ENS 49449
ENS Event | |
|---|---|
12:30 Oct 18, 2013 | |
| Title | Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment |
| Event Description | At 0830 EDT, Calvert Cliffs Nuclear Power Plant determined that the following was an unanalyzed condition:
As a result of recent industry operating experience (OE 305419) regarding the impact of unfused direct current (DC) ammeter circuits in the Control Room, Calvert Cliffs performed a review of ammeter circuitry. The review determined the described condition to be applicable to Calvert Cliffs resulting in an unanalyzed condition with respect to 10 CFR 50 Appendix R analysis requirements. The wiring design for the ammeters contains a shunt in the current flow from each DC battery or charger. The ammeter wiring attached to the shunt does not contain fuses. It is postulated that a fire in the Unit 1 Cable Spreading Room could cause one of the ammeter wires to hot short to ground. Concurrently, the fire causes another DC wire from the opposite polarity on the same battery to also short to ground. This would cause a ground loop through the unfused ammeter cable. The potential exists that the cable could heat-up causing a secondary fire in the Unit 2 Cable Spreading Room. The secondary fire could adversely affect safe shutdown equipment and potentially cause the loss of the ability to safely shutdown per 10 CFR 50 Appendix R. This condition is reportable as an eight hour ENS report in accordance with 10 CFR 50.72(b)(3)(ii)(B) as an unanalyzed condition. Compensatory measures (fire watches) have been implemented for affected areas of the plant. The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Calvert Cliffs Maryland (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| Time - Person (Reporting Time:+1.58 h0.0658 days <br />0.0094 weeks <br />0.00216 months <br />) | |
| Opened: | Dan Geneva 14:05 Oct 18, 2013 |
| NRC Officer: | Donald Norwood |
| Last Updated: | Oct 18, 2013 |
| 49449 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 536632018-10-11T04:00:00011 October 2018 04:00:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Air Start Solenoid Closure Failure ENS 534012018-05-14T17:05:00014 May 2018 17:05:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Saltwater System Non-Conforming with Licensing Basis for Tornado Generated Missiles ENS 509612015-04-07T16:45:0007 April 2015 16:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Dual Unit Automatic Reactor Trips Due to a Voltage Transient Resulting in Generator Trips ENS 507522015-01-22T22:45:00022 January 2015 22:45:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Heat Exchanger Lineup Could Exceed Design Basis Temperatures ENS 498892014-03-10T20:53:00010 March 2014 20:53:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 494492013-10-18T12:30:00018 October 2013 12:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 483672012-10-03T04:10:0003 October 2012 04:10:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to High Energy Line Break Barrier Being Partially Open ENS 476192012-01-23T18:00:00023 January 2012 18:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Breach in High Energy Line Break Barrier ENS 475122011-12-08T22:55:0008 December 2011 22:55:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Potentially Could Affect the Common Control Room ENS 474132011-11-03T22:00:0003 November 2011 22:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Diesel Generator Starting Air Not Compliant with Appendix R Requirements ENS 438302007-12-08T05:50:0008 December 2007 05:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Reactor Power Inadvertently Increased Above Accident Analysis Limit 2018-05-14T17:05:00 | |