05:00 Jan 15, 2004 | |
Title | Part 21 Report Involving an Undersized Emergency Feedwater Pump Shaft |
Event Description | FPL Energy Seabrook has determined that a Substantial Safety Hazard could exist regarding an undersized Emergency Feedwater Pump shaft in accordance with the requirements of 10CFR21. Therefore, FPL Energy Seabrook is reporting this deficiency to the NRC in accordance with 10CFR21. This Part 21 evaluation documents a deficiency in a rotating assembly for an Emergency Feedwater Pump refurbished at the Flowserve Charlotte Service Center - Charlotte, NC.
The defect was an undersized shaft that was .001 inches smaller than the minimum diameter specified by the vendor. The shaft dimensions are considered to be proprietary by the vendor, so the undersized condition could not be identified by FPL Energy Seabrook personnel prior to installation. The undersized shaft was discovered during post-maintenance testing following shaft replacement. The NRC Resident Inspector will be informed. |
Where | |
---|---|
Seabrook New Hampshire (NRC Region 1) | |
Reporting | |
10 CFR 21.21 | |
Time - Person (Reporting Time:+27.1 h1.129 days <br />0.161 weeks <br />0.0371 months <br />) | |
Opened: | Mike Okeeth 08:06 Jan 16, 2004 |
NRC Officer: | Chauncey Gould |
Last Updated: | Jan 16, 2004 |
40453 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 40453\u003C/a\u003E - \u003Ca href=\"/Seabrook\" title=\"Seabrook\"\u003ESeabrook\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EPart 21 Report Involving an Undersized Emergency Feedwater Pump Shaft\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 40453 - Seabrook\n","link":"","lat":42.89886111111111,"lon":-70.85284722222222,"icon":"/w/images/9/9b/NextEra_Energy_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 473952011-10-31T22:00:00031 October 2011 22:00:00
[Table view]10 CFR 21.21 General Electric Cr-120B Relays Supplied by National Technical Systems Fail Bench Test ENS 404532004-01-15T05:00:00015 January 2004 05:00:00 10 CFR 21.21 Part 21 Report Involving an Undersized Emergency Feedwater Pump Shaft 2011-10-31T22:00:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_40453&oldid=428765"