ENS 43651
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
17:00 Sep 18, 2007 | |
| Title | Shield Building Ventilation System Inoperable |
| Event Description | At 1200 a condition associated with the Shield Building Ventilation Train A damper controller was identified that rendered the system inoperable. This condition was identified while Shield Building Ventilation Train B was inoperable for routine maintenance. Consequently, both trains of Shield Building Ventilation were simultaneously inoperable. Technical Specification TS 3.6.c requires a reactor shutdown within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> of this condition. The routine maintenance on Shield Building Ventilation Train B was completed and retest performed at 1331. Shield Building Ventilation Train B was returned to operable and Technical Specification requirements to shutdown were exited. The plant remains in a 7 day Action Statement per TS 3.6.c with Shield Building Ventilation Train A inoperable .
This event is reportable under 10CFR50.72(b)(3)(v)(C), 'Any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to control the release of radioactive material.' I&C technician was walking down a different job in the area and noticed a light illuminated on the A control board which should not have been illuminated. Additional investigation revealed an electrical condition would have prevented the modulation of the dampers thereby rendering the A train system inoperable. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Kewaunee Wisconsin (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material | |
| LER: | 05000305/LER-2007-009 Re Both Trains of Shield Building Ventilation Inoperable Due to Damper Controller Failure on One Train While Second Train Inoperable for Routine Maintenance |
| Time - Person (Reporting Time:+-0.52 h-0.0217 days <br />-0.0031 weeks <br />-7.12296e-4 months <br />) | |
| Opened: | Tim Bunkelman 16:29 Sep 18, 2007 |
| NRC Officer: | Joe O'Hara |
| Last Updated: | Sep 18, 2007 |
| 43651 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |