At 1905 EST,
Vermont Yankee declared a Notice of an Unusual Event (
NOUE) based on
EAL SU 4.1, loss of 75% of the control room
annunciators associated with safety related systems for greater than 15 minutes. Around 1845 EST, several
annunciators were received and based on the failure mode, the licensee conservatively estimated that greater than 75% of the
annunciators in the control room were
inoperable.
The licensee will notify the NRC Resident Inspector.
- * * NOTIFIED BY BOB VITA TO BILL HUFFMAN AT 2037 EST ON 8/29/10 * * *
The licensee determined that the cause of the annunciator loss was a blown fuse. The fuse was replaced and the annunciators were restored without further issues. Vermont Yankee exited the NOUE at 2028 EST.
The licensee has notified State authorities and will notify NRC Resident Inspector.