ENS 42173
ENS Event | |
|---|---|
04:20 Nov 29, 2005 | |
| Title | Automatic Reactor Trip Following Main Feed Pump Trip |
| Event Description | At 22:19 CST, Main Feedwater Pump B tripped on over current. A secondary plant runback from 100% power was automatically initiated. During the secondary plant runback, the reactor automatically tripped on Steam Generator B low-low level at 22:20 CST.
All three Auxiliary Feedwater pumps automatically started due to low-low Steam Generator level. The plant has been stabilized at Hot Shutdown (RCS temperature approximately 547 degrees F, RCS pressure approximately 2235 psig). Investigation into the cause of the trip is on-going. This event is being reported under 10CFR50.72(b)(2)(iv)(B) for actuation of the reactor protection system (RPS) when the reactor is critical and 10CFR50.72(b)(3)(iv)(A) for valid actuation of the Auxiliary Feedwater System. All control rods fully inserted on the automatic trip. Steam generator water levels have recovered to indicate in the narrow range. The current decay heat removal path is auxiliary feedwater to the steam generators steaming through the power operated relief valves. There are no known primary to secondary leaks. All safety related buses are powered from offsite power. Emergency diesel generators are available and in standby. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Kewaunee Wisconsin (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| Time - Person (Reporting Time:+-2.93 h-0.122 days <br />-0.0174 weeks <br />-0.00401 months <br />) | |
| Opened: | Ethan Treptow 01:24 Nov 29, 2005 |
| NRC Officer: | Pete Snyder |
| Last Updated: | Nov 29, 2005 |
| 42173 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | A/R |
| Before | Power Operation (100 %) |
| After | Hot Standby (0 %) |
Kewaunee | |
WEEKMONTHYEARENS 466662011-03-10T21:49:00010 March 2011 21:49:00
[Table view]10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Inadvertant Opening a Substation Breaker Causing Loss of Station Power ENS 454382009-10-15T17:04:00015 October 2009 17:04:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Momentary Loss of Shutdown Cooling with Autostart of Emergency Diesel Generator ENS 431962007-02-28T05:33:00028 February 2007 05:33:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip During the Performance of a Surveillance ENS 430962007-01-12T16:39:00012 January 2007 16:39:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Turbine Trip/Reactor Trip ENS 429832006-11-10T20:20:00010 November 2006 20:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip at Low Power ENS 429472006-10-30T14:48:00030 October 2006 14:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip ENS 425302006-04-27T01:49:00027 April 2006 01:49:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Failure of Rps Signal to Initiate Reactor Trip ENS 421732005-11-29T04:20:00029 November 2005 04:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Following Main Feed Pump Trip ENS 414252005-02-20T17:58:00020 February 2005 17:58:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Rps Actuation on Steam Generator Low Level 2011-03-10T21:49:00 | |