s APPENDIX A NOTICE OF VIOLATION

' GPU Nuclear' Corporation Docket No. 50-289 Three Mile. Island, Unit 1 License No. DPR-50-

[As a result of the inspection conducted during September 16 - October 11,.-

1985, and-in accordance with the'NRC Enforcement Policy (10 CFR 2. Appendix C

~

published by Federal Register Notice 49 FR 8583,' dated March 8, 1984), the

.following violation was identified.

Technical Specification 6.8.1 requires, in part, that procedures be implemented. The criteria listed in Maintenance Procedure 1401-18, Revision-0, June 3, 1985, " Equipment Storage Inside Class 1 Buildings,"

Enclosure 1, Section 3, states in part, " Equipment on rollers shall always be restrained....

Safe distance of any NSR/ITS [ nuclear safety.

related/important to safety) equipment from unrestrained objects...shall.

be at least twice the. height of the object all around....

Scaffolding...shall,be removed or seismically anchored...."

Contrary to the above as.of October 5, 1985, scaffolding.on unlocked roller wheels was in the diesel' generator radiator room in a Class-1.

building, at an unsafe distance of less than twice the height of-the scaffold.from the A diesel radiator (NSR equipment) and the scaffolding was not restrained or seismically anchored.

This is a Severity Level IV Violation (Supplement I).

-This notice is sent in accordance with the provisions of 10 CFR 2.201, which-requires, within 20 days of receipt of this notice, a written statement of explanation. Your statement should include:

(1) the corrective steps which; have.been taken and the results achieved; (2) corrective steps which will be taken to ' avoid further violations; and (3) the date when full compliance:will-

~be achieved. Where good cause is shown, consideration will be given to extending this response time.