| Title | Unusual Event - Internal Flooding in Service Water Intake Structure |
| Event Description | Licensee entered into Unusual Event due to EAL 9.7.1, which is internal flooding in excess of sump handling capability affecting safety related areas of the plant.
Failure of the sump pump level switches in the active Service Water Intake Structure (SWIS) bay resulted in several inches of water on the floor and receipt of a SWIS 'Pump Room Flooded' alarm. There was no excessive leakage from the service water system and no damage to safety related systems in the room. Sump pumps are now operating and level in the SWIS bay is lowering. All safety related systems are operable except for the 'A' Diesel Area Panel Room Supply Fan, which is cleared and tagged for scheduled maintenance. Licensee will notify the NRC Resident Inspector and has notified the states of New Jersey and Delaware and the local township.
At 0736 EDT the licensee terminated the Unusual Event. The SWIS sump pumps are working as designed using the sump pump level switch. The sump pumps are running and lowering level (approximately 0.75 inches remains on the SWIS floor). The licensee has notified the State of New Jersey and Delaware Emergency Response organizations and will be notifying the NRC Resident Inspector. Notified R1DO (Powell), NRR EO (Thorp), IRD MOC (McDermott), DHS (McKentry), and FEMA (Sweetser). |
| Where | |
|---|---|
| Hope Creek New Jersey (NRC Region 1) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
| Time - Person (Reporting Time:+-3.23 h-0.135 days <br />-0.0192 weeks <br />-0.00442 months <br />) | |
| Opened: | Glen Canady 05:33 Aug 28, 2008 |
| NRC Officer: | John Knoke |
| Last Updated: | Aug 28, 2008 |
| 44442 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 581682026-02-23T07:09:00023 February 2026 07:09:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event - Loss of All Offsite Power ENS 531012017-11-30T21:57:00030 November 2017 21:57:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Earthquake ENS 489472013-04-19T19:18:00019 April 2013 19:18:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Declared Due to Inability to Confirm a Fire in the Protected Area within 15 Minutes ENS 471922011-08-23T18:00:00023 August 2011 18:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of an Unusual Event Due to a Seismic Event ENS 444422008-08-28T08:47:00028 August 2008 08:47:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event - Internal Flooding in Service Water Intake Structure ENS 417532005-06-07T18:37:0007 June 2005 18:37:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Unidentified Drywell Leakage Greater than 10 Gpm ENS 411552004-10-28T14:03:00028 October 2004 14:03:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to a Toxic Gas Release in the Security Center 2026-02-23T07:09:00 | |