ENS 40565
ENS Event | |
|---|---|
18:45 Mar 3, 2004 | |
| Title | Swing Diesel Generator Auto Started from a Bus Undervoltage Valid Signal |
| Event Description | At the time of this occurrence Unit 1 is in a scheduled Refueling Outage and Unit 2 is at 100% Maximum Operating Power. Also note, the 1 B Diesel Generator is a Swing Diesel Generator which is capable of supplying Unit 1 1F 4160 Volt bus and also when required 2F 4160 Volt bus.
At 13:45 EST on 03/03/04, the 1B Diesel Generator auto started due to a momentary Bus Undervoltage sensed on the 1F 4160 volt bus. At the time of the occurrence the 1F 4160 Volt bus was energized with the Normal Supply Breaker racked out and the Alternate Supply Breaker closed in and supplying the 1F 4160 Volt bus. The Normal Supply Breaker was racked out for a scheduled breaker replacement. At the time of the occurrence 2 electricians were removing the Racked Out Normal Supply breaker from the cubicle. The breaker shutter mechanism (a component of the breaker) fell off of the breaker inside the cubicle causing the 1F 4160 Volt bus to sense a momentary bus undervoltage, the Alternate Supply breaker momentarily cycled open and re-closed causing the 1B Diesel Generator to auto start. Since the 1 B Diesel Generator auto started from a valid signal (Bus Undervoltage) an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> report is being made. At the time of this report the 1B Diesel Generator has been Shutdown and restored to a standby Lineup. The 1B Diesel Generator remains Operable. The licensee notified the NRC Resident Inspector.
Subsequent investigation revealed the most probable cause of this event was the trip of the alternate supply breaker to the emergency bus, resulting in its momentary de-energization and an automatic start of the diesel generator on an actual bus undervoltage signal. The alternate supply breaker apparently tripped as a result of the shutter in the formal supply breaker cubicle falling against the fingers of the breaker when as the breaker was being removed from the breaker cubicle. The affected breaker was already n the racked out position. When the breaker was moved to allow its removal from the cubicle, the shutter was apparently forced upward by the movement of the breaker musing the shutter to move upward and the shutter actuating lever to pivot downward until the moc switch mechanism actuated the logic causing the alternate supply breaker to -rip and the diesel generator to start. The shutter actuating lever became separated from the shutter allowing the moc switch to return to its expected open position thereby allowing the alternate supply breaker to recluse and provide power to the bus before the swing diesel generator had sufficient permissives to tie to the bus. Even with the condition found in this breaker cubicle the breaker can be safely racked out. It is when the breaker is removed from the cubicle that there is an increased potential for the shutter and its connected lever arm to cause a logic actuation similar to that experienced in this event. The condition does not create an operability concern for the bus and at most could cause a logic actuation in the conservative direction and does not present any known operability issues for the associated 4160 volt buses. Additional inspections have been performed on 6 balance of plant 4160 volt breakers that are identical in design with acceptable clearances observed in the locations where problems were noted in the subject breaker cubicle. The normal supply breaker for the 1F 4160V bus has been inspected with no problems noted. The associated shutter and lever mechanisms for this breaker have been inspected, components replaced and the breaker returned to service. The alternate supply breaker on the safety related 4160 volt switchgear that was involved in this event was also checked and found to have acceptable clearances and no problems noted with the shutter mechanism. At this point this condition is limited to the breaker cubicle that is the subject of this notification based on extent of condition review performed up this point. There are currently no operability concerns for the affected 4160 volt switchgear or associated diesel generator. Notified R2DO (R. HAAG). |
| Where | |
|---|---|
| Hatch Georgia (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| Time - Person (Reporting Time:+-1.73 h-0.0721 days <br />-0.0103 weeks <br />-0.00237 months <br />) | |
| Opened: | Greg Johnson 17:01 Mar 3, 2004 |
| NRC Officer: | Arlon Costa |
| Last Updated: | Mar 5, 2004 |
