ENS 53813
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
05:00 Jan 3, 2019 | |
| Title | Reactor Trip Due to Cycling of Turbine Governor Valve |
| Event Description | At 2028 [EST] on January 3, 2019, with the reactor at 85% power, the reactor was manually tripped due to cycling of Turbine Governor Valve #4. The trip was uncomplicated with all systems responding normally following the trip. Investigation of the cause of the valve cycling is ongoing.
All full-length control rods inserted fully. Auxiliary Feedwater System actuated as designed in response to low steam generator water levels. Operations stabilized the plant in Mode 3 (hot standby). Decay heat is being removed by atmospheric dump valves. This condition has no impact to the health and safety of the public. The licensee notified the NRC Senior Resident Inspector. This event is being reported pursuant to 10 CFR 50.72(b)(2)(iv)(B) and 10 CFR 50.72(b)(3)(iv)(A). |
| Where | |
|---|---|
| Palisades Michigan (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| LER: | 05000255/LER-2019-001 Reactor Protection System and Auxiliary Feedwater System Actuation Due to Turbine Governor Valve Failure |
| Time - Person (Reporting Time:+18.95 h0.79 days <br />0.113 weeks <br />0.026 months <br />) | |
| Opened: | Jacob Milliken 23:57 Jan 3, 2019 |
| NRC Officer: | Jeffrey Whited |
| Last Updated: | Jan 4, 2019 |
| 53813 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | Yes, Manual Scram |
| Before | Power Operation (85 %) |
| After | Hot Standby (0 %) |
Palisades | |
WEEKMONTHYEARENS 538192019-01-09T05:00:0009 January 2019 05:00:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip from Full Power Due to Rps Testing ENS 538132019-01-03T05:00:0003 January 2019 05:00:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Cycling of Turbine Governor Valve ENS 527642017-05-19T06:06:00019 May 2017 06:06:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Reactor Protection System Actuation While Shutdown ENS 513972015-09-16T05:17:00016 September 2015 05:17:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Turbine Trip ENS 475232011-12-14T20:10:00014 December 2011 20:10:00 Other Unspec Reqmnt, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Both Main Feedpumps ENS 472902011-09-25T19:06:00025 September 2011 19:06:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Loss of Two 120 Volt Ac Instrument Busses ENS 465642011-01-22T22:35:00022 January 2011 22:35:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Loss of Generator Load ENS 442372008-05-23T16:49:00023 May 2008 16:49:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip on Possible Generator Lockout ENS 439002008-01-13T10:21:00013 January 2008 10:21:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip After Loss of Main Feedwater Pump ENS 433512007-05-08T17:22:0008 May 2007 17:22:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip on Low Steam Generator Water Level ENS 425692006-05-11T19:14:00011 May 2006 19:14:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Actuation of Reactor Protection System Due to Failure of Control Rod to Withdraw ENS 425552006-05-04T21:50:0004 May 2006 21:50:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unexpected Reactor Protection System (Rps) Actuation During Testing ENS 419672005-09-01T14:25:0001 September 2005 14:25:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Main Generator Hydrogen Leak ENS 413192005-01-09T16:27:0009 January 2005 16:27:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Lowering Main Condenser Vacuum ENS 410022004-08-31T11:18:00031 August 2004 11:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Rps Actuation Due to Fire in 2B Condensate Pump 2019-01-09T05:00:00 | |