JAFP-83-0817, Monthly Operating Rept for Jul 1983

From kanterella
(Redirected from JAFP-83-0817)
Jump to navigation Jump to search
Monthly Operating Rept for Jul 1983
ML20077H940
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 08/08/1983
From: Jackie Cook, Corbin McNeil
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
References
JAFP-83-0817, JAFP-83-817, NUDOCS 8308120083
Download: ML20077H940 (15)


Text

.

OPERATING DATA REPORT DOCKETNO. 50-333 DATE August 1983 COMPLETED BY J. Cook TELEPHONE (315)342-3840 OPERATING STATUS FitzPatrick Notes

1. Unit Name:
2. Reporting Pen.o d:

830701-830731 2436

3. Licensed Thermal Power (MWt):
4. Nameplate Rating (Gross MWe): 883
5. Design Electrical Rating (Net MWe):. 821
6. Maximum Dependable Capacity (Gross MWe):
7. Maximum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons:

None

9. Power Level To W!.ich Restricted. If Any (Net MWe): None
10. Reasons For Restrictions. lf Any:

This Month Yr.-to.Date Cumulative 744 5087 70224

11. Hours in Reporting Pen.o d
12. Numter Of Hours Reacter Was Critical 0 3390.9 49646.6
13. Reactor Reserve Shutdown flours 0 0 0
14. Honts Generator On-Line 0 3353 , , , _ 48368.2
15. Unit Reserve Shutdown flours 0 0 0
16. Gross Thermal Energy Generated (MWH) 0 7669944 1011'3802
17. Gross Electrical Energy Generated (MWH) 0 2598480 35033260
18. Net Electrical Energy Generated (MWH) 0 2518780 33383165
19. Unit Service Factor 0% 65.9% 68.9%
20. Unit Availability Factor 0% 65.9% 68.9%
21. Unit Capacity Factor (Using MDC Net) . 0% 61.1% 62.4%
22. Unit Capacity Factor (Using DER Net) . 0% 60.3% 57.9%
21. Unit Forced Outage Rate 0% 9.1% 15.3%
24. Shutdowns Scheduled Over Next 6 Months (Type. Date.and' Duration of Each):

l

25. If Shut Down At End Of Report Period. Estimated Dste of Startup: Late August 1983
26. Units in Test Status (Prior to Commercial Operation): Forecast Achieved '

INITIAL CRITICALITY _

INITIAL ELECTRICITY 1 COMMERCIAL OPERATION 1

8308120083 830000 FDR ADOCK 05000333 - - '

R PDR l

s AVERAGE DAILY UNjT POWER LEVEL DOCKET NO. 50-333 FitzPatrick UNIT August 1983 DATE COMPLETED BY J. Cook (315j342-3840 TELEPHONE MONT11 July 1983 DAY AVER AGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe Net) (MWe Net) 1 0 0 17 2

0 0 18 0

3 19 0 4 0 0 20 0

5 M 0 0

6 22 0 7 0 0 23 0

8 24 0 9 0 0 25 10 0 0 26 0

II 27 0 12 0 0 28 13 0

29 0 14 0 30 0 15 0 0 31 0

16

SUMMARY

The FitzPatrick plant continued it's Fifth Refueling Outage through this reporting period.

J

DOCKET NO.

50-333 UNITSIIUTDOWNS AND POWER REDUCTIONS UNIT NAME FitzPartick ,

DATE Aucust 1983 REPORT MONTil July 1983 COMPLETED BY J. Cook ,

TELEPl!ONE (315)3423840 r.

- E a

$? g j .Y E Licensee ,E r, {% Cause & Corrective No. Date g 3g g jg5 Event g? o- Action to H

$~ $ 5 ;5 c Report # MV 5"1 Prevent Recurrence e

{

c v

8 830603 s 744 c 1 N/A N/A N/A Refueling outage (cumulative hours to date 1398.6)

I 2 3 4 F: Forced Reason: Method:

S: Scheduled A Equipment Failure (Explain) Exhibit G Instructions 1-Manual for Preparation of Data B-Maintenance of Test 2 Manual Scram- Entry Sheels for Licensee C-Refueling 3 Automatic Scram.

D-Regulatory Restriction Event Report (LER) File (NUREG-4-Other (Explain) 0161)

E Operator Training & License Examination F Administrative 5 G Operational Erros (Explain)

Il-Other (Explain) Exhibit I Same Source

NEW YORK POWER AUTHORITY JAMES A. FITZPA'1 RICK NUCLEAR POWER PLANT NARRITIVE

SUMMARY

OF OPERATING EXPERIENCE JULY 1983 The refueling and maintenance outage which began June 3, 1983, continued throughout this reporting period. The major areas of work are scram discharge modification, turbine generator maintenance, LLRT testing, TORUS modification, and post accident sampling system modi-fications. Presently the outage activities are on schedule with an expected start up in late August.

