IR 05000329/1978002

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-329/78-02 & 50-330/78-02 on 780208-10. No Noncompliance Noted.Major Areas Inspected:Qa & QC Re Receipt & Storage of Electrical Switchgear,Load Ctrs & Motor Control Ctrs & Installation of Electrical Switchgear
ML19326D219
Person / Time
Site: Midland
Issue date: 02/24/1978
From: Barrett P, Spessard R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML19326D213 List:
References
50-329-78-02, 50-329-78-2, 50-330-78-02, 50-330-78-2, NUDOCS 8006090643
Download: ML19326D219 (6)


Text

,

_ _. _.

. 9..

.

.

.

.

U.S. NUCLEAR REGULATORY COMMISSION

, 'v 0FFICE OF INSPECTION AND ENFORCEMENT

REGION III

Report No. 50-329/78-02; 50-330/78-02 Docket No. 50-329; 50-330 License No. CPPR-81; CPPR-82

'

Licensee:

Consumers Power Company 1945 West Parnall Road

,

i Jackson, MI 49201 Facility Name: Midland Nuclear Power Plant, Units 1 and 2 Inspection At: Midland Site, Midland, MI Inspection Conducted:- February 8, 9, and 10, 1978 ~

P.A.Barrett[.

2 /88 70 Inspector:

WW

'

'

Approved By:

R. L. Spessard, Chief G-/33 / 78 Engineering Support Section 1 Inspection Summarv--

Inspection on February 8, 9, and.10,.1978,.(Report No. 50-329/78-02;._

50-330/78-02)

Areas Inspected:h Electrical receipt and -storage-procedures;1 QA/QC -.

matters relative.to -the receipt and storagerof electricahswitchgearr load centers.and. motor control: centers;:andJ)A/QC matters. relative

.

to the installation of electrical switchgear.

The inspection involved 22 inspector-hours onsite by one NRC inspector.

Results: No items of noncompliance were identified.

.

O Boo

eoso

-

-

.

.

-

--

-

-

-..

-

-

..,

.

-

~

.

DETAILS pb Persons Contacted Principal Licensee Employees

  • B. W. Marguglio, Director Quality Assurance, Project Engineering and Construction
  • J. L. Corley, Quality Assurance Superintendent
  • B. H. Peck, Construction Supervisor
  • P. R. Kyner, Quality Assurance Supervisor, Electrical
  • P. W. Jacobsen, Quality Assurance Engineer R. G. Wollney. Quality Assurance Supervisor, Civil Bechtel Power Corporation Employees J. Milandin, Quality Assuarnce Manager G. L. Richardson, Lead Quality, Assuranca Fngineer

,

  • R. C. Hollar,-Quality _ Assurance Engineer
  • W.-L. Barclay!-Project Field. Quality Control-Engineer. _

ij D. Thompson,; Lead Qual.ity-Control Engineer

  • L. - Sto rnetta, c As s istantaroject -I.ield -Engiha a r

-

H. Foster, Assistant Project Field -Erigineer.,_. Quality Control-f-~s The inspector also contacted other personnel during the inspection ( )

including engineers and QC inspectors.

  • Denotes.those attending the exit interview.
  • Funcrinnnl or Program Areas Inspected ;

1.

Record. Review of-Implementing-Instructions-and Procedures _

a.

The RIII inspector reviewed receipt records for the following electrical-equipment:

(1) 4160 volt switchgear No. 1A05, received on Material Receiving Report- (MRR)-No. -AE0-2240, dated. December 15, 1976.

(2) 4160 volt switchgear No. lA06, received on MRR No. AEO-2239, dated December 15, 1976.

y-2-

'

--.

.

-

.~.

, -. _ - -

-.-

-

-

-

_. _

_

-

_. _ _. _.

-

.. _

_

.. -_

_ _ _ _ _.

. -.. _ _ _.

-

,..

..

%

'

"

(3)

4160 volt switchgear No. 2A05, received on MRR No. AEO-2284, dated December 22, 1976.

, ( ~)I

<

I N--

(4) 4160 volt switchgear No. 2A06, received on MRR No. AEO-2363, dated January 5, 1977.

!

(5) Eight circuit breakers for switchgear Unit No.

2A06:

Breakers M-8-1-9-A, M-8-2-9-A, M-8-3-9-A, l

M-8-4-9-A, M-8-5-9-A, M-8-6-9-A, M-8-7-9-A, and M-8-8-9-A received on MRR No. AEO-994, dated October 14, 1975.

Breaker No. M-8-6-9-A was j

properly replaced, MRR No. AEO-1639, Revision 1,

'

dated September 8, 1976, as a result of a finding identified in Nonconformance Report, NCR No. 352.

  • The Quality Verification Documents, form G-321-D,

j did not indicate the required acceptance of Bechtel j

Proj ect Engineering.

However, the deficiencies

were properly controlled on the Suspense Log Sheet.

j (6) - 480. volt. load. centers.No. 1B18 - and No. _2B18,~ received -

on MRR No.. AEO-2566,-dated Sept-ember-9,1977.

!

A (7) Seven circuit breakers for load center No._1B18:. '

.

s erial 'ndmbers dl58A2164-4202-2,'214MMl,:+21246,'4216-'4,'-4.

!

'

l-212-4,N-225-2P and -216-2, received on various MRRs., Note:e NCR-50.2.742:which-identified a

,

-

'

documentation -shortage was properly closed out prior i

to the release of the applicable breakers, j

(8) Seven circuit breakers for load center No. 2B18*

I

serial numbers 258A2166-214-JMi -216-2, -216-1,

.

i-212-3JMi -212-2JM,re212-1JMirand -225,vreceived-

'i on MRR'No. AEO.2768i3evision 1,_ dated _Septanar la,

!

