, JAMES A. FITZPATRICK NUCLEAR POWER PLANT OPERATING DATA REPORT DOCKET NO. 50-333 UNIT NAME FITZPATRICK DATE Oct. 1985 COMPLETED BY JOHN COOK TELEPHONE (315)342-3840 OPERATING STATUS

1. UNIT NAME: FITZPATRICK
2. REPORTING PERIOD: 850901-850930
3. LICENSED THERMAL POWER (MWT): 2436
4. NAMEPLATE RATING (GROSS MWE): 883
5. DESIGN ELECTRICAL RATING (NET MWE): 821
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): 830
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE): 810
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 - 7) SINCE LAST REPORT, GIVE REASONS:

NONE

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE): NONE
10. REASONS FOR RESTRICTIONS IF ANY:

THIS MONTH YR-TO-DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD: 720 6551 89232
12. NUMBER OF HOURS REACTOR WAS CRITICAL: 720 3650.6 63266.6
13. REACTOR RESERVE SHUTDOWN HOURS: 0 0 0 14 HOURS GENERATOR ON-LINE: 720 3455.7 61403
15. UNIT RESERVE SHUTDOWN HOURS: 0 0 0
16. GROSS THERMAL ENERGY GENERATED (MWH): 1741536 7815192 130751146
17. GROSS ELECTRICAL ENERGY GENERATED (MWH): 588950 2625010 44905290
18. NET ELECTRICAL ENERGY GENERATED (MWH): 569065 2536745 42934750
19. UNIT SERVICE FACTOR: 100 52.8 68.8
20. UNIT AVAILABILITY FACTOR: 100 52.8 68.8
21. UNIT CAPACITY FACTOR (USING MDC NET): 97.6 47.8 62.4
22. UNIT CAPACITY FACTOR (USING DER NET): 96.3 47.2 58.6
23. UNIT FORCED OUTAGE RATE: 0 13.8 13.5
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE AND DURATION OF EACH):

Planned Maintenance Outage March 10. 1986 to last approximately 2 weeks.

25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION): FORECAST ACllIEVED INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION O gq Ai

JAMES A. FITZPATRICK NUCLEAR POWER PLANT AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-333 UNIT FITZPATRICK DATE OCT. 1985 COMPLETED BY- JOHN COOK TELEPHONE (315)342-3840

- MONTH SEPTEMBER 1985 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL

'l 795 17 799 2 793 18 798 3 791- 19 796 4 790 20 796 5 790 21 796 i 6 789 22 797 7 788 23 798 1 1

8 787 24 797 9 787 25 795 10 789 26 701 11 794 27 780 12 797 28 794 13 793 29 795 14 799 30 795 15 795 31 ---

16 796

SUMMARY

THE FITZPATRICK PLANT OPERATED AT NEAR FULL THERMAL POWER FOR THIS ENTIRE REPORTING PERIOD.

f \ "

.A m__

.y ._;, _. .

q> .x - ,

sy '

.,4.

g JAMES A._FITZPATRICK NUCLEAR. POWER PLANT,, . ,,.j'7 ' ,.

. UNIT SHUTDOWNS AND P%'ER REDUCTIONS .

-. r.

50-333 DOCKET NO.<

f ,

UNIT NAME FITZPATRICK

,- DATE Oct. 1985 REPORT MONTH September 1985 -! COMPLETED BY- JOHN COOK l _ ,. ~ ~

TELEPHONE- 1315)342-3840:

^

D .

C

~

UH R -METHOD S O RO E OF .Y C' ' MC CAUSEIAND CORRECTIVE ACTION- _.

AU A SHUTTING LICENSEE SO PO TO NO. DATE TYPE TR S DOWN EVENT TD 0D PREVENT RECURRENCE IS O THE REPORT EE NE O N REACTOR M - E -

N N ' '

T '

NONE . s-7 ,<

~

) ..

.i e- ,

/

-I .2. 3 4 F: FORCED REASON: METHOD: EXHIBIT G.- INSTRUCTIONS' S: SCHEDULED A. EQUIPMENT FAILURE (EXPLAIN) 1-MANUAL FOR PREPARATION OF DATA.

