The following was received from the State of
Tennessee via facsimile:
A pharmacy technician noted that the exhaust fan connected to the I-131 glove box was not working. Maintenance was contacted and found a broken fan belt which was repaired the same day. Up to 35% of the air exhaust of the I-131 vapor was not available for dilution. On 8/28/09, it was noted the effluent concentration of I-131 was over the limit of state regulations. It was immediately reported to the Radiation Safety Officer. An investigation revealed a bolus of I-131 was released through the ventilation system. Minor release in the room but the continuous air concentration in the pharmacist's breathing zone remained under regulatory limits. Surveys of the room revealed three locations of fixed contamination which were covered with cardboard and allowed to decay to background. All staff bioassays were below detectable limits.
Event Report ID No.: TN-09-110