APPENDIX i.
NOTICE OF VIOLATION Gulf States Utilities Docket:
50-458
. River Bend Station Operating License:
NPF-47 During an NRC ~ inspection conducted on November 22 through December 31, 1987, one violation of NRC requirements was identified. The violation involved a failure to follow procedure for control of locked valves.
In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions,"
10 CFR Part 2, Appendix C (1987), the violation is listed below:
Failure to Follow Procedure for Control of Locked Valves River Bend Station Technical Specifications, paragraph 6.8.1.a. requires that procedures for activities identified in Appendix A of Regulatory
' Guide 1.33,~ Revision 2, February 1978, be established, implemented and maintained.
Paragraph 1.c to Regulatory Guide 1.33 requires that administrative controls for equipment control (e.g., locking and tagging)
be covered by written procedures.
Operations Support Procedure OSP-0014 "Control of Locked Valves and Devices," requires that when it is necessary to change the position of a locked valve or device,.the authorized individual will make appropriate entries in the Locked Valves / Device Manipulation Log and obtain a locked valve key from the shift supervisor or control operating foreman.
l Contrary to the above, on December 19, 1987, a nuclear equipment operator unlocked and closed the normally locked open valve,1C11-VF123, which i
isolated the condensate storage tank from the control rod drive system.
The nuclear equipment operator did not obtain the specific lock valve key from the shift supervisor or control operating foreman, nor.was an entry made in the locked valve log. This resulted in neither the shift supervisor or control operating foreman being cognizant that the valve j
position had been changed.
This is a Severity Level IV violation.
(Supplement I) (458/8729-01)
Pursuant to the provisions of 10 CFR 2.201, Gulf States Utilities is hereby required to submit a written statement or explanation to this office within-30 days of the date of the letter transmitting this Notice, a written statement or explanation in reply,. including:
(1) the reason for the violation if
!
admitted, (2) the corrective steps that have been taken and the results
-
achieved, (3) the corrective steps that will be taken to avoid further
!
violations, and (4) the date when full compliance will be achieved. Where good cause'is shown, consideration will be given to extending the response time.
y Dated at Arlington, Texas, this 22nd day of January 1938.