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

DATE SYSTEM O EST HOW LETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE

'7/27 29 26640 LLRT Seat Leakage Machined seat, lapped disc and pilot 206 A0V-86B seat and disc 7/25 29 27294 Visual Loose Packing Freed frozen packing gland, and adjusted 16 A0V-86C 7/27 10 27365 LLRT Seat Leak Replaced valve 60 RHR-52A 7/20 10 25213 N/A No Failure Replaced motor and limit switches per 32 MOV-12A NRCB 79-01B 7/26 23 24429 Operations Seat Leakage Replaced internals 11 A0V-53 7/26 23 24430 Operations Seat Leakage Replaced seat ring 11 A0V-42 7/28 39 25791 LLRT Seat Leakage Ground & lapped 60 IAS-22 7/26 39 25916 LLRT Seat Leakage Ground & lapped 69 SAS-10 7/21 71 25058 N/A No Malfunction Preventive Maintenance 40 L-25 7/25 71 25057 N/A No Malfunction Preventive Maintenance 40 L-15 7/29 02 25849 LLRT Seat Leatrage Ground & lapped seat & plug 21 A0V-39 81 7/26 23 18330 Visual Leaking packing & Pressure Replaced pressure seal, lapped seat &

Seal disc, repacked MOV-14

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT .

SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

DATE ST SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE 7/18 03 24499 OPS Packing leak on 111 valve Replaced 111 valve 1 HCU-34-23 6/30 93 15242 N/A No Malfunction Preventive Maintenance 320 EDG B&D 6/30 08 26685 Refuel, Bridge OPS Worn bushing in mast Replaced nylon bushings and stop pins 30 7/26 27 18760 Visual Various air leaks in Tightened fittings, replaced tubing, & 32 Various drywell fittings. Replaced 14S0V-13A & B 7/22 27 25907 LLRT Seat Leak Replaced "T" ring 120 A0V-112 7/22 27 25908 LLRT Seat Leak Replaced "T" ring 120 A0V-111 7/25 27 25906 LLRT Seat Leak Replaced "T" ring 60 A0V-116 7/25 27 25905 LLRT Seat Leak Replaced "T" ring 60 A0V-115 7/25 27 18774 OPS Air Leak, bad solder joint re-soldered 1 A0V-115 7/26 23 25670 Visual Loose fitting - oil leak Tightened fitting 1 TU-2 7/26 23 25669 Visual Loose fitting - oil leak Tightened fitting 1 HPI-906

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

l WORK REQUEST # REPAIR DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE i M M ENT #

\

7/18 03 18646 OPS Pilot valve chatter Rebuilt pilot valve 1 HCU-06-23 7/18 03 18647 OPS Pilot valve chatter Rebuilt pilot valve 1 HCU-26-51 7/18 03 18859 OPS 111 Valve packing leak Replaced 111 valve 1 HCU-10-39 worn packing 7/18 03 i9427 OPS 117 Valve air leak Rebuilt 117 valve 1 HCU-26-35 7/20 12 25848 LLRT Seat Leak Ground seat & disc 60 RWC-62 7/19 27 25913 LLRT Seat Leak Replaced "T" ring 45 A0V-118 7/19 27 25912 LLRT Seat Leak Replaced "T" ring 45 A0V-ll7 3/10 34 20258 Visual Leaking packing & gaskets rurmanited during operating cycie 350 NRV-lllA 7/21 34 25794 LLRT Seat Leak Replaced Furmanite fittings, replaced 892 NRV-Illa shaft dog, ground seat and adjusted disc angle. Replaced disc 3/2 34 20259 Visual Leaking packing & gaskets Furmanited during operating cycle 129 NRV-111B 7/13 34 25797 LLRT Seat Leak Replaced Furmanite fittings, ground seat 453 NRV-lllB and disc, adjusted disc angle a

