The following information was provided by the licensee via phone and email:
At 1744 EDT, on 7/31/2025, it was discovered both trains of control room emergency ventilation (CREVS) and control room emergency temperature system (CRETS) were simultaneously inoperable due to a damper going shut in the control room ventilation system. The damper went back to its normal open position in less than a minute. Due to this inoperability, the system was in a condition that could have prevented the fulfillment of a safety function; therefore, this condition is being reported as an eight-hour, non-emergency notification per 10 CFR 50.72(b)(3)(v)(D). There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
Multiple technical specification limiting conditions for operation (LCOs) such as
LCO 3.0.3, 3.7.8, and 3.7.9 were entered as a result of this event.