1977 v Note:- NCR-No.-742 which :4daeu4 d.-a-doc -

'

-

<

umentation-shortage vas Troperly closed out prioi -

to the" release 'of-the-applicable, breakers.

(9) ~ 480 volt motor control centers No. 1B44 and No.

2B43, received on MRR No. AE0-4909, dated November 25, 1977.

i (10) 480 volt motor control centers No. 1B55 and No.

2B24, received on MRR No. AEO-5091, dated December 19, 1977.

These records were in accordance with Bechtel's Quality Control Notices Manual, Project Special Provisions Notice, PSP, G-5.1,

.,

Revision -3 and Quality Control Instruction-R-1:00, Revision,5,

,

dated September 14, 1977.

!

,

-3-

,

,.

,. - -, _.

.

..

,,

..

.

.

b.

The RIII inspe: tor reviewed storage records for the following

,f

electrical equipment:

'\\

(1)

4160 volt switchgear units No. 1A05, No. lA06, No.

2A05, and No. 2A06.

(2)

480 volt load centers No. 1B18 and No. 2B18.

The records were in accordance with Bechtel's PSP G-5.1, Revision 3; Field Procedure General, FPG No. 5.000, Revision 2.

The RIII inspector determined that ten (10)

of the seven-day Maintenance Information records, F-10-21, required per FPG No. 5.000 and completed between July 1, 1977 and January 30, 1978 for 4160 volt switchgear did not identify the specific units that were inspected.

However, the responsible Bechtel Field Engineer stated that there were only four Class IE switchgear units and that the requirements of the F-10-21 were completed for all four units for each seven-day inspection period.

The licensee stated that the_ ten-(10) records -would be. changed 'to identify the. specific. units.. inspected and_that meashres-would-be establishedtto require specific.identifioition on future"--

records.

>

_

During a phone. conversation-with the licensee-on-FebruaryJ 7,..,

1978p the' licensee stated _that_the-ten (10) records had'-been Iy changed to identify the specific units inspected and-that

\\- /

Bechtel Site QA had submitted Quality Action Request, QAR, #5D-67 to the Bechtel Site Construction Superintendent to establish requirenents-to have-specific identification on future records.

1he inspector has no further-questions on this matter.

No items of noncompliance.were identified:--

'

The~RIII-inspector reviewed =the_following_ audit _ functions.

c.

concerning receipt-and storage:---

(1)

Consumers Power Audit No. F-77-38, dated November 8, 1977.

(2) Bechtel's QA site audits of construction, field engineering and QU:

No. 14-1-3, dated April 27-30, 1976; No.14-1-4, dated November 14-15, 1976; and 14-1-5, dated May 9-31, 1977, i

i l

,Akf

\\

.

j x- /

.

-4--

-

-

_ _ _ _.

- -

.

.

,

-

.

-

-

- _ - _ _

-

,.,

..

-

.

.

The scope of the audits were commensurate with the activities; reference standards were indicated;

{g_,g

/

corrective action was taken on adverse findings; re-audits were performed; and the audits were performed within the intent of the scope.

Bechtel Power Corporation has recently adopted a Monitoring Program which replaces many of the audit functions.

The QA Quality Monitor Schedule for the first quarter of 1978 includes monitoring of receipt and storage activities.

No items of noncompliance were identified.

d.

The Rill inspector reviewed the followitig installation records for 4160 volt switchgear Units No. lA05, No. lA06, No. 2A05, and No. 2A06:

(1) QC Inspection Record, QCIR, No. C304-288W which identified the : velds wide _and inspected;._the. weld procedure No. PI-A-Lh,-Revision 0; the welder, No. E-20;"and the weld examiner.

(2)(_ThelWeld'tQualification. Maintenance. Record < for M der d e r e

E-20, indicated-compliance-with Specification 7220--U-27,

~ Weld'itig'Statidard2WQ-l',' Revi'sion"7; Fardgraph--8 ? l:1 'which' '

specified a-three. month qur.lification-limit.

(3) The weld examiner's Personnel Qualification Record dated March - 17, -1977, which indicated qualification as a Level II examiner.

(4) -QCIR1No. =E6.0-5,r Revisions O and ;14 No.;E6.0-6, Revisions;0.and:lLNo. -E6.0-7, Revisions -D andelt and

-

No.-iE6.0-8;' Revisions O_and i as required-by-Quality- =

Control Instruction-No. E-6.0, Revision 3.

No items of noncompliance were identified.

2.

Observation of Work Activities a.

The RIII inspector observed the storage of the following electrical equipment:

(1)

switchgear units No. 1A05, No. lA06, No. 2A05, and No. 2A06.

(\\

,

s- /

l-5-i

'

i

~

--

y.

p-,-c, m,

m

+-

.

-

_ ~. -_

_

__ _-

_-

-

- - _ - ~ _ _ _

.

.-

.

..>

-

l

,

'

-

.

,

,

.

.

l (2)

load centers No. 1B18 and No. 2B18.

s (3) motor control centers No. 1B44, No. 1B55, No. 2B43, and No. 2B24.

l l

'

(4) various circuit breakers.

l

'

i l

b.

The housekeeping activities of the Units 1 and 2 i

auxiliary buildings and the electrical components

!

warehouse were in accordance with Consumers Power l-Quality Assurance Program Policy No. 13 Revision 4, and ANSI N45.2.3 Section 3.2.1 (cleanness), 3.2.2 (Environment),

and 3.3 Materials and Equipment.

l No items of noncompliance were identified.

I i

'

Exit Interview

1 The inspector met with staff representatives (denoted under persons

contacted) at the conclusion of the inspection.of February 10, 1978.-

l The inspector-summarized. the scope.and findings of the -inspection. -

The : licensee acknowledged the findings as repbrted.