JPN-98-005, Forwards Application for Amend to License DPR-59,allowing RCS Pressure Tests to Be Performed While Remaining in Cold Shutdown Mode.Encl Supersedes & Replaces Application for Amend Submitted 960201

From kanterella
(Redirected from JPN-98-005)
Jump to navigation Jump to search
Forwards Application for Amend to License DPR-59,allowing RCS Pressure Tests to Be Performed While Remaining in Cold Shutdown Mode.Encl Supersedes & Replaces Application for Amend Submitted 960201
ML20202D527
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 02/06/1998
From: James Knubel
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20202D532 List:
References
RTR-NUREG-1433 JPN-98-005, JPN-98-5, NUDOCS 9802170107
Download: ML20202D527 (3)


Text

1 123 Main Street -

Whits Plans. New York 10001 914 081.67A Did 287 3309 (Fa4 A NewWrkPower s.-.. x es.'

4# Authority ErN f W:""

February 6,1998 JPN-98 005 United States Nuclear Regulatory Commission ATTN: Document Control Desk Mail Station P1-137 Washington, DC 20555

Subject:

James A. FitzPatrick Nuclear Power Plant Docket No. 50 333 Revision to Proposed Technica' Specification Change (JPTS 95 004, lasRIylce Leak and Hydrostatic Testina Ooeration)

References:

1. NYPA Letter, W. J. Cahill, Jr. to USNRC, " Proposed Changes to the Technical Specifications Regarding Inservice Leak and Hydrostatic Testing Operation (JPTS-95-004)", JPN-96-005 dated February 1, 1996
2. LER-95-007, Enforcement Discretion Required for Control Room Ventilation Operability Requirements, dated April 20,1995, from H. P.

Salmon, Jr.

3. NYPA Letter, M. J. Colomb to USNRC, " Additional Information Regarding Proposed Change to the Technical Specifications Regarding inservice Leak and Hydrostatic Testing Operation (JPTS-95-004)",

JAFP 96-0379 dated September 26,1996

Dear Sir:

This application for an amendment to the James A. FitzPatrick Technical Specifications (TS) supersedes and replaces the amendment application transmitted by Reference 1. The application for an amendment proposes to allow reactor coolant system pressure tests to be performed while remaining in the Cold Shutdown Mode. Primary containment integrity is not required in the Cold Shutdown Mode thus allowing unrestricted access to the primary containment for the performance of inspections. The changes will also allow some outage activities on other systems to continue at the same time as during pressure testing. The changes are consistent with Special Operations Section 3.10.1, " Inservice Leak and Hydrostatic Testing Operation," from Standard Technical Specifications (STS), NUREG- $

1433, Revision 1. Minor exceptions are required to ensure consistency within FitzPatrick TS, reflect differences between FitzPatrick TS and STS, and ensure the same level of ECCS kC b . {

d redundancy afforded by STS during pressure testing. These exceptions will be eliminated when the FitzPatrick TS are converted to improved Technical Specifications based on NUREG-1433, Revision 1. Editorial changes to improve the table of contents, relocate text, use consistent terminolo,gy,, and reflect the addition of new TS pages are also proposed.

4002170107 90020'6 l l PDR p

ADOCK 05000333 PDR ll llilllllll llllll

  • iia e : -

a

a United StCtCs Nuclear Regulatory Commission Attn: Document Control Desk

Subject:

Revision to JPTS-95-004 Page 2 This revision also addresses instrumentation required for initiation of Reactor Building

-(secondary containment) isolation, automatic initiation of the Standby Gas Treatment System, and additional details regarding secondary containment isolation valves. Revised Technical Specification pages (in Attachment 1) have been changed to explicitly state which instrumentation is required by proposed limiting condition for operation (LCO) 3.12.A,

" Inservice Leak and Hydrostatic Testing Operation", and an explicit reference to the

- definition of secondary containment integrity has been added. Discussion of the changes and a comparison to STS LCO 3.10.1 requirements are included in Attachment ll.

The signed original of the Application for Amendment to the Operating License is enclosed for filing. Attachment I contains the proposed new Technical Specification pages, and Attachment 11 is the Safety Evaluation for the proposed changes. Changes to the text in -

Attachment 11 to reflect the request for additionalinformation is indicated by a vertical bar in the margin. A markup of the affected Technical Specification pages is included as Attachment ll1.-

There are no commitments contained in this submittal.

A copy of this application and the associated attachments are being provided to the designated New York State officialin accordance with 10 CFR 50.91, if you have any questions, please contact Mr. A. Zaremba at (315) 349-6365.

Very truly yours,

, f +

' J. Knubel h Senior Vice President and

, Chief Nuclear Officer cc: Next page s

d y

_. ,,--r------- - , - --v ---

-w

- cc: . Riglon:1 Administrator -

- U. S. Nuclear. Regulatory Commission 475 Allendale Road:

King of Prussia, PA 19406

Office of the Resident inspector -3 U. S.- Nuclear Regulatory Commission l

- P.O. Box 136:

~ Lycoming, NY 13093 -

Daniel Dorman, Project Manager Project Directorate 11

Division _of Reactor Projects-l/ll-U. S. Nuclear Regulatory Commission -

Mall Stop _14 B2 Washington, DC 20555--

Mr. F. William Valentino, President New York State Energy, Research,

- and Development Authority -

Corporate Plaza West

. 286 Washington Avenue Extension -

Albany, NY .-12203-6399

?

_ a

'1