ENS 43834
ENS Event | |
|---|---|
20:02 Oct 15, 2007 | |
| Title | Inadvertent Start of Emergency Diesel Generator D2 |
| Event Description | This notification is being made to report an invalid system actuation in accordance with 10 CFR 50.73(a)(2)(iv)(A). Prairie Island Nuclear Generating Plant (PINGP) Train B Unit 1 emergency diesel generator (D2) started due to an invalid system actuation.
On 10/15/07, at approximately 1402 hours0.0162 days <br />0.389 hours <br />0.00232 weeks <br />5.33461e-4 months <br /> (CDT), with PINGP Unit 1 in MODE 1, D2 started inadvertently during an air roll. The inadvertent start of D2 Diesel Generator occurred while the diesel was declared inoperable (Technical Specification LCO 3.8.1 CONDITION B was entered at 0916 10/15/07 and exited at 1433 10/15/07). Normally, an air roll uses starting air to turn the engine one revolution to clear oil from the top piston of the D2 opposed piston diesel engine. The D2 control switch is to be in pullout per procedure. However, due to operator error, the D2 control switch was not in pullout during the air roll and D2 started during the attempted air roll. D2 did not automatically connect to the associated emergency bus (Bus 16), because no bus undervoltage signal was present and the supply breaker was open. The Train A diesel generator (D1) remained operable during this event and the Train A EDG was able to provide power to the Train A emergency bus (Bus 15), if necessary. The invalid start was entered into the PINGP corrective action program. The preliminary investigation of this event determined that the D2 start was caused by operator error - the outplant operators performing the air roll missed a step in the procedure that directed calling the control room to verify the D2 control switch in pullout prior to conducting the air roll. Corrective actions for this event are in progress and are being tracked via the corrective action program. The licensee will notify the NRC Resident Inspector. |
| Where | |
|---|---|
| Prairie Island Minnesota (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.73(a)(1), Submit an LER, Invalid Actuation | |
| Time - Person (Reporting Time:+1360.92 h56.705 days <br />8.101 weeks <br />1.864 months <br />) | |
| Opened: | Gene Dammann 13:57 Dec 11, 2007 |
| NRC Officer: | Mark Abramovitz |
| Last Updated: | Dec 11, 2007 |
| 43834 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 582102026-01-26T19:43:00026 January 2026 19:43:00
[Table view]10 CFR 50.73(a)(1), Submit an LER Invalid System Actuation ENS 531352017-10-26T01:50:00026 October 2017 01:50:00 10 CFR 50.73(a)(1), Submit an LER Invalid Actuation of Cooling Water System ENS 531342017-10-23T13:56:00023 October 2017 13:56:00 10 CFR 50.73(a)(1), Submit an LER Invalid Actuation of Emergency Diesel Generator ENS 507022014-10-26T08:40:00026 October 2014 08:40:00 Other Unspec Reqmnt, 10 CFR 50.73(a)(1), Submit an LER 60-Day Optional Telephone Notification of Invalid Actuation of Residual Heat Removal Pump ENS 438342007-10-15T20:02:00015 October 2007 20:02:00 10 CFR 50.73(a)(1), Submit an LER Inadvertent Start of Emergency Diesel Generator D2 2026-01-26T19:43:00 | |