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT -

SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

DATE SYSTEM ST HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE Ti 7/22 03 19497 OPS Accumulator Leak Rebuilt accumulator 20 HCU-42-47 7/8 10 25889 LLRT Seat Leakage Replaced seats and wedge, weld built up 206 MOV-26B and machined seats, repaired Limitorque torque switch 6/30 13 25796 LLRT Seat Leakage Machined seat rings, ground seat and 202 RCI-105 disc 6/22 23 25775 LLRT Seat Leakage Ground seat and disc 150 HPI-12 7/1 23 25774 LLRT Seat Leakage Replaced disc arm, ground seat and disc 240 HPI-65 6/25 39 25781 LLRT Seat Leakage Ground seat & disc 20 BAS-04 6/24 39 25914 LLRT Seat Leakage Ground seat & disc 15 BAS-05 7/19 17 26674 OPS Worn belts Replaced belts 12 RC-456A 7/20 10 25218 N/A No Malfunction Replaced motor and limit switches per 34 MOV-89B NRCB 79-01B 7/20 10 25217 N/A No Malfunction Replaced motor & limit switches per 18 MOV-89A NRCB 79-01B 7/19 12 16282 OPS Worn packing Repacked 6 MOV-15

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT -

SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

O EST ACTION TAKEN TO PRECLUDE RECURRENCE T DATE SYSTEM g HOW DETECTED CAUSE OF MALFUNCTION Installed flanges and set valve per 80 7/18 14 $4463 N/A No Malfunction SV-20A F1-79-018 Replaced motor and limit switches per 18 7/20 15 25226 N/A No Malfunction MOV-163 NRCB 79-01B Replaced key 9 27373 OPS Key fell out 7/16 10 RHR-450 .

N/A No Malfunction Disassembled and inspected for 163 6/30 10 02355 P-1D Preventive Maintenance P&V ISI 10 7/7 46 13535 N/A No Malfunction ESW-13A 22996 N/A No Malfunction Electrical Preventive Maintenance 231 6/30 71 EDG "D" 25950 OPS Valve Binding Disassembled, repaired seat, repacked, 166 6/30 10 reassembled MOV-32 No Malfunction P&V ISI 10 7/6 46 27351 N/A ESW-6A & B Improper previous Replaced bonnet gasket 16 7/6 46 25989 Incidental ESW-9B Observation maintenance P&V ISI 6 7/7 46 20741 N/A No Malfunction ESW-13B 7/7 46 13538 N/A No Malfunction P&V ISI - Found valve full of marine 7 SWS-60A growth 25795 LLRT Seat Leakage Ground seat & disc 232 7/8 13 RCI-04

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT .

SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

DATE SYSTEM OR Q S HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T

'7/8 03 21029 N/A No Malfunction Disassembled and dried 8 CRDS-30-50 &

30-54  !

I 25783 l 6/26 20 A0V-95 LLRT Seat Leakage Replaced valve internals 20 7/12 10 27374 OPS Broken disc hanger Replaced disc hanger 49 RHR-42B 7/12 00 07639 N/A No Malfunction Installed cable markers 60 IIPCI Leak Detection Sys.

7/12 14 21525 Would not Loose seat Tightened seat 53 MOV-5B stroke shut fully l 7/8 29 25847 LLRT Seat Leakage Disassembled, machined, lapped, 180 A0V-80D reassembled 7/16 10 25214 N/A No Malfunction Replaced motor per NRCB 79-01B and PM'd 21 MOV-12B 7/14 01-125 01832 N/A No Malfunction Performed Preventive Maintenance 70 MOV-11, 12 13A & B 14A & B 15A & B 100A & B 7/14 46 26720 N/A Disassemble & inspect due Cleaned valve internals 4 SWS-60B to condition of 46-SWS-60A

__ m

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL 8 MECHANICAL MAINTENANCE

SUMMARY

DATE SYSTEM

  • O HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE E

7/13 10 25220 N/A No Malfunc. tion Replaced motor per NRCB 79-01B and PM'd 30 MOV-149A 7/16 10 25219 N/A No Malfunction Replaced motor per NRCB 79-01B and PM'd 24 MOV-148 7/12 16 16582 Incidental Operator Misadjusted Adjusted linkage 6 Drywell- Observation Emerg. Air Lock Door 6/25 20 25782 LLRT Seat leakage Replaced wedge, ground seats 79

?iOV-94 7/27 05 20163 N/A No Malfunction Performed Preventive Maintenance 30 Scram Contactors 7/23 02 24821 OPS Seat Leaks Replaced Valve Internals 22 A0V-17 & 18 l

l M

POWER AUTHORITY OF THE STATE OF NEW YORK  ;

JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

I & C JULY 1983 RESULTS OF ACTION TAKEN REPAIR WORK REQUEST # DUECTED CAUSE OF TO PRECLUDE TIME DATE SYSTEM H MALFUNCTION MALFUNCTION COMPONENT # RECURRENCE HOURS 7/1/83 63 26587 OPS Post Refuel Test Perform Friction Cal. CRD-10-31 24 l CRD-10-31 Test on Drive & 42-23 7/1/83 67 27308 OPS Input Cable Does Not Follow Checked 2 PR-46C Input Signal Calibration 7/5/83 17 17799 JIC Broken Pot Out of Replaced Pot 20 RM-251A Tolerance

~

7/6/83 11 25888 OPS Defective No Loss of Replaced Relay 15 MTR RL 67B Relay Continuity Alarm 13273 JIC Out of Out of Check Calibratioi 2 7/11/83 27 .

