Licensee reported hot work activities associated with demolition activities were completed at 1545 EST on 11/15/04. The
fire watch had secured at 1615 on 11/15/04 after the hot work was completed for the day. At 0713 EST on 11/16/04 the smell of smoke was detected in the containment foyer. The hot work from the previous day had ignited wood cribbing and other demolition material in the containment building. The containment building was at a negative pressure and no release occurred. The fire was confirmed to be out at 0925. The fire was extinguished by the onsite fire brigade. There were no injuries to personnel. The Haddam Neck Fire Department responded to the scene, but was not required to extinguish the fire. The licensee notified the
CT Department of Environmental Protection, the
CT State Police, and will be contacting the NRC Region 1 Site representative.