ENS 41606
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
02:30 Apr 16, 2005 | |
| Title | Plant Shutdown Required by Technical Specifications - Inoperable Emergency Diesel Generator |
| Event Description | Unit 2 Train A emergency diesel generator D5 was removed from service at 0838 CDT on 4/11/05 for surveillance testing and Technical Specification (TS) 3.8.1, 'AC Source - Operating,' Condition B, 'One DG inoperable,' was entered. TS Required Action 3.8.1.B.4 requires D5 be restored to operable status with a Completion Time of 7 days. At 1026 CDT, the test was halted due to high-indicated crankcase pressure on Engine 2 (D5 is a tandem engine generator). The test procedure specifies shutting down the DG if crankcase pressure exceeds 30 mm for more than a few minutes (the setpoint for the crankcase pressure trip is 52 mm).
Investigation of the cause of the high-indicated crankcase pressure on Engine 2 (and whether Engine 1 was effected) started immediately. Unit 2 Train B emergency diesel generator was demonstrated operable by completing a surveillance test at 0423 CDT on 4/12/05. Evaluation of the scope of work to return D5 to operable status and the schedule for completing the work indicated that repairs could not be completed within the 7 days allowed outage time. Based on this assessment an orderly shutdown of Unit 2 is being performed. Shutdown of Unit 2 commenced at 21:30 CDT on 4/15/05. Unit 2 shutdown will continue until D5 is restored to operable status. The licensee intends to issue a press release. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Prairie Island Minnesota (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
| Time - Person (Reporting Time:+-3.95 h-0.165 days <br />-0.0235 weeks <br />-0.00541 months <br />) | |
| Opened: | Jeff Human 22:33 Apr 15, 2005 |
| NRC Officer: | Mike Ripley |
| Last Updated: | Apr 15, 2005 |
| 41606 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (96 %) |
WEEKMONTHYEARENS 502152014-06-20T01:35:00020 June 2014 01:35:00
[Table view]10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown ENS 481862012-08-14T08:12:00014 August 2012 08:12:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Based on Both Emergency Diesels Being Declared Inoperable ENS 438592007-12-21T10:13:00021 December 2007 10:13:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Both Edg'S Being Declared Inoperable ENS 423122006-02-05T19:36:0005 February 2006 19:36:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Required T.S. Shutdown Due to Emergency Diesel Generator Inoperability ENS 416062005-04-16T02:30:00016 April 2005 02:30:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Plant Shutdown Required by Technical Specifications - Inoperable Emergency Diesel Generator ENS 415482005-03-30T13:35:00030 March 2005 13:35:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Shutdown Due to Containment Fan Coil Units Declared Inoperable ENS 412042004-11-18T02:50:00018 November 2004 02:50:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shut Down Due to Both Trains of Containment Cooling System Fan Coil Units Inoperable 2014-06-20T01:35:00 | |