The following is a summary of information received via email from Monticello Nuclear Generating Plant (
MNGP):
On March 9, 2021, GE Hitachi (GEH) issued Safety Communication SC 21-02 for PRC 21-02, Transfer of Information, Revision 0, pursuant to 10 CFR 21.21(b). Monticello Nuclear Generating Plant (MNGP) was listed as a potentially affected plant. This is a deviation from the Power Range Nuclear Monitor (PRNM) Licensing Topical Report, NEDC 32410P-A.
On May 5, 2021, MNGP completed an evaluation of this deviation and concluded this condition represents a substantial safety hazard in that the condition could result in an Average Power Range Monitoring (APRM) flux reading either below or above the Technical Specification (plus/minus) 2% band. The condition is a defect that is reportable pursuant to 10 CFR 21.21(d)(4).
The GEH NUMAC PRNMS was installed in 2009 with System Part No. 299X739NF.