| 40565 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 40565\u003C/a\u003E - \u003Ca href=\"/Hatch\" title=\"Hatch\"\u003EHatch\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003ESwing Diesel Generator Auto Started from a Bus Undervoltage Valid Signal\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 40565 - Hatch\n","link":"","lat":31.93298888888889,"lon":-82.34381666666667,"icon":"/w/images/1/14/Southern_Nuclear_icon.png"}],"imageoverlays":null} | |
WEEKMONTHYEARENS 573432024-09-27T07:46:00027 September 2024 07:46:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip on Lowering Condenser Vacuum ENS 570212024-03-11T17:37:00011 March 2024 17:37:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Manual Reactor Trip ENS 568262023-11-01T10:48:0001 November 2023 10:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Manual Reactor Trip Due to Trip of Reactor Feed Pump ENS 564462023-03-31T18:32:00031 March 2023 18:32:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Scram and Automatic Actuation of Containment Isolation Valves (Civs) ENS 556792021-12-29T20:52:00029 December 2021 20:52:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip and Automatic Actuation of Containment Isolation Valves ENS 553942021-08-03T14:26:0003 August 2021 14:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 539532019-03-24T05:59:00024 March 2019 05:59:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Scram Due to Degrading Condenser Vacuum ENS 538932019-02-23T07:12:00023 February 2019 07:12:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Actuation of 2C Emergency Diesel Generator ENS 527002017-04-21T03:45:00021 April 2017 03:45:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Reactor Protection System Actuation While Shutdown ENS 525582017-02-16T18:20:00016 February 2017 18:20:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unexpected Autostart of an Emergency Diesel Generator ENS 519502016-05-23T14:09:00023 May 2016 14:09:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Plant Hatch Unit 2 Containment Isolation Valve Actuation ENS 487602013-02-16T08:10:00016 February 2013 08:10:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Protection System Scram Signal Due to Scram Discharge Volume High Level ENS 487382013-02-10T12:00:00010 February 2013 12:00:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Scram Inserted Due to Degrading Reactor Water Chemistry ENS 473692011-10-24T20:11:00024 October 2011 20:11:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Scram Due to Erratic Irm Indications During Startup ENS 458502010-04-16T23:17:00016 April 2010 23:17:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Loss of Cooling Accident Signal Due to High Drywell Pressure Signal ENS 451482009-06-23T07:51:00023 June 2009 07:51:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram Due to High Reactor Water Level ENS 450712009-05-15T09:19:00015 May 2009 09:19:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Group 1 Isolation of All Main Steam Valves While Performing a Special Procedure ENS 450522009-05-10T14:41:00010 May 2009 14:41:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Intermediate Range Reactor Scram During Transition to Run ENS 450492009-05-08T19:15:0008 May 2009 19:15:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Inadvertant Main Steam Isolation While Performing Maintenance ENS 446792008-11-22T15:18:00022 November 2008 15:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Manual Reactor Scram After Feed Pump Trip ENS 443372008-07-04T12:39:0004 July 2008 12:39:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram on Turbine Trip ENS 440462008-03-07T19:46:0007 March 2008 19:46:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Automatic Reactor Scram with Hpci/Rcic Actuation Due to Loss of Condensate Feedwater ENS 435522007-08-07T19:06:0007 August 2007 19:06:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Scram on Low Reactor Water Level Following Partial Loss of Condensate Feedwater Flow ENS 420962005-10-29T17:25:00029 October 2005 17:25:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event - Main Transformer Fire ENS 417252005-05-23T21:47:00023 May 2005 21:47:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Scram Due to Condenser Hotwell Chemistry ENS 410702004-09-25T05:06:00025 September 2004 05:06:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Group 2 Containment Isolation Actuation ENS 405652004-03-03T18:45:0003 March 2004 18:45:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Swing Diesel Generator Auto Started from a Bus Undervoltage Valid Signal 2024-09-27T07:46:00 | |