IR 05000456/2015007

From kanterella
(Redirected from IR 05000457/2015007)
Jump to navigation Jump to search
IR 05000456/2015007, 05000457/2015007; on 07/29/2015 - 08/28/2015; Braidwood Station, Units 1 and 2; Routine Triennial Fire Protection Baseline Inspection (Dxs)
ML15279A618
Person / Time
Site: Braidwood  
Issue date: 10/05/2015
From: Robert Daley
Engineering Branch 3
To: Bryan Hanson
Exelon Generation Co, Exelon Nuclear
References
IR 2015007
Download: ML15279A618 (23)


Text

October 5, 2015

SUBJECT:

BRAIDWOOD STATION, UNITS 1 AND 2 - TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000456/2015007; 05000457/2015007

Dear Mr. Hanson:

On August 28, 2015, the U.S. Nuclear Regulatory Commission (NRC) completed a Triennial Fire Protection Inspection at your Braidwood Station, Units 1 and 2. The enclosed inspection report documents the inspection results, which were discussed on August 28, 2015, with Mr. J. Bashor and other members of your staff.

The inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.

The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.

NRC inspectors documented one finding of very low safety significance (Green) in this report.

This finding was determined to involve a violation of NRC requirements. However, because of its very low safety significance, and because the issue was entered into your Corrective Action Program, the NRC is treating the issue as a Non-Cited Violation (NCV) in accordance with Section 2.3.2 of the NRC Enforcement Policy.

If you contest the subject or severity of the NCV, you should provide a response within30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001, with copies to the Regional Administrator, Region III; the Director, Office of Enforcement, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001; and the NRC Resident Inspector at the Braidwood Station. In accordance with Title 10, of the Code of Federal Regulations (CFR), Part 2.390, Public Inspections, Exemptions, Requests for Withholding, of the NRC's "Rules of Practice," a copy of this letter, its enclosure, and your response (if any) will be available electronically for public inspection in the NRCs Public Document Room or from the Publicly Available Records (PARS)

component of the NRC's Agencywide Documents Access and Management System (ADAMS).

ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Robert C. Daley, Chief Engineering Branch 3 Division of Reactor Safety Docket Nos. 50-456; 50-457 License Nos. NPF-72; NPF-77

Enclosure:

IR 05000456/2015007; 05000457/2015007

REGION III==

Docket Nos:

50-456; 50-457 License Nos:

NPF-72; NPF-77 Report No:

05000456/2015007; 05000457/2015007 Licensee:

Exelon Generation Company, LLC Facility:

Braidwood Station, Units 1 and 2 Location:

Braceville, IL Dates:

July 29 through August 28, 2015 Inspectors:

A. Dahbur, Senior Reactor Inspector

D. Szwarc, Senior Reactor Inspector, Lead

R. Winter, Reactor Inspector Approved by:

Robert C. Daley, Chief Engineering Branch 3 Division of Reactor Safety

Table of Contents

SUMMARY

................................................................................................................................ 2

REPORT DETAILS

REACTOR SAFETY

1R05 Fire Protection

OTHER ACTIVITIES

4OA2 Identification and Resolution of Problems

4OA6 Management Meetings 15

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

.......................................................................................... 1

LIST OF ITEMS

OPENED, CLOSED AND DISCUSSED................................................ 1 LIST OF ACRONYMS USED.......................................................................................... 1

LIST OF DOCUMENTS REVIEWED

............................................................................... 2