| Title | Alert Declared Due to Toxic Gas Build Up Following an Emergency Diesel Generator Test Run |
| Event Description | On April 25, 2012 at 2106 CDT, Point Beach Nuclear Plant declared an Alert under EAL HA3.1 due to toxic gas in a vital area. During a maintenance run on the plant's emergency diesel generator, diesel exhaust caused the concentration of carbon monoxide in an adjacent vital area room (Plant Instrument Air Compressor Room) to exceed OSHA IDLH (Immediately Dangerous to Life and Health) levels. The diesel was immediately secured and the room was ventilated. There were no personnel injuries and no public health and safety issues associated with this event.
The licensee notified the NRC Resident Inspector. Notified DHS SWO, FEMA, USDA, DOE, DHS NICC, HHS AND EPA.
The Alert at Point Beach was terminated at 2314 CDT on 04/25/12. The licensee notified the NRC Resident Inspector. Notified R3DO (Lara), NRR EO (Lubinski), IRD (Scott via email only). Notified DHS SWO, FEMA, USDA, DOE, DHS NICC, HHS, EPA, and Nuclear SSA (email only).
On April 25, 2012, at 2106 CDT, Point Beach Nuclear Plant declared an Alert under EAL HA3.1 (EN#47863) due to toxic gas in a vital area. During a maintenance run on the plant's emergency diesel generator, diesel exhaust caused the concentration of carbon monoxide in an adjacent vital area room (Plant Instrument Air Compressor Room) to exceed OSHA IDLH (Immediately Dangerous to Life and Health) levels. The diesel was immediately secured and the room was ventilated. There were no personnel injuries and no public health and safety issues associated with this event. This retraction is based on the fact that station personnel incorrectly used an Alert trigger value for toxic gas concentration that was well below the actual value which would pose an immediate danger to life and health. In a subsequent evaluation, NextEra concluded that the station used the carbon monoxide (CO) OSHA limits (OSHA Permissible Exposure Limit 8-hour time weighted average of 50 ppm to 200 ppm short term exposure limit) that are normally monitored for confined spaces. The recommended CO limit value of 1200 ppm was determined to be the correct IDLH for the plant air compressor room, the actual reading in the room was 124 ppm. The plant air compressor room is not a confined space, and is not required to be monitored to the same limits as a confined space. Therefore, the Emergency Notification made on April 25, 2012, documenting an Alert due to toxic gas in a vital area is retracted. The NRC Resident Inspector has been notified. Notified R3DO (Kunowski). |
| Where | |
|---|---|
| Point Beach Wisconsin (NRC Region 3) | |
| Reporting | |
| Emergency class: | Alert |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
| Time - Person (Reporting Time:+-3.4 h-0.142 days <br />-0.0202 weeks <br />-0.00466 months <br />) | |
| Opened: | Alex Rivas 22:42 Apr 25, 2012 |
| NRC Officer: | Vince Klco |
| Last Updated: | Aug 2, 2012 |
| 47863 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 530042017-10-09T12:37:0009 October 2017 12:37:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declaration for Toxic Gas Spill ENS 526272017-03-20T21:20:00020 March 2017 21:20:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared for Fire Alarm in Containment ENS 494332013-10-13T14:46:00013 October 2013 14:46:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration ENS 487222013-02-06T17:43:0006 February 2013 17:43:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event - Loss of Offsite Power to Essential Buses for Greater than 15 Minutes ENS 478632012-04-26T02:06:00026 April 2012 02:06:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared Due to Toxic Gas Build Up Following an Emergency Diesel Generator Test Run ENS 474782011-11-27T08:38:00027 November 2011 08:38:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to a Loss of Offsite Power During Switching Operations ENS 443362008-07-04T00:45:0004 July 2008 00:45:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Sodium Hypochlorite Leak ENS 439072008-01-15T20:15:00015 January 2008 20:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Unusual Event - Loss of Offsite Power ENS 429122006-10-17T02:26:00017 October 2006 02:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event - Identified Leakage Greater than 25 Gpm 2017-03-20T21:20:00 | |