ENS 51680
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
03:41 Jan 24, 2016 | |
| Title | Manual Scram Due to Lowering Intake Level |
| Event Description | At 2241 [EST] on 1/23/2016, James A FitzPatrick inserted a manual scram from 89 percent power due to lowering intake level. Following the successful scram, a residual transfer occurred, resulting in a loss of the non-vital busses, loss of all Circulating Water Pumps, and a manual closure of the Main Steam Isolation Valves (MSIVs). The cause of the residual transfer is unknown.
RPV [Reactor Pressure Vessel] level shrink during the scram resulted in a successful Group 2 isolation. Reactor Vessel [level] and pressure are being maintained with the High Pressure Coolant Injection System which was manually started. A cooldown is in progress. FitzPatrick will proceed to Mode 5 until the cause is identified and corrected. The Emergency Diesel generators auto started as a result of the loss of power to the non-vital busses. Offsite power remained available throughout the event. Operators are controlling pressure manually via the relief valves. FitzPatrick will notify the Public Service Commission of the event. The NRC Resident Inspector was notified. |
| Where | |
|---|---|
| FitzPatrick New York (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation | |
| LER: | 05000333/LER-2016-001 Regarding System Actuations During Manual Scram in Response to Frazil Ice Blockage and Residual Transfer |
| Time - Person (Reporting Time:+-2.52 h-0.105 days <br />-0.015 weeks <br />-0.00345 months <br />) | |
| Opened: | Craig Lohr 01:10 Jan 24, 2016 |
| NRC Officer: | Daniel Mills |
| Last Updated: | Jan 24, 2016 |
| 51680 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | Yes, Manual Scram |
| Before | Power Operation (89 %) |
| After | Hot Shutdown (0 %) |
WEEKMONTHYEARENS 573332024-09-23T11:20:00023 September 2024 11:20:00
[Table view]10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram Due to Generator Trip ENS 545032020-01-31T10:55:00031 January 2020 10:55:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Scram Due to Main Turbine Trip ENS 520422016-06-24T16:15:00024 June 2016 16:15:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Scram Due to Reactor Recirculation Pumps Degradation ENS 516802016-01-24T03:41:00024 January 2016 03:41:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Scram Due to Lowering Intake Level ENS 485012012-11-11T08:55:00011 November 2012 08:55:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Reactor Scram Due to Turbine Trip Followed by Unusual Event Declared Due to Main Transformer and Bus Duct Fire ENS 484792012-11-05T02:53:0005 November 2012 02:53:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Scram from Full Power Following Turbine Trip ENS 437522007-10-28T04:59:00028 October 2007 04:59:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Scram Due to Lowering Intake Level ENS 436352007-09-12T10:35:00012 September 2007 10:35:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Scram Following Intake Structure Traveling Screen Fouling ENS 419872005-09-14T06:13:00014 September 2005 06:13:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram on Low Reactor Vessel Water Level During Planned Maintenance ENS 400722003-08-14T20:26:00014 August 2003 20:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power. 2024-09-23T11:20:00 | |