B. MAINTENANCE OF TEST 2-MANUAL SCRAM ENTRY SHEETS FOR LICENSEE C. REFUELING 3-AUTOMATIC SCRAM EVENT REPORT (LER) FILE D. REGULATORY RESTRICTION 4-OTHER (EXPLAIN) (NUREC-0161)

E. OPERATOR TRAINING AND LICENSE EXAMINATION-F. ADMINISTRATIVE G. OPERATIONAL ERROR (EXPLAIN)

H. OTHER (EXPLAIN) 4

. , - - ,,, , . , , , - - - . -m,, ,, #. - - - , . - . , - , -..r- ~ , .,, 3 .w---e,, _o .- ,--y,.,-, ,-v- . , - r -'ct ->-r,---3 ey e' v , - - - - - - - -

s s f

4 h

-NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE  ;

SEPTEMBER 1985 The FitzPatrick plant operated at near full thermal power for this entire  ;

reporting period.

At the end of the reporting period the unit is operating at approximately 795 Mw* .

e r

F b

l i

t a

4 l

x i

e  !

+

4 9

I f

k t

t t

.- - -, ,- .- - , - e

JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE SUMMERY ,

September 1985 -

~

ACTION TAKEN REPAIR-WORK REQUEST NO. HOW CAUSE OF RESULTS OF TO PRECLUDE TIME DATE SYSTEM COMPONENT No. DETECTED MALFUNCTION MALFUNCTION RECURRENCE HOURS 850905 03 040185 OPS UNKNOWN-COULD NOT LETS ROD 10-11 TO NONE TAKEN 10 RMCS DUPLICATE PROBLEM SELECT EARLY 850910 07 039042 OPS DEFECTIVE RELAY K "A" RBM DRIVING REPLACED RELAY 2 07-RBM-A IN RELAY MODULE #1 850920 07 038947 OPS UNKNOWN DRIFTING UP PERF. IMP-7.22, 10 LPRM-44-37 SLOWLY DID NOT DRIFT 850918 07 034820 OPS AGE NO LAMPS FUNCT. REPLACED LAMPS 27 TIP-C AT INDEXER POS 850924 07 041512 OPS N/A LPRM-36-29 ("D") NO PROBLEM WAS FOUND 3 LPRM-36-29 FAILED HIGH 850924 07 034698 OPS NEEDS CALIBRATION DOWNSCALE PERFORMED A LPRM CAL 6 LPRM-36-21 ON IT 850923 07 034744 OPS BAD MED RANGE CAN'T INPUT REPLACED RESISTOR 8 LPRM-28-21 VAR. RESISTOR CURRENT, CAL TO 8v 850924 07 034837 OPS UNKNOWN DRIFTED UPSCALE CHECKED NO PROBLEM 8 LPRM-28-29 850924 07 040315 OPS PEN TENSION XY PEN NOT ADJUSTED PEN TENSION 5 R-131-1 SEATING ON PAPER 850926- 07 038916 OPS UNKNOWN TIP CHANNELS 3-7, ADJUSTED TOP, BOTTOM 8 NM-131 2-8 ABORTED CORE LIMIT 850?27 07 038914 OPS UNKNOWN XY PLOT NOT NONE ON WR. OD-1 0 R-131-1 TRACING CORR. PERF 09/25/85

l JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE SUIMERY September 1985

  • q ACTION TAKEN REPAIR WORK REQUEST NO. HOW CAUSE OF RESULTS OF. TO PRECLUDE- TIME DATE SYSTEM COMPONENT NO. DETECTED MALFUNCTION MALFUNCTION RECURRENCE LHOURS 1

850905 03 040185 OPS UNKNOWN-COULD NOT LETS ROD 10-11 TO NONE TAKEN 10 RMCS DUPLICATE PROBLEM SELECT EARLY_ _

850910 07 039042 OPS DEFECTIVE RELAY K "A" RBM DRIVING REPLACED RELAY 2-07-RBM-A IN RELAY MODULE #1 850920 07 038947 OPS UNKNOWN DRIFTING UP PERF IMP-7.22, 10 LPRM-44-37 SLOWLY DID NOT DRIFT I

l 850918 07 034820 OPS ACE NO LAMPS FUNCT. REPLACED LAMPS 27 TIP-C AT INDEXER POS l

850324 07 041512 OPS N/A _ LPRM-36-29 ("D") NO PROBLEM WAC FOUND 3 LPRM-36-29 -FAILED HIGH 850924 07 034698 OPS NEEDS CALIBRATION DOWNSCALE PERFORMED A LPRM CAL 6 LPRM-36-21 ON IT

