ENS 45690
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
14:00 Feb 9, 2010 | |
| Title | Offsite Notification to South Carolina Dhec Concerning Tritium Found in Ground Water |
| Event Description | Event Description: Ground water monitoring wells were installed on the Oconee site and initially sampled in 2008 in support of the Nuclear Energy Institute (NEI) Ground Water Protection Initiative (NEI 07-07). As part of an on-going investigation, a number of new monitoring wells have been installed and additional wells are in progress at Oconee. On February 8, 2010, Oconee was notified by the Duke Energy Environmental Lab that samples taken on January 26, 2010, from monitoring wells GM-7R and GM-7DR displayed tritium levels of 24,400 pCi/l and 35,400 pCi/l respectively, triggering the communication protocol of the NEI initiative. The threshold for initiating the communication protocol is 20,000 pCi/l. There is no public or plant worker risk associated with the GM-7R and GM-7DR well samples. Wells GM-7R and GM-7DR are not drinking water sources and therefore, there is no potential dose to the public or plant workers. Samples from surrounding monitoring wells indicate that tritium in ground water has not migrated off the plant site. Duke is continuing to investigate the source of tritium in wells GM-7R and GM-7DR. Tritium levels in samples from the remaining wells are below the communication protocol threshold. The licensee plans to notify the South Carolina DHEC state officials and local stakeholders of the sample results.
Initial Safety Significance: There is no safety significance due to the tritium identified in ground water at Oconee. The subject wells are not drinking water sources, and there is no indication tritium has migrated off the Oconee site in the ground water. Corrective Action(s): The source of tritium in the ground water at Oconee is not understood at this time. Duke is continuing an investigation to identify the source and implement a corrective action plan. The licensee will issue a press release and has informed the NRC Resident Inspector. |
| Where | |
|---|---|
| Oconee South Carolina (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release | |
| Time - Person (Reporting Time:+-4.05 h-0.169 days <br />-0.0241 weeks <br />-0.00555 months <br />) | |
| Opened: | Bob Meixell 09:57 Feb 9, 2010 |
| NRC Officer: | Steve Sandin |
| Last Updated: | Feb 9, 2010 |
| 45690 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 3 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 579172025-09-10T19:40:00010 September 2025 19:40:00
[Table view]10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification ENS 568302023-11-03T19:30:0003 November 2023 19:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification - Press Release ENS 509172015-03-23T11:17:00023 March 2015 11:17:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Death of Employee ENS 502882014-07-20T23:53:00020 July 2014 23:53:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Small Keowee Hydroelectric Station Oil Discharged to the Keowee River ENS 500932014-05-07T18:50:0007 May 2014 18:50:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Voluntary Notification to Offsite Government Agencies Due to Leak of Water Containing Low Level Tritium Concentration in Accordance with Nei Initiative 07-07 ENS 487892013-02-27T01:30:00027 February 2013 01:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Sewage Spill in the Turbine Building That Discharged to the Keowee River ENS 477852012-03-24T22:10:00024 March 2012 22:10:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Sewage Spill in the Turbine Building That Discharges to the Keowee River ENS 473862011-10-27T04:00:00027 October 2011 04:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Damaged Packaging Containing Radioactive Material ENS 471562011-08-16T10:00:00016 August 2011 10:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to an On-Site, Non-Work Related, Fatality ENS 467732011-04-21T18:05:00021 April 2011 18:05:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Inadvertent Sewage Discharge ENS 456902010-02-09T14:00:0009 February 2010 14:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to South Carolina Dhec Concerning Tritium Found in Ground Water ENS 444832008-09-12T01:35:00012 September 2008 01:35:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Work-Related Fatality ENS 443172008-06-24T18:00:00024 June 2008 18:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Osha ENS 436152007-09-06T04:30:0006 September 2007 04:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Oil Spill at Keowee Hydro Station 2025-09-10T19:40:00 | |