In accordance with 10CFR50.73(a)(2)(iv)(A), this telephone notification reports an
invalid actuation of the Unit 2 train B (2B)
Emergency Diesel Generator (
DG) on February 1, 2012, at
2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br />. At the time of the event, Unit 2 was in Mode 5, Cold Shutdown. The 2B
DG was being prepared for an operability surveillance following a planned work window. As part of this surveillance, a chart recorder is installed to monitor key
DG parameters to include the
DG start signal. When the second
lead was connected across the starting relay contact test point, a
DC ground alarm was received and the 2B
DG started. The engine functioned successfully and as expected, the 2B
DG did not automatically connect to its safety bus, since no bus under-voltage signal was present. The cause is attributed to a faulty chart recorder in that an inadvertent ground resulted in the actuation of the starting relay. This condition was entered into the corrective action program.
The licensee notified the NRC Resident Inspector.