! 850923 07 034744 OPS BAD MED RANGE CAN'T INPUT REPLACED RESISTOR 8 LPRM-28-21 VAR. RESISTOR CURRENT, CAL TO 8v 850924 07 034837 OPS UNKNOWN DRIFIED UPSCALE CHECKED W/J TOLBERT 8 LPRM-28-29 NO PROBLEM 850924 07 040315 OPS PEN TENSION XY PEN NOT ADJUSTED PEN TENSION 5 j R-131-1 SEATING ON PAPER 850926 07 038916 OPS UNKNOWN TIP CHANNELS 3-7, ADJUSTED TOP, BOTTOM 8 NM-131 2-8 ABORTED CORE LIMIT 850927- 07 038914 OPS UNKNOWN XY PLOT NOT NONE ON WR. OD-1 0 R-131-1 TRACING CORR. PERF 09/25/85 i

s

--,---y---n.3, y . ,,,-y-- ,-,,..w--cr-+--- w -,+--,w- myy,e.,-re ,, m-, . r yy s ,--,-~.y,-w--,,-,p-, ,--w.,,--.e, ,, - - -r-w ,,--,,-,v,, .. ---- --, ,,- ,.-,-,wy y-- , , , --- , --m.- rw . - , ,

^

JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE SUMMERY ,

September 1985 -

ACTION TAKEN REPAIR WORK REQUEST NO. HOW CAUSE OF RESULTS OF TO PRECLUDE TIME DATE SYSTEM COMPONENT NO. DETECTED MALFUNCTION MALFUNCTION RECURRENCE HOURS l 850913 10 039013 OPS SENSOR PLUG "A" SW ALARMS, REPAIRED PLUG AND COAX 16 LS-100A KEEPS DRY INDIC 850910 17 039027 OPS UNKNOWN PEN ISN'T REPLACED AMP. , CLEANED 6 RR-456A FOLLOWING CALIBRATED RECORDER 66-HU-3A 850906 17 038987 OPS BAD RESISTOR FAILED DOWNSCALE REPLACED RESISTOR 12 RIS-456A AND DIODE AND DIODE 850909 17 032547 OPS SLIDE WIRE, STRIP RECORDER ADJUSTED SLIDE WIRE 4 RR-459 ZERO, SPAN NOT = MTR ADJ ZERO, SPAN NEED ADJUST. RECORDER 850910 17 040203 OPS UNKNOWN "A" SLD RECORDER CALIBRATED RECORDER 4.5 RIS-452A MTR NOT W/IN 10%

850911 17 034802 OPS BROKEN DIAL 10% TOL BETWEEN REPLACED CORD, 10 RM-504 CORD MON. AND RECORDER , LUBRICATED, ADJUSTED 850918 17 040199 OPS GAIN DRIFT SPIKING OF RCRDR ADJ. GAIN ON BLACK PEN , 3 RIS-431 CALIBRATED 850905 27 040400 OPS DEFECTIVE KEYPAD 0 3H, ANALYZER ORDERED NEW PAD, 80 FCX-101 READS INCORRECT SUBSTITUTED A DG ONE 850911 27 023160 I&C UNKNOWN ALARMS DON'T TESTED AND ALARMS 4 PCX-101A,B OPERATE PROPERLY WORKED OKAY l 850917 27 032815 I&C OUT OF CAL DIFF. IN READINGS PZRFORMED CAL BY l PCX-101 (0 2ANALYZERS) ISP-30-1 i 850927 68 040330 OPS COMPUTER TIMER SPIKING 10-15 DEG ISOLATED Ah3 FIXED 56 TI-101 CAUSING ALARM TTMER l

JAMES A. FITZPATRICK NUCLEAR POWER PLANT .

