ENS 52370
ENS Event | |
|---|---|
17:05 Nov 16, 2016 | |
| Title | Technical Support Center Ventilation System Inoperable |
| Event Description | At 1105 CST on Wednesday, November 16th, 2016, the Dresden Nuclear Power Station (DNPS) Technical Support Center (TSC) Emergency Ventilation System was emergently declared inoperable due to an unplanned loss of the pneumatic air supply compressor. The loss of the air compressor resulted in the emergency air filtration unit flow control damper failing to the full open position. In this condition, the emergency air filtration unit could exceed the max flow rate of 1100 SCFM and the max differential pressure of 6 inches H2O at rated flow rate resulting in degraded performance. This results in a potential loss of protective action function provided by the emergency ventilation filtration system and could impede the ability to perform Emergency Assessments should a radiological emergency event occur requiring the system to be in service.
Actions are being taken to repair the pneumatic air system to restore functionality of the TSC ventilation system. In the interim, contingency actions are being developed to manually control the emergency air filtration unit flow control damper in a degraded condition. In the event that ventilation cannot be restored, Station Procedures provide guidance to relocate the TSC to an alternate facility. This event is being reported under 10 CFR 50.72(b)(3)(xiii), 'Any event that results in a major loss of emergency assessment capability, offsite response capability, or offsite communications capability (e.g., significant portion of control room indication, Emergency Notification System, or offsite notification system).' The licensee has notified the NRC Resident Inspector.
The pneumatic air supply compressor has been repaired and tested satisfactorily. The Technical Support Center is now considered operable. The licensee will be notifying the NRC Resident Inspector. Notified R3DO (Peterson). |
| Where | |
|---|---|
| Dresden Illinois (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
| Time - Person (Reporting Time:+1.28 h0.0533 days <br />0.00762 weeks <br />0.00175 months <br />) | |
| Opened: | Rick Gallagher 18:22 Nov 16, 2016 |
| NRC Officer: | Bethany Cecere |
| Last Updated: | Nov 17, 2016 |
| 52370 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 563612023-02-06T11:30:0006 February 2023 11:30:00
[Table view]10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communications and Assessment Capabilities ENS 525422017-02-08T14:51:0008 February 2017 14:51:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Emergency Ventilation System Inoperable ENS 523702016-11-16T17:05:00016 November 2016 17:05:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Ventilation System Inoperable ENS 521072016-07-20T16:30:00020 July 2016 16:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Ventilation Out-Of-Service for Planned Preventative Maintenance ENS 520982016-07-18T20:00:00018 July 2016 20:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Offsite Communications Capability ENS 516642016-01-20T10:00:00020 January 2016 10:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Out of Service for Planned Preventative Maintenance ENS 512322015-07-15T05:04:00015 July 2015 05:04:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Out of Service Due to Planned Maintenance ENS 511732015-06-23T08:42:00023 June 2015 08:42:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Emergency Preparedness Capability Due to Phone System Failures ENS 507592015-01-26T09:55:00026 January 2015 09:55:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Out of Service for Planned Preventative Maintenance ENS 502892014-07-21T10:25:00021 July 2014 10:25:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Out of Service for Planned Preventative Maintenance ENS 497872014-02-03T06:43:0003 February 2014 06:43:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Emergency Ventilation System Out of Service for Planned Maintenance ENS 491882013-07-14T21:00:00014 July 2013 21:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Out of Service for Planned Preventative Maintenance ENS 471192011-08-03T09:00:0003 August 2011 09:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Out of Service for Planned Preventative Maintenance ENS 469012011-05-28T14:12:00028 May 2011 14:12:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Inbound Phone Call Capabilities on Commercial and Fts Lines ENS 461062010-07-19T04:30:00019 July 2010 04:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communications Capability Due to Planned At&T Fiber Optic Cable Outage ENS 459512010-05-24T22:25:00024 May 2010 22:25:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Declared Inoperable ENS 455502009-12-08T19:28:0008 December 2009 19:28:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Out of Service for Planned Preventative Maintenance ENS 441302008-04-09T21:15:0009 April 2008 21:15:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of All Ens Telephone Lines on Site After Maintenance ENS 407462004-05-14T00:15:00014 May 2004 00:15:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Ens and Commercial Phone Lines to Control Rooms 2023-02-06T11:30:00 | |