During the performance of Alloy 600 bare metal visual examinations, the presence of
boric acid deposits indicated a leak in a
weld in the
steam generator D (EBB01D) bowl drain line.
This condition is being reported as a degraded condition on the primary coolant system under 10 CFR 50.72 (B)(3)(ii)(A).
During investigation the defect was characterized as a 1/16" rounded indication in the drain line to boss weld.
This condition cannot be found acceptable under ASME Section XI, IWB-3600, 'Analytical Evaluation of Flaws' or ASME Section XI, Table IWB-3410-1, 'Acceptable Standards.'
The [NRC] Resident Inspector has been notified.
- * * UPDATE FROM S. GIFFORD TO J. KNOKE AT 15:10 EDT ON 04/20/05 * *
On 04/20/05 at 12:10 CDT, during the performance of Alloy 600 Bare Metal Visual Examinations, the presence of boric acid deposits indicated a leak in a weld in the Steam Generator C (EBB01C) bowl drain line.
The inspection of Steam Generators A & B showed no presence of boric acid deposits.
The licensee notified NRC Resident Inspector. Notified the R4DO (Shannon).