The following information was provided by the licensee via phone and email:
This is a non-emergency notification submitted in accordance with 10 CFR 21.21(d)(3)(i). A written notification in accordance with 10 CFR 21.21(d)(3)(ii) will be provided within 20 days.
On October 8, 2024, North Anna Power Station (NAPS) determined a manufacturing defect affecting the normal AC supply molded case switch for the Unit 1, 1-IV battery charger was reportable under Part 21. On July 29, 2024, the 1-IV battery charger was declared inoperable due to the AC input voltage reading approximately 250 VAC on the B-C phases and A-C phases. The A-B phase voltage was normal at 480 VAC. Troubleshooting determined the normal AC supply molded case switch was the cause of the degraded voltage due to a loose terminal connection screw on the 'C' phase load side of the contacts.
The NRC Senior Resident Inspector has been notified.
Battery Manufacturer: Ametek Solidstate Solutions
Switch Manufacturer / Model: Eaton / J250K
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
The licensee plans to inspect all battery chargers on both units to verify they don't have loose terminal screws. They are unaware of this issue affecting any other site.