PS-110B Tolerance Tolerance l

7/11/83 93 26716 OPS Defective Failed to Replaced 36 EDG-D Tacometer Accelerate Tacometer 7/12/83 11 25967 OPS Set Point Drift Alarm Temp Will Ran Calibration 26 Annuciator Not Clear Check 7/12/83 93 26723 OPS Out of Adjustment Could Not Unload Adjusted & 22 EDG-D & Deftet Pot Generator Replaced Pot 7/13/83 02 17442 JIC Performance Test Need Testing Tested RTD's 38 RTD's 7/13/83 11 26307 JIC Calibration Check Calibration Perfo rmed 5 LS-70 Check ISP-82 7/14/83 93 26309 JIC Defective Air Leaks on Replaced 26 PS-11B, 11D Pressure Switch Pressures Pressure Switche!

7/15/83 76 26613 OPS Broken Fuse Spurious Alarm Replaced Fuse 6 IIolder lloider MUX #3

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

I & C JULY 1983 ACTION TAKEN REPAIR WORK REQUEST # CAUSE OF RESULTS OF TIME DATE SYSTEM H EMED MALFUNCTION TO PRECLUDE COMPONENT # MALFUNCTION RECURRENCE HOURS Pen Assembly Recorder Not Realigned 8 j 7/19/81 02-3 26682 OPS LR-98 Was Bent Working Properly Assembly & Cal. )

04216 OPS Old Age Failed Power Replaced 16 1' 7/21/83 07 SRM/IRM On/Off Indicator Switch 17828 JIC Check Perform Maint. Performed 45 7/22/83 07 IMP-7.I8 I SRM/IRM on Drives l

24937 JIC Old Age and Use Leaky Isolation Replaced 20 7/22/83 02-3 FT-64K Valve Whitney Manifold 02-3 24938 JIC Old Age and Use Leaky Isolation Replaced 20 7/22/83 Whitney Manifold FT-64P Valve 25547 JIC Defective LPRM Replaced LPRM Replaced LPRM 77 7/23/83 07 LPRM-44-29 Det. String 44-29 Det. String 44-M9 JIC Defective Wiper Broken Wiper Replaced Wiper 8 7/25/83 06 26253 PR/LR-97 Ass. & Cal. Out Arm Ass. & Cal.

7/25/83 03 26616 OPS Bulbs Damaged Indicator Lights Replaced Bulbs 10 CRD-42-31 Broken OPS Switch Stuck Relays Picked Up Open Switch & 8 7/25/33 02-3 2689@

LIS-72B For No Reason Perform ISP-3.2 26312 JIC Old Age Air Leaks Around Replaced Switch 6 7/26/83 93 PS-11A, 12C Gaskets & Calibrated Switches Out Of Cycling Open- Calibrated 32 7/26/83 14 26684 .0PS MOV-5B Tolerence .

Close-Open Cont. 14-FIS-45B mum

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

I & C JULY 1983

  1. EST #

DATE SYSTEM CO NE T g HOW DETECTED p[ALF C ON MAL CI T EC R H S 7/28/83 76 26743 OPS Defective 2H-30 Doesn't Respond Replaced 10 Smoke Det. (CT 82-2468) to Test Gas Defective Part i

l

Jame0 A. FitzPatrick

"~ Nuclear Power Plant

~ ~ P.o. Box 41 Lycormng, New York 13093 315 342.3840

  1. > NewYorkPbwer l tv Authority August 8, 1983 JAFP-83-0817 Director, Office of Inspection and Enforcement U.S. Regulatory Coramission Washington, D.C. 2'-555 ATTENTION: Docuruent Control Desk

REFERENCE:

Docket No. 50-333

Dear Sir:

.s.

The Operating Status Report for the month of July, 1983 is enclosed. The refueling information remains the same as previously submitted.

If there are any questions concerning this report, contact John Cook at (315/342-3840, Ext. 439.

Very truly yours, Corbin A. McNeill, Jr.

CAM:JPC:rv Enclosures cc: Internal Distribution .g 4