ENS 44858
ENS Event | |
|---|---|
05:00 Jan 28, 2009 | |
| Title | Notification to Sc-Dhec Concerning Exceedance of Biological Oxygen Demand (Bod5) Limit |
| Event Description | On January 28, 2009, the composite sample from our waste treatment facility analyzed by our NPDES certified vendor laboratory indicated that wastewater discharged from the Westinghouse Columbia plant (to Congaree River) during the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period contained 60.8 pounds of BOD5 (56 mg/l BOD5) which exceeded the Daily Maximum Permit Limit of 60 # of BOD5 per day. The daily average for BOD5 discharges during January was approximately 23.6 pounds per day and is within permit limitations (30 #/D). Other BOD5 results for the month were less than 12 # BOD5/day.
Following recognition of the problem on 2/3/09, Westinghouse immediately responded to evaluate the waste treatment facility including the sanitary package plant, the sanitary lagoon, process lagoons, and final discharge tanks. All systems were operating properly and producing clear effluent with no unusual odors or solids present. Waste treatment operations logs were inspected and no unusual problems were noted. All dissolved oxygen results for the month of January were greater than 10.0 mg/l indicating satisfactory performance of the wastewater treatment facility. Visual analysis of the entire waste treatment facility on 2/3/09 indicated that all processes were operating normally and no problems were being experienced. Investigation samples for BOD5 were collected on 2/3/09 from process source locations prior to the final discharge. All precursor investigation BOD5 samples were analyzed to contain less than 11.0 mg/l BOD5. Based on our information and discussions with [South Carolina - Department of Health and Environmental Control (SC-DHEC)], we are reporting the exceedance data, but believe the sample was anomalous (or contaminated) due to the lack of any elevated source of BOD5 (based on investigation samples) or process upsets noted in the entire waste treatment facility. Westinghouse remains deeply committed to continuous compliance with all NPDES requirements. |
| Where | |
|---|---|
| Westinghouse Electric Corporation Columbia, South Carolina (NRC Region 2) | |
| License number: | SNM-1107 |
| Reporting | |
| Part 70 App A (C) | |
| Time - Person (Reporting Time:+491.55 h20.481 days <br />2.926 weeks <br />0.673 months <br />) | |
| Opened: | Ralph Winiarski 16:33 Feb 17, 2009 |
| NRC Officer: | Pete Snyder |
| Last Updated: | Feb 17, 2009 |
| 44858 - NRC Website | |
Westinghouse Electric Corporation with Part 70 App A (C) | |
WEEKMONTHYEARENS 576412025-04-01T04:15:0001 April 2025 04:15:00
[Table view]Part 70 App A (C) Concurrent Report - Offsite Notification Due to NON-RADIOLOGICAL Medical Transport ENS 562322022-11-17T16:50:00017 November 2022 16:50:00 Part 70 App A (C) Offsite Notification Due to Injured Employee Being Admitted to Hospital ENS 543312019-10-14T04:00:00014 October 2019 04:00:00 Part 70 App A (C) Three Individuals Sent to Hospital Due to Concerns After Completion of Maintenance Work ENS 537462018-11-19T05:00:00019 November 2018 05:00:00 Part 70 App A (C), 10 CFR 70.50(b)(3) Contaminated Worker Requiring Medical Treatment ENS 535042018-07-12T04:00:00012 July 2018 04:00:00 Part 70 App A (C) Offsite Notification to South Carolina Department of Health and Environmental Control ENS 524402016-12-16T12:00:00016 December 2016 12:00:00 Part 70 App A (C) Offsite Notification of an Industrial Safety Incident ENS 514252015-09-25T08:30:00025 September 2015 08:30:00 Part 70 App A (C) Offsite Notification Due to Employees Injured by Non-Radioactive High Temperature Water and Steam ENS 477322012-03-11T13:00:00011 March 2012 13:00:00 Part 70 App A (C) Offsite Notification to State Required by Npdes Permit for a Bypass Discharge ENS 459192010-05-12T16:20:00012 May 2010 16:20:00 Part 70 App A (C) Offsite Notification ENS 448582009-01-28T05:00:00028 January 2009 05:00:00 Part 70 App A (C) Notification to Sc-Dhec Concerning Exceedance of Biological Oxygen Demand (Bod5) Limit ENS 445692008-10-15T18:40:00015 October 2008 18:40:00 Part 70 App A (C) Offsite Notification to Sc-Dhec ENS 443662008-07-25T20:00:00025 July 2008 20:00:00 Part 70 App A (C) State Agency Notified of Discharge of Ammonia Exceeding State Limits ENS 437992007-11-20T20:00:00020 November 2007 20:00:00 Part 70 App A (C) Tamper Seals Broken on Uf6 Shipping Canister ENS 437322007-10-17T22:30:00017 October 2007 22:30:00 Part 70 App A (C) Offsite Notification Due to Transportation Package Requirements Not Being Properly Met 2025-04-01T04:15:00 | |