MAINTENANCE SUMMERY ,

September 1985 -

ACTION TAKEN REPAIR WORK REQUEST NO. HOW CAUSE OF RESULTS OF TO PRECLUDE TIME DATE SYSTEM COMPONENT NO. DETECTED MALFUNCTION MALFUNCTION RECURRENCE HOURS 850909 71 038942 OPS INCORRECT WIRING ALARM PRESENT 64 IR-1 FOR RECORDER W/0UT BLOWN FUSE l 850925 71 022732 OPS UNKNOWN CHARCER GROUND NONE, PROBLEM 4 BC-1A DET. CIRC. HICH DISAPPEARED 850920 72 040166 OPS FAULTY ANN. CARD IND. HIGHER TEMP REPLACFD ANN. CARD 8 TI-129 THAN ACTUAL 850924 76 039020 OPS DEFECTIVE AUTO ALARM WILL NOT REPLACED RECEIVER, 14 MPX-4 CROSSOVER RECVR RESET DIG AUTO CROSSOVER l

l i

l

NEW YORK POWER AUIBORITY JAFES A. FITZPATRICK hiXIEAR POWER FIAhT ," ,

SAFE 1Y REIATED EIELTRICAL & FECHANICAL PAINIENANCE SIWARY SEPIE BER 1985 .

REPAIR NORK REQUEST i TILE DATE SYSIDI C WPGENT HOW DEIFnw CALEE OF MAIRNCTION ACITON TAKEN TO PRECIIDE RECURRENCE H(XJRS 9/8 76 22737 OPS Switch sticking Iubricated switch. 38 CP-SRP


_-----------------------------------------------------------------------------_----------e 9/4 66 35235 OPS Oil leak in A/C unit Tightened fitting. 4 IhV-3B


.. -- =---------====

_ _--------------------------------------=====___=___=-------------------------==-- = =____;

9/6 10 38928 OPS Limit switch out of Adjusted limit switch. 8 SOV-203 adjustment


----- -------------_--------------------------------------------------_--_-__-_---------_-----------e 9/6 71 22749 OPS Relay failure Replaced relay. 16 IhV-3B

--- ___ _----------------- ===____ _ _ ---------------------------==_____==---


e 9/18 24 22746 OPS Limit switch out of Adjusted limit switch. 20 EDD 1 & 2 adjustment

---. . _ - - - - - - - - - - - - - - - - - - - - = = _ _ _ = - - - - - ___ ___ - ______=-------==-___====----------------===--- ==-==___==____ __;

9/12 71 39030 OPS Iogic guard failure Replaced logic board, fuses, legs. 40 IIW-3A

-- __------ - -_- = - ----------. ---------------------------------- ---------------------------------------------e 9/24 11 39056 OPS Gasket leak Replaced cylinder head gasket. 8 P-2A


=______-------------------------------------------------------------------------------------------e 9/25 15 22634 QC Corrosion Replaced packing gland swing bolt. 2 l

--- ___=----====___'0V-102 ---------------------------------------------------------------------------------------------------------e 9/27 10 37427 OPS Torque switch Adjusted torque switch setting. 4 M W-15C


==____--=_- _-----------------------------------------------------------------------------------------------------q 9/30 71 30705 OPS Iogic card failure Replaced logic cards. 24 IhV-3A

_.. - __--- _ _-------------- ======___ -------= ___=-------------------------------------------------------------e 9/30 71 30702 OPS Circuit breaker Replaced molded case circuit breaker. 4 C153-0A5

_-- __ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - = _ _ _ = = = = _ _ _ _ _ - - - - - - - - - - - - - - - = = - - - - - - - - - - - - - - - - - - <

9/27 27 33531 OPS Bonnet gasket leak Replaced bonnet gasket. 4 PCV-122B


--------_ _=-- _=-- - =-.-

9/27 27 33418 OPS Bonnet gasket leak Replaced bonnet gasket. 4 GS-14B

. _ ---------------- ____ ==--------=_---- ___--- --------------------------------------------- =--


n

f a James C. FitaPatrick

. Nuclear Power Plant PO Boi 41 Lycomeg. New York 13093 315 342.3840 Radford J. Converse

  1. > NewWrkPbwer 4# Authority October 7, 1985 JAFP 85-0808 Director, Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission j Washington, D.C. 20555 ATTENTION: DOCUMENT CONTROL DESK

REFERENCE:

DOCKET NO. 50-333

Dear Sir:

Enclosed please find the J. A. FitzPatrick Operating Status Report for the month of September, 1985. Refueling information remains the same as previously submitted.

If there are any questions concerning this report, please contact John l Cook at (315) 342-3840, Ext. 439.

  • ,6GGCLOW RADFORD J. CONVERSE RJC JPC:mac Enclosures cc: Distribution l