees from the vertical.
An exemption is requested since not all protected area physical barrier fencing sections meet this requirement.
FENOC requests approval of the enclosed exemption request by July 21,2018.
There are no regulatory commitments contained in this submittal. lf there are any questions or if additional information is required, please contact Mr. Thomas A. Lentz, Manager - Fleet Licensing, at 330-315-6810.
Sincerely, amue I L. Belcher
Beaver Valley Power Station, Unit Nos. 1 and 2 Davis-Besse Nuclear Power Station Perry Nuclear Power Plant L-17-112 Page 2 of 2
Enclosure:
Exemption Request cc:
NRC Region I Administrator NRC Region lll Administrator NRC Resident lnspector - Eleaver Valley NRC Resident lnspector - Davis-Besse NRC Resident lnspector - Perry NRC Proiect Manager - FENOC Fleet Director BRP/DEP Site BRP/DEP Representative Utility Radiological Safety Boand Branch Chief, OEMA, State of Ohio
Exemption Request Page 1 of 6
Subject:
Request for exemption from a requirement of 10 CFR 73.2, "Definitions" to allow the use of protected area fencing sections not meeting the physical barriers requirement at Beaver Valley Power Station Unit Nos. 1 and 2, Davis-Besse Nuclear Power Station, and Perry Nuclear Power PIant 1.0 PURPOSE
2.0 BACKGROUND
3.0 PROPOSED EXEMPTION 4.0 JUSTIFICATION OF EXEMPTION 5.0 ENVIRONMENTAL ASSESSMENT
6.0 CONCLUSION
7.0 REFERENCES
Page 2 of 6 1.0 PURPOSE ln accordance with 10 CFR 73.5, "Specific exemptions," FirstEnergy Nuclear Operating Corporation (FENOC) requests a permanent exemption from the provisions of 10 CFR 73.2, "Definitions" for Beaver Valley Power Station (BVPS) Unit Nos. 1 and 2, Davis-Besse Nuclear Power Station (DBNPS), and Perry Nuclear Power Plant (PNPP).
The request relates solely to a requirement for fences in the definition of a physical barrier. The regulation requires, in part, fences topped by three strands or more of barbed wire or similar material on brackets to be angled inward or outward between 30 and 45 [degrees] from the vertical. An exemption is requested since not all protected area physical barrier fencing sections meet this requirement.
2.0 BACKGROUND
On May 17 ,2016, FENOC received a minor violation during conduct of the NRC evaluated force-on-force inspection at BVPS. The minor violation was due to not all barbed wire on the top of protected area physical barrier fencing sections meeting the angled requirement of 10 CFR 73.2. Specifically, barbed wire on the top of physical barrier fencing is currently oriented vertically on gates, near gates, near interfaces with buildings, and on corners. DBNPS and PNPP have similar configurations, except DBNPS also has vertical barbed wire on top of fences near the intrusion detection system (lDS).
3.0 PROPOSED EXEMPTION FENOC requests a permanentexemption to 10 CFR 73.2 for BVPS, DBNPS, and PNPP to allow protected area physical barrier fences to be topped by three strands or more of barbed wire or similar material that are vertically oriented on and near gates, near interfaces with buildings, on corners, and, in the case of DBNPS, near the lDS.
4.0 JUSTIFICATION OF EXEMPTION The basis for this exemption is that the vertical configuration of barbed wire on the top of limited protected area sections (on and near gates, near interfaces with buildings, on corners, and near the IDS) does not have an adverse impact on the site protective strategies and will continue to protect against the design basis threat of radiological sabotage. Because the vertical barbed wire will maintain the plant's physical security, the underlying purpose of the regulation is met.
The limited protected area sections where the configuration does not meet the regulatory requirement is a small portion of the entire protected area perimeter.
Consultation of design drawings and protected area site walkdowns estimates this portion to be approximately six percent or less for each of the three sites.
Finally, the NRC staff has partially approved this configuration at each of the three sites.
NRC approval of Chapter 6, Section 6.2 of the BVPS, DBNPS, and PNPP Physical Security Plans (References 1,2, and 3, respectively), acknowledged that the angular requirement for the fence topping may not be met at locations such as gates and buildings.
Page 3 of 6 10 CFR 73.5, "Specific exemptions," states that the Commission may grant exemptions from the requirements of the regulations of this pail provided specific criteria are met.
The requested exemption satisfies these criteria as described below.
- 1. This exemption is authorized by law.
The Commission has the authority under 10 CFR 73.5 to grant an exemption from the requirements of Part 73 upon proper justification. Therefore, granting an exemption is explicitly authorized by law.
- 2. This exemption will not endanger life or property or the common defense and security.
This exemption to allow vertical barbed wire fence toppings in limited protected area sections (on and near gates, near interfaces with buildings, on corners, and near the IDS) does not degrade the purpose of physical deterrent for which the barbed topping is intended. Therefore, this exemption will not endanger life or property or the common defense and security.
- 3. This exemption is otherwise in the public interest.
This exemption to allow vertical barbed wire fence toppings in limited protected area sections (on and near gates, near interfaces with buildings, on corners, and nearthe IDS) maintains the physical security of the sites and does not have an adverse effect on public interest.
