At 0336 [CDT] on 5/21/14, during activities to isolate the preferred power supply for wiring modification, all control room
annunciators cleared and lost power due to a disconnect switch failure associated with the alternate power supply. The normal power supply was restored at 0349 [CDT] to restore the
annunciators to functional status. During the brief period of time the
annunciators were unavailable, redundant assets as described in existing station documentation and/or the control room alarm typer remained functional along with the station computer alarms and
Safety Parameter Display System to provide backup assessment capability.
This event was previously determined to not be reportable, however, following additional review of the significance this is reportable. The NRC Resident has been notified of the event. The late reporting of this event has been entered into the Corrective Action Program.
The licensee notified the State of
Ohio as well as Lucas and Ottawa counties.