5.0 ENVIRONMENTAL ASSESSMENT FENOC has determined the proposed exemption meets the eligibility criteria for categorical exclusion of an environmental review in 10 CFR 51.22(cX25), as there are:
(i) no significant hazards consideration; (ii) no significant change in the types or significant increase in the amounts of any effluents that may be released offsite; (iii) no significant increase in individual or cumulative public or occupational radiation exposure; (iv) no significant construction impact; (v) no significant increase in the potential for or consequences from radiological accidents; and (vi) the requirements from which the exemption is sought involves safeguards plans or other requirements of an administrative, managerial or organizational nature. The information provided below supports the basis for determination.
(i) No significant hazards consideration.
FENOC has evaluated the proposed exemption to determine whether or not a significant hazards consideration is involved by focusing on three standards set forth in 10 CFR 50.92, "lssuance of amendment," as discussed below:
1 . Does the proposed exemption involve a significant increase in the probability or consequence of an accident previously-evaluated?
Page 4 of 6 Response: No The proposed exemption would allow the existing limited protected area physical barrier fences at BVPS, DBNPS, and PNPP to remain topped by three strands or more of barbed wire or similar material that are vertically oriented on and near gates, near interfaces with buildings, on corners, and, in the case of DBNPS, near the !DS.
Orientation of barbed wire on the top of limited protected area physical barrier fencing sections does not alter any assumptions or methodologies associated with previously-evaluated accidents. Therefore, there is no increase in the probability or consequence of any previously-evaluated accident.
- 2. Does the proposed exemption create the possibility of a new or different kind of accident from any accident previously-evaluated?
Response: No The proposed exemption to allow the existing orientation of barbed wire on top of limited protected area physical barrier fencing sections does not involve a physical alteration of the plant. No new or different type of equipment will be installed, and there are no physical modifications to existing equipment associated with the proposed exemption. There are no changes to operating procedures, and therefore, personnel failures.
Therefore, the proposed exemption does not create the possibility of a new or different kind of accident from any accident previously-evaluated.
- 3. Does the proposed exemption involve a significant reduction in a margin of safety?
Response: No The proposed exemption to allow the existing orientation of barbed wire on top of limited protected area physical barrier fencing sections does not alter the design basis or any safety limits for the plants. The proposed exemption does not impact station operations or any plant systems, structures, or components that are relied upon for accident mitigation.
Therefore, the proposed exemption does not involve a significant reduction in a margin of safety.
Based on the above, FENOC concludes that the proposed exemption does not involve a significant hazards consideration under the standards set forth in 10 CFR 50.92(c), and, accordingly, a finding of "no significant hazards consideration" is justified.
Page 5 of 6 (ii) There is no significant change in the types or significant increase in the amounts of any effluents that may be released offsite.
The proposed exemption for Iimited protected area physical barrier fencing sections will not result in changes to the systems, structures, or components that function to limit or monitor the release of effluents. Therefore, there is no expected change in the type or amount of effluents that may be released offsite with the proposed exemption.
(iii) There is no significant increase in individual or cumulative public or occupational radiation exposure.
The proposed exemption for limited protected area physical barrier fencing sections is not expected to increase individual or cumulative public or occupational radiation exposure. There are no expected changes in normal occupational doses.
(iv)There is no significant construction impact.
No construction activities are associated with the proposed exemption.
(v) There is no significant increase in the potential for or consequences from radiological accidents.
As discussed in the no significant hazards consideration analysis in ltem (i) above, the proposed exemption for limited protected area physical barrier fencing sections is not expected to increase the potential for or consequences from radiological accidents.
(vi)The requirement from which an exemption is sought involves safeguard plans or other requirements of an administrative, managerial, or organizational nature.
The proposed exemption to 10 CFR 73.2 would allowthe existing limited protected area physical barrier fences at BVPS, DBNPS, and PNPP to remain topped by three strands or more of barbed wire or similar material that are vertically oriented on and near gates, near interfaces with buildings, on corners, and, in the case of DBNPS, near the !DS. This exemption involves safeguard plans.
6.0 CONCLUSION
Pursuantto 10 CFR 73.5, the requested exemption is authorized by !aw, will not endanger life or property or the common defense and security, and does not have an adverse effect on public interest. Approval of this exemption request does not violate the underlying purpose of the regulation.
Page 6 of 6 7.0. REFERENCES 1 Safety Evaluation by the Office of Nuclear Reactor Regulation and the Office of Nuclear Security and Incident Response Related to Order EA-03-080 to Facility Operating License Nos. DPR-66 and NPF-73, FirstEnergy Nuclear Operating Company (FENOC) Beaver Valley Power Station (BVPS, Units 1 and 2),
Docketed Nos. 50-334 and 50,412, dated 10128104.
- 2. Safety Evaluation by the Office of Nuclear Reactor Regulation and the Office of Nuclear Security and lncident Response Related to Order EA-03-086 to Facility Operating License No. NPF-3, FirstEnergy Nuclear Operating Company, Davis-Besse Nuclear Power Station, Docket No. 50-346, dated 10128104.
- 3. Safety Evaluation by the Office of Nuclear Reactor Regulation and the Office of Nuclear Security and lncident Response Related to Order EA-03-086 to Facility Operating License No. NPF-58, FirstEnergy Nuclear Operating Company (FENOC), Perry Nuclear Power PIant, Unit 1, Docket No. 50.